HAMWORTHY HEATING LTD
41
PUREWELL VariHeat he
500001155/F
APPENDIX B - ELECTRICAL CONNECTIONS AND CONTROLS
ELECTRICAL DATA
Model
65 he
85 he
105 he
125 he
Normal Supply Voltage
230V ~ 50Hz
Power Consumption (maximum)*
-
W
554
667
Start and Run Current (per boiler)
-
A
0.54
0.6
Figure B1.1 - Electrical Supply
*Where The max allowable power output from the IEC Outlet is 460 W (fitted with A T2A fuse).
IMPORTANT: Individual boiler must be earthed.
The boiler must be isolated from the mains electricity supply in the event of electric arc
welding being carried out on any connecting pipework.
1.1
Wiring external to the boiler must be installed in accordance with the IEE Regulations and any local
regulations which apply. Wiring must be completed in heat resistant 3-core cable of 1.0mm² cross sectional area.
Boilers are normally supplied for connection to a 230 volts, 50Hz mains supply. The BIC 930 control is supplied
with a replaceable fuse (T1.25A). External fuses should be 6A for all boiler modules.
1.2
3-Phase Electrical Supplies. Banks of Vari
Heat
he boilers and boilers installed in close proximity to each other
MUST NOT
be supplied from different phases of a 3 phase supply. The method of connection to the mains
electricity supply must facilitate complete electrical isolation of the single boiler with a separation of at least 3mm
in all poles.
1.3
A mains isolator must be provided adjacent to each boiler in a readily accessible position. The supply should
only serve the boiler.
1.4
Volt free contact electrical supplies must be isolatable where fitted.
1.5
Further details regarding connection to the electricity supply are given in BS EN 60335, Part 1.
WARNING: THE MAINS POWER SUPPLY MUST NOT BE SWITCHED
BY A TIME-CLOCK CONTROL.
CAUTION: DO NOT FEED MAINS VOLTAGE ONTO THE TIMER TERMINALS
1.6
The mains power supply must be maintained at all times. Each Purewell VariHeat he boiler incorporates a
remote stop/start loop, which can be used to operate the boiler(s) under a timed regime. The boiler controls
provide a 30V DC signal that can be fed through a volt free contact for operation. Refer to BS 6644 for further
information on installing the electrical supply.
NOTE:
FOR ELECTRICAL CONNECTIONS TO BOILER SEE FIGURE 4.5 (Page 9)
FOR BOILER WIRING SCHEMATIC SEE FIGURE 9.0 (Page 31)
FOR MULTIPLE BOILER WIRING DIAGRAM SEE FIGURE B1.1 (Page 41)
FOR CONTROL WIRING SEE FIGURE E1.3.1 TO E1.3.4 (Pages 50 & 51)