background image

 
HAMWORTHY HEATING LTD 

 

SHERBORNE 

 

500001103/E 

13.4 

Re assemble the fan/transition/burner 

assembly using new gaskets where necessary, and 
refit in reverse order.

 Test all gas joints broken or 

disturbed for soundness before firing

. Re-light 

the boiler, check and adjust the combustion as 
described in 

Section 11.4.

 

 
Check thermostat settings and adjust if required. 
 
Re-fit the boiler cover and tidy floor around boiler as 
necessary. 
 

14.0 REPLACEMENT OF FAILED COMPONENTS 
 

There are a number of components listed below 
which can be replaced simply and quickly by 
following the given procedure. In each case the 
operation of replaced components must be checked 
by carrying out the appropriate part of the 
commissioning procedure. See 

Section 11.0: 

COMMISSIONING & TESTING.  
 
NOTE: Isolate all electrical supplies to the boiler 
and turn off the gas supply before commencing 
any servicing or component exchange 
procedure. 
 

To access the components, remove the screw on 
the top of the outer cover and pull the cover away 
from the wall. The cover is located on the wall frame 
by two ball studs. 
 

14.1 Hot Surface Igniter and Flame Probe 
Assembly.    Part Nos.  563801011 & 533805010  

 

Note :- the igniter and probe ceramics are very 
fragile.

 Reference to Figure 11.5 shows position of 

the igniter and flame probe assembly. Unplug the 
igniter from the harness and remove the single 
socket cap head screw securing the igniter to the 
burner flange. Carefully withdraw the igniter, renew 
as required and generally remove any loose sooty 
deposits, clean as required. Replace igniter and 
secure socket cap head screw holding the igniter to 
the burner flange. Disconnect the flame sensing 
probe connection, remove the single socket cap 
head screw securing the probe to the burner flange 
and carefully withdraw the probe. Renew as 
required and generally remove any loose sooty 
deposits, clean as required.  

Note

 – do not remove both securing screws as the 

separate flange and Mica sight glass will become 
detached.

 

 
14.2 Control Thermostat Renewal  

 
The thermostat consists of a potentiometer and 
remote sensor

. Part nos. 563901312 & 533901378

 
To replace the thermostat or sensor, the following 
procedure must be followed.  

NOTE!

 Record existing temperature setting of 

thermostat for reference before removal. Remove 
the clip securing the thermostat phials in the pocket 
and carefully remove thermostat phials. Remove the 
screw securing the fascia panel to the controls 
housing and carefully lower the front panel and hang 
on the two hooks provided on the control panel 
body. Disconnect the sensor cable plug from the 
PCB and remove the sensor. Prise out the indicator 
disc from the centre of the control knob and loosen 
the collet nut securing the knob to the shaft. Pull off 
the control knob and undo the securing nut on the 
central spindle. Disconnect the potentiometer cable 
plug from the PCB and remove the potentiometer. 
Replace components in reverse order ensuring that 
the sensor is correctly located within the pocket. Do 
not force the bulb into the pocket. When replacing 
the potentiometer knob, rotate the shaft fully 
clockwise and fit the tightening the collet nut. Fit the 
indicator disc aligning the mark with ‘max’ on the 
graduation scale. Refit and secure the fascia panel. 
Run the boiler and turn the thermostat up and down 
to check for correct operation. Set thermostat to 
previously noted setting.

 

 
14.3 Temperature Limiter (Limit Stat) Renewal.  
Part Nos. 533901179 
 

Remove the 'push on' spade connections from the 
temperature limiter body noting position of coloured 
cables. Remove plastic cover (if fitted) and unscrew 
holding nut to detach temperature limiter from 
housing. Remove the bulb from the heat exchanger 
pocket and check the operation of the device by 
carefully applying a heat source to the bulb. Set 
temperature limiter to 100

°

C and re-assemble 

temperature limiter ensuring correct cable notation. 
Refer to thermostat diagram if terminal identification 
differs from those given in Figure 9.1 (Boiler 
schematic wiring diagrams). 

