background image

 
HAMWORTHY HEATING LTD 

 

SHERBORNE 

 

500001103/E 

11.7  Installation Noise 
 

In order to avoid the possibility of noise from the 
installation, care should be taken to follow the 
manufacturer’s instructions. Particular attention 
should  be  paid  to  minimum  water  flow  rates.  If  in 
doubt contact the manufacturer. 
 

11.8  User Instructions 
 

When the above is complete, the boiler owner or their 
representative should be made aware of the lighting 
and operating instructions. A practical demonstration 
should be given describing each functional step. This 
Installer's Guide and user's instructions should then 
be handed over and be kept in a safe place for easy 
reference. 
 

12.0 FAULT FINDING

 

 

12.1 Fault Finding  
 
12.1.1 Safety Features Summary 

 
Should the control thermostat fail, the temperature 
limiter will trip thus creating an immediate shutdown 
regardless of firing mode. An overheat neon on the 
controls fascia will indicate this condition has 
occurred. If, after pushing the overheat reset button, 
the neon on the fascia does not extinguish and the 
boiler does not fire up, it could be that the boiler is still 
too hot, i.e. the limit thermostat has not re-set - see 
Figure 11. Allow the boiler to cool down. An 
investigation should be carried out to ascertain the 
reason for the overheating. An obvious reason would 
be too low a water flow rate through the boiler. 
 
The flame is under constant supervision by the 
burner sequence controller. This is accomplished by 
measuring the flame's ability to rectify an AC current. 
If the flame diminishes for whatever reason and the 
rectified current drops below the controllers minimum 
detection current (1.2 µA DC), the controller will 
induce a lockout within 1 second, which will require a 
manual re-set (situated on the controls fascia) to re-
start the control sequence - see Figure 11. Failure to 
establish and detect a flame during the light up 
sequence, results in burner shutdown and lockout 
within 5 seconds. If the boiler continues to lockout, 
then an investigation must be made to ascertain the 
cause. See Figures 12.1 to 12.4 for possible 
corrective scenarios. False flame signals at the start 
and during purge will cause the boiler to lockout. 
 
Restoration of the power supply after an interruption, 
results in a full light up sequence to safely restart the 
burner. Power failure after a lockout, will not interfere 
with this condition when the supply has been 
restored. 

 
12.1.2 Fault Finding Procedures 
 

General fault finding is shown in Figures 12.1 to 12.4. 

If the boiler still cannot be operated satisfactorily after 
following the chart, consult the local office of 
Hamworthy Heating for assistance. 

 
12.1.3 Possible Causes Of Boiler Lockout 

 
1) Ignition failure due to no power at the Hot Surface  
Igniter. 
2) Ignition failure due to faulty gas valve. 
3) Ignition failure due to broken igniter or flame probe 
lead. 
4) No ignition due to faulty controller. 
5) Ignition failure due to blockage in the flue or air 
ducts. 
6) Ignition failure due to gas supply problem. 
 

13.0 SERVICING 

 
A competent person registered for working on non 
domestic gas appliances should check and ensure 
that the flue, its support and terminal, the ventilation 
to the boiler house, safety valve, drain, water filter if 
fitted, pressure gauge, etc.; are in a serviceable and 
working condition and still comply with the relevant 
standards and codes of practice - see 

Section 3. 

 
13.1 Regular annual servicing is recommended

preferably by a Hamworthy appointed person, to 
ensure trouble free operation. Although cleaning of 
flueways may not be necessary on a yearly basis, it is 
important that all controls and safety features are 
checked for correct operation.  

NOTE!

 Measuring flue gas CO

2

 and gas 

temperatures will give an indication of the state of the 
boiler flueways and waterways. Results should be 
compared with previously measured values to 
establish possible loss of efficiency. 
 

13.2 Annual Service 
 

The procedure detailed relates to a single boiler and 

MUST

 be carried out on ALL individual modules 

which constitute an installation. Before servicing the 
boiler, the following procedure must be carried out :-  

WARNING: Isolate all electrical supplies and turn 
off the gas service valve. 

 

1)

 Remove the screw on the top of the outer cover 

and pull the cover away from the wall. The cover is 
located on the wall frame by four ball studs. 

2)

 Disconnect the flame probe lead at the probe, and 

the igniter lead at the plug and socket. Unplug the 
connectors from the fan (two) and the gas valve. 
Disconnect the 15mm gas connection to the gas 
valve inlet. 

3)

 Remove the front screw and loosen the rear screw 

securing the fascia panel to the controls panel body. 
Carefully withdraw the fascia panel and secure on the 
two hooks on the control panel body. Unplug the 
condense level switch from the PCB and feed the 
connector through the grommet in the rear of the 
controls panel ( S70C only). Refit the fascia panel. 

4)

 Remove the 2 – M10 nuts and washers securing 

28 

Содержание Sherborne Series

Страница 1: ...G OPERATING OR SERVICING EQUIPMENT Sherborne Series Boilers Room Sealed Fully Modulating Pre Mix Gas Fired Boilers for Heating and Domestic Hot Water Installations Installation Commissioning and Servi...

Страница 2: ...ating safely and efficiently Maintenance Agreements 01202 662555 Regular routine servicing of equipment by Hamworthy service engineers inspects the safety and integrity of the plant reducing the risk...

Страница 3: ...ASE ENSURE RELEVANT INFORMATION REQUIRED WITHIN DOCUMENT IS FOUND RELATING TO SPECIFIC GAS TO BE FIRED BEFORE FIRING BOILER THIS BOILER COMPLIES WITH ALL RELEVANT EUROPEAN DIRECTIVES EC TYPE CERTIFICA...

Страница 4: ...6 3 Design Waste Gas Volume and Temperature 6 4 Maximum Length of Flue Duct 6 5 Disconnection 6 6 Flue Discharge 6 7 Surface Temperatures 6 8 Flue System Location 7 0 AIR SUPPLY 12 7 1 Air Supply By...

Страница 5: ...tion 10 6 Gas Connection 10 7 Fitting the Control Panel 10 8 Fitting the Front Cover 11 0 COMMISSIONING AND TESTING 24 11 1 Electrical Installation 11 2 Gas Installation 11 3 Water Circulation System...

Страница 6: ...gure 8 12 Site Wiring Diagram 15 16 Figure 9 1 Wiring Schematic 17 Figure 10 3 1 Connection of Flue System Concentric Ducts Horizontal 19 Figure 10 3 1 1 Connection of Flue System Concentric Ducts Hor...

Страница 7: ...boiler s off should a high or low pressure fault occur Note The boiler is not suitable for direct connection to domestic hot water supplies or gravity circulation systems The pressurisation unit must...

Страница 8: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E Figure 1 1 Boiler Installation Typical 2...

Страница 9: ...0 150 150 30 Hole Gas 3 4 Electric M20 Electric M20 Cover removal clearance 30 Return 50 Flow 200 Flue 76 Flow 140 Flue 154 Return 185 460 280 600 A B 800 Water connections 85 200 320 Boiler Model Ret...

Страница 10: ...RAL DATA Sherborne S65 Sherborne S70C Boiler Input kW Gross maximum 77 7 Boiler Input kW Nett maximum 70 0 Boiler Input kW Gross minimum 15 5 Boiler Input kW Nett minimum 14 5 Boiler Output kW minimum...

Страница 11: ...ll relevant information but the following extracts from the above references are emphasised since failure to comply with these requirements will almost certainly result in an unsatisfactory installati...

Страница 12: ...Any combustible material adjacent to the boiler and the flue system must be so placed or shielded to ensure that its temperature does not exceed 65 C Further details regarding boiler location are give...

Страница 13: ...Drain The boiler is provided with a condense drain suitable for connection to 22mm plastic waste pipe not supplied which must be connected to a tundish not supplied Discharge piping from a tundish sh...

Страница 14: ...al terminal 007 Assembly 80 125 Wall plate 125 014 Ref 028 Ref 100 150 90 Concentric Bend Ref 027 45 Concentric Bend 100 150 100 150 Adjustable 100 150 x 1m long 029 030 Ref Concentric Flue Ref Concen...

Страница 15: ...ce Eccentric Adaptor Flue type C33 150 x 100 80 100 80 Flue Support Bend Ref 020 Ref 043 023 Ref Ref 001 Ref 029 Ref 030 Ref 033 027 Ref 028 Ref 038 Ref 044 Ref Ref 032 Flat Roof Flashing Adjustable F...

Страница 16: ...let 0 4m min 10m max Ref 023 Ref 001 80 Flue Support Bend Outlet 0 4m min 10m max 80 100 Outlet 10m max Inlet 10m max Single Flue Single Flue Single Flue 250 long 100 1000 long 100 500 long 100 Wall C...

Страница 17: ...000 long 100 Single Flue Ref 026 Vertical terminal 100 Flue Ref 023 80 100 Eccentric Adaptor Ref 017 Wall Clamp 100 Ref 022 021 Ref 020 Ref Single Flue 500 long 100 1000 long 100 Single Flue Single Fl...

Страница 18: ...ve a total minimum free area of Low Level inlet 550cm2 per boiler High Level outlet 275cm2 per boiler 7 2 Air Supply Room sealed installation If the Sherborne boiler is installed as a room sealed boil...

Страница 19: ...d between the boiler and the first water isolating valve The minimum bore mm of these pipes per installation is as follows The vent pipe must rise continually must not be valved except by a design whi...

Страница 20: ...759 Part 1 for information See also BS 6880 Part 1 for design considerations 8 12 1 Boiler Control Schemes 8 12 2 Single Boiler Installations For single boiler installations the Sherborne range of boi...

Страница 21: ...R 2 BOILER NUMBER 3 TO HAMWORTHY HEATING LIMITED MILTON BOILER SEQUENCE CONTROL REFER TO MILTON INSTALLATION MANUAL FOR FURTHER DETAILS NOTE VOLT FREE CONTACT TERMINALS NOT SHOWN FOR CLARITY CONTACT T...

Страница 22: ...PUTS CONTROL INPUT CONTROL INPUT ROTARY SWITCH SW1 ROTARY SWITCH SW1 ROTARY SWITCH SW1 ROTARY SWITCH SW1 BOILER MODULE NUMBER 1 BOILER MODULE NUMBER 2 SEQUENCING INTERFACE MODULE SEQUENCING INTERFACE...

Страница 23: ...9 9 10 10 2 1 4 3 2 1 3 4 5 BN GN YE BU 1 2 3 4 5 GAS VALVE 2 1 3 1 2 1 2 HSI PROBE 1 2 1 TEST POINT FLAME SIGNAL 1 2 3 1 2 3 4 GND PWM GND HS DC SERVO FAN V N L 2 1 3 4 5 1 2 3 GN YE BN BU GN YE 1 2...

Страница 24: ...ame mains isolator as the boiler it is fitted to A 0 10V analogue control signal from the external sequence control system is required ground and signal connections The interface module is configured...

Страница 25: ...ommissioning a check has been made to ensure that the pipe is clear and free from obstruction 10 3 1 Connection of Through Wall Horizontal Balanced Flue Terminal 80 125mm The flue terminal should be c...

Страница 26: ...sary In terminating the flue system ensure that the joint through the wall roof is made good and weatherproofed Whilst carrying out the above procedure ensure that all seals are correctly located and...

Страница 27: ...acksaw or jigsaw carefully cut around the inside of the recess to provide the flue outlet Having fitted the flue system to the boiler carefully refit the burner assembly and secure to the heat exchang...

Страница 28: ...ody Secure the conduit adapters to the wall frame and the control panel and fit the flexible conduits Feed the cables through the conduits connecting to the appropriate connections on the PCB see Figu...

Страница 29: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E Figure 10 6 Gas Pipe Fitting 23...

Страница 30: ...should attempt the following Before attempting to commission any boiler ensure that personnel involved are aware of what action is about to be taken and begin by making the following checks 1 Flueway...

Страница 31: ...Switch Gas Supply Isolating Valve Control Panel Lockout Reset Button Control Thermostat Limit Thermostat Fan Venturi Gas Valve Air Inlet Chamber Flue Outlet Wall Frame Condensing Models Only Position...

Страница 32: ...WORTHY HEATING LTD SHERBORNE 500001103 E Figure 11 2 Gas Valve Venturi Arrangement Figure 11 5 Position of Probes on Burner Assembly 92 max 88 min 40 min 42 max 49 min 51 max 7 1 3 2 18 25 11 5 16 17...

Страница 33: ...e module disconnect the manometer and close the pressure test point Record all readings for future reference on the relevant commissioning sheet Isolate the electrical supply and rotate SW1 to set the...

Страница 34: ...hen the supply has been restored 12 1 2 Fault Finding Procedures General fault finding is shown in Figures 12 1 to 12 4 If the boiler still cannot be operated satisfactorily after following the chart...

Страница 35: ...the sump casting Remove the 2xM6 screws securing the condense trap to the sump and disconnect the section of pipe routed back to the wall frame S65 Model support the sump from underneath and remove t...

Страница 36: ...ler main PCB set correctly Is the on off switch on Fascia power on indicator illuminated Is the temperature limiter reset Fascia overheat indicator illuminated Check fuses and supply connections Check...

Страница 37: ...the flame signal above the minimum 1 2 A Is there an HSI signal from the ignition controller Is there power to the HSI probe Check wiring connections to ignition controller Check fan control wiring co...

Страница 38: ...sequence control switches to high fire Continued Ref Fig 12 4 Insufficient water circulation Temperature control circuit faulty Temperature control set above Milton control temperature Boiler under Mi...

Страница 39: ...nning at wrong speed or running when should be stopped Condensate Drain Trap Blocked Condensing models only Overheat high limit thermostat tripped Premature flame detection Flame sensing circuit fault...

Страница 40: ...thermostat phials Remove the screw securing the fascia panel to the controls housing and carefully lower the front panel and hang on the two hooks provided on the control panel body Disconnect the sen...

Страница 41: ...casting Withdraw the assembly from the air inlet duct 4 Remove the 2xM5 screws securing the venturi gas valve assembly to the fan noting the cork sealing gasket 5 Re assemble in reverse order using n...

Страница 42: ...380 Boiler main PCB S70c Nat Gas 533901381 Boiler main PCB S65 LPG 533901415 Boiler main PCB S70c LPG 533901416 Fascia PCB 533901382 Ignition Sequence Controller 533901379 Fan assembly 533901376 Contr...

Страница 43: ...37mbar The following tables and paragraphs using the same numbering system as the main installer s guide highlight the different values and procedures to be used when firing propane and should be used...

Страница 44: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E USEFUL USER INFORMATION INSTALLER SITE ADDRESS DATE OF COMMISSIONING BOILER TYPE BOILER SIZE S UNIT NO S SERIAL NO S FLUE NOTES 38...

Страница 45: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E NOTES 39...

Страница 46: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E NOTES 40...

Страница 47: ...Notes...

Страница 48: ...y reserves the right to make changes and improvements which may necessitate alteration to the specification without prior notice Connect direct Direct Dial Telephone and Fax Numbers Direct Email Addre...

Отзывы: