HAMWORTHY HEATING LTD
9
PUREWELL
Variheat mk2
218612 A03
Figure 4.4 – Water Connection Points
4.4 Water Supply
Feed and Expansion tanks to comply with static height requirements of BS6880 & BS6644.
Cold feed and open vent pipes to comply with requirements of BS 6644.
Pressurised system to comply with BS 7074.
It is recommended that the system pipework is flushed twice before water treatment.
In hard water areas (>180mg CaCO
3
/litre) precautions such as water treatment are strongly recommended to
prevent the build up of sludge and scale and also to control the system water pH to between 7.0 & 8.0.
Leaks in the system pipe work should be fixed to prevent dilution of water treatment.
Maximum working water pressure is 6 bar.
For minimum water pressure see Appendix ‘E’ - Water Data (Page 45)
Flow Connection
Return Connection
Model Type
PV70c, 95c & 110c
Model Type
PV140c & 180c