 
14.4 Main Gas Valve / Venturi 
Part No. 533903033

 

 

Note:

 the gas valve and venturi are supplied as a 

matched and factory set assembly and must not be 
tampered with or adjusted. 

1)

 To replace the gas valve/venturi it is preferable to 

remove the complete fan assembly. 

2)

 Unplug the connectors from the fan (two) and the 

gas valve. Remove the 4xM4 screws securing the 
die-cast gas valve inlet elbow to the gas valve taking 
care not to loose the ‘O’ ring. 

3)

 Disconnect the pressure feedback tube from the 

gas valve. Remove the 4xM5 screws/nuts securing 
the fan/venturi/gas valve assembly to the transition 
duct. 

Note

 the use of a spacer on the screw/nut 

nearest to the heat exchanger casting. Withdraw the 
assembly from the air inlet duct.  

4)

 Remove the 2xM5 screws securing the venturi/

gas valve assembly to the fan noting the cork 
sealing gasket.  

5)

 Remove the copper feedback connecting elbow 

34 

Содержание Sherborne Series

Страница 1: ...G OPERATING OR SERVICING EQUIPMENT Sherborne Series Boilers Room Sealed Fully Modulating Pre Mix Gas Fired Boilers for Heating and Domestic Hot Water Installations Installation Commissioning and Servi...

Страница 2: ...ating safely and efficiently Maintenance Agreements 01202 662555 Regular routine servicing of equipment by Hamworthy service engineers inspects the safety and integrity of the plant reducing the risk...

Страница 3: ...ASE ENSURE RELEVANT INFORMATION REQUIRED WITHIN DOCUMENT IS FOUND RELATING TO SPECIFIC GAS TO BE FIRED BEFORE FIRING BOILER THIS BOILER COMPLIES WITH ALL RELEVANT EUROPEAN DIRECTIVES EC TYPE CERTIFICA...

Страница 4: ...6 3 Design Waste Gas Volume and Temperature 6 4 Maximum Length of Flue Duct 6 5 Disconnection 6 6 Flue Discharge 6 7 Surface Temperatures 6 8 Flue System Location 7 0 AIR SUPPLY 12 7 1 Air Supply By...

Страница 5: ...tion 10 6 Gas Connection 10 7 Fitting the Control Panel 10 8 Fitting the Front Cover 11 0 COMMISSIONING AND TESTING 24 11 1 Electrical Installation 11 2 Gas Installation 11 3 Water Circulation System...

Страница 6: ...gure 8 12 Site Wiring Diagram 15 16 Figure 9 1 Wiring Schematic 17 Figure 10 3 1 Connection of Flue System Concentric Ducts Horizontal 19 Figure 10 3 1 1 Connection of Flue System Concentric Ducts Hor...

Страница 7: ...boiler s off should a high or low pressure fault occur Note The boiler is not suitable for direct connection to domestic hot water supplies or gravity circulation systems The pressurisation unit must...

Страница 8: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E Figure 1 1 Boiler Installation Typical 2...

Страница 9: ...0 150 150 30 Hole Gas 3 4 Electric M20 Electric M20 Cover removal clearance 30 Return 50 Flow 200 Flue 76 Flow 140 Flue 154 Return 185 460 280 600 A B 800 Water connections 85 200 320 Boiler Model Ret...

Страница 10: ...RAL DATA Sherborne S65 Sherborne S70C Boiler Input kW Gross maximum 77 7 Boiler Input kW Nett maximum 70 0 Boiler Input kW Gross minimum 15 5 Boiler Input kW Nett minimum 14 5 Boiler Output kW minimum...

Страница 11: ...ll relevant information but the following extracts from the above references are emphasised since failure to comply with these requirements will almost certainly result in an unsatisfactory installati...

Страница 12: ...Any combustible material adjacent to the boiler and the flue system must be so placed or shielded to ensure that its temperature does not exceed 65 C Further details regarding boiler location are give...

Страница 13: ...Drain The boiler is provided with a condense drain suitable for connection to 22mm plastic waste pipe not supplied which must be connected to a tundish not supplied Discharge piping from a tundish sh...

Страница 14: ...al terminal 007 Assembly 80 125 Wall plate 125 014 Ref 028 Ref 100 150 90 Concentric Bend Ref 027 45 Concentric Bend 100 150 100 150 Adjustable 100 150 x 1m long 029 030 Ref Concentric Flue Ref Concen...

Страница 15: ...ce Eccentric Adaptor Flue type C33 150 x 100 80 100 80 Flue Support Bend Ref 020 Ref 043 023 Ref Ref 001 Ref 029 Ref 030 Ref 033 027 Ref 028 Ref 038 Ref 044 Ref Ref 032 Flat Roof Flashing Adjustable F...

Страница 16: ...let 0 4m min 10m max Ref 023 Ref 001 80 Flue Support Bend Outlet 0 4m min 10m max 80 100 Outlet 10m max Inlet 10m max Single Flue Single Flue Single Flue 250 long 100 1000 long 100 500 long 100 Wall C...

Страница 17: ...000 long 100 Single Flue Ref 026 Vertical terminal 100 Flue Ref 023 80 100 Eccentric Adaptor Ref 017 Wall Clamp 100 Ref 022 021 Ref 020 Ref Single Flue 500 long 100 1000 long 100 Single Flue Single Fl...

Страница 18: ...ve a total minimum free area of Low Level inlet 550cm2 per boiler High Level outlet 275cm2 per boiler 7 2 Air Supply Room sealed installation If the Sherborne boiler is installed as a room sealed boil...

Страница 19: ...d between the boiler and the first water isolating valve The minimum bore mm of these pipes per installation is as follows The vent pipe must rise continually must not be valved except by a design whi...

Страница 20: ...759 Part 1 for information See also BS 6880 Part 1 for design considerations 8 12 1 Boiler Control Schemes 8 12 2 Single Boiler Installations For single boiler installations the Sherborne range of boi...

Страница 21: ...R 2 BOILER NUMBER 3 TO HAMWORTHY HEATING LIMITED MILTON BOILER SEQUENCE CONTROL REFER TO MILTON INSTALLATION MANUAL FOR FURTHER DETAILS NOTE VOLT FREE CONTACT TERMINALS NOT SHOWN FOR CLARITY CONTACT T...

Страница 22: ...PUTS CONTROL INPUT CONTROL INPUT ROTARY SWITCH SW1 ROTARY SWITCH SW1 ROTARY SWITCH SW1 ROTARY SWITCH SW1 BOILER MODULE NUMBER 1 BOILER MODULE NUMBER 2 SEQUENCING INTERFACE MODULE SEQUENCING INTERFACE...

Страница 23: ...9 9 10 10 2 1 4 3 2 1 3 4 5 BN GN YE BU 1 2 3 4 5 GAS VALVE 2 1 3 1 2 1 2 HSI PROBE 1 2 1 TEST POINT FLAME SIGNAL 1 2 3 1 2 3 4 GND PWM GND HS DC SERVO FAN V N L 2 1 3 4 5 1 2 3 GN YE BN BU GN YE 1 2...

Страница 24: ...ame mains isolator as the boiler it is fitted to A 0 10V analogue control signal from the external sequence control system is required ground and signal connections The interface module is configured...

Страница 25: ...ommissioning a check has been made to ensure that the pipe is clear and free from obstruction 10 3 1 Connection of Through Wall Horizontal Balanced Flue Terminal 80 125mm The flue terminal should be c...

Страница 26: ...sary In terminating the flue system ensure that the joint through the wall roof is made good and weatherproofed Whilst carrying out the above procedure ensure that all seals are correctly located and...

Страница 27: ...acksaw or jigsaw carefully cut around the inside of the recess to provide the flue outlet Having fitted the flue system to the boiler carefully refit the burner assembly and secure to the heat exchang...

Страница 28: ...ody Secure the conduit adapters to the wall frame and the control panel and fit the flexible conduits Feed the cables through the conduits connecting to the appropriate connections on the PCB see Figu...

Страница 29: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E Figure 10 6 Gas Pipe Fitting 23...

Страница 30: ...should attempt the following Before attempting to commission any boiler ensure that personnel involved are aware of what action is about to be taken and begin by making the following checks 1 Flueway...

Страница 31: ...Switch Gas Supply Isolating Valve Control Panel Lockout Reset Button Control Thermostat Limit Thermostat Fan Venturi Gas Valve Air Inlet Chamber Flue Outlet Wall Frame Condensing Models Only Position...

Страница 32: ...WORTHY HEATING LTD SHERBORNE 500001103 E Figure 11 2 Gas Valve Venturi Arrangement Figure 11 5 Position of Probes on Burner Assembly 92 max 88 min 40 min 42 max 49 min 51 max 7 1 3 2 18 25 11 5 16 17...

Страница 33: ...e module disconnect the manometer and close the pressure test point Record all readings for future reference on the relevant commissioning sheet Isolate the electrical supply and rotate SW1 to set the...

Страница 34: ...hen the supply has been restored 12 1 2 Fault Finding Procedures General fault finding is shown in Figures 12 1 to 12 4 If the boiler still cannot be operated satisfactorily after following the chart...

Страница 35: ...the sump casting Remove the 2xM6 screws securing the condense trap to the sump and disconnect the section of pipe routed back to the wall frame S65 Model support the sump from underneath and remove t...

Страница 36: ...ler main PCB set correctly Is the on off switch on Fascia power on indicator illuminated Is the temperature limiter reset Fascia overheat indicator illuminated Check fuses and supply connections Check...

Страница 37: ...the flame signal above the minimum 1 2 A Is there an HSI signal from the ignition controller Is there power to the HSI probe Check wiring connections to ignition controller Check fan control wiring co...

Страница 38: ...sequence control switches to high fire Continued Ref Fig 12 4 Insufficient water circulation Temperature control circuit faulty Temperature control set above Milton control temperature Boiler under Mi...

Страница 39: ...nning at wrong speed or running when should be stopped Condensate Drain Trap Blocked Condensing models only Overheat high limit thermostat tripped Premature flame detection Flame sensing circuit fault...

Страница 40: ...thermostat phials Remove the screw securing the fascia panel to the controls housing and carefully lower the front panel and hang on the two hooks provided on the control panel body Disconnect the sen...

Страница 41: ...casting Withdraw the assembly from the air inlet duct 4 Remove the 2xM5 screws securing the venturi gas valve assembly to the fan noting the cork sealing gasket 5 Re assemble in reverse order using n...

Страница 42: ...380 Boiler main PCB S70c Nat Gas 533901381 Boiler main PCB S65 LPG 533901415 Boiler main PCB S70c LPG 533901416 Fascia PCB 533901382 Ignition Sequence Controller 533901379 Fan assembly 533901376 Contr...

Страница 43: ...37mbar The following tables and paragraphs using the same numbering system as the main installer s guide highlight the different values and procedures to be used when firing propane and should be used...

Страница 44: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E USEFUL USER INFORMATION INSTALLER SITE ADDRESS DATE OF COMMISSIONING BOILER TYPE BOILER SIZE S UNIT NO S SERIAL NO S FLUE NOTES 38...

Страница 45: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E NOTES 39...

Страница 46: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E NOTES 40...

Страница 47: ...Notes...

Страница 48: ...y reserves the right to make changes and improvements which may necessitate alteration to the specification without prior notice Connect direct Direct Dial Telephone and Fax Numbers Direct Email Addre...

Отзывы: