7.  Operating conditions 

7.1.  Fuels 

The Melbury HE boiler is designed for operation with fuel oil EL and natural gas. 

 

 

Attention:  The use of other fuels such as for example biogas is only permitted with the express approval of the 

manufacturer. 

 

 

7.2.  Combustion air 

The combustion air must not have high dust concentrations. 
Important: Furthermore, it must be free of halogens (chlorine and fluorine compounds). An excessive presence 

of halogen in the combustion air leads to great corrosion damage. Make sure that no paints, 

thinners, cleaning agents, degreasing agents, solvents, chlorine containers, etc. are stored in the 

boiler room! 

 

 

7.3.  Filling the installation and water quality 

The installation must be thoroughly rinsed before it is finally filled. 
When filling for the first time and refilling, check the quality of the water in accordance with the values 

recommended in chapter 4.3. Poor water quality leads to damage in heating installations from calcification and 

corrosion. On the other hand, the service life, functional reliability and efficiency can be increased using 

appropriately treated water. 
During the filling process, the circulation pumps should be switched off and all ventilating valves opened, so that 

the air in the system can completely escape. The filling process is finished when the operating pressure has 

been reached. 

 

 

7.4.  Protection against corrosion 

Normally, no corrosion problems arise if systems are properly designed and installed and are run according to 

these instructions; consequently, there is no need to use chemical additives. However, if water is of poor quality 

or if oxygen seeps from the air into the heating system (expansion chambers open, expansion/supply chambers 

too small, plastic tubes without diffusion blocking in floor heating) damages are something which cannot be 

completely excluded. If you happen to use chemical additives in your system, make sure that they are effective, 

harmless and above all appropriate for the materials your system is made of. Enquire with your chemical additive 

supplier. 
In this case, you will need to arrange for a specialist water company to carry out annual quality checks on the 

water used in the heating system in order to avoid any damage to the system. 

 

 

7.5.  Requirements for operation 

The maximum operating pressure and the maximum temperature to be observed are listed on the type plate. The 

minimum temperatures to be observed are given in chapter 4.1. 
It is strictly recommended to maintain the boiler in operation during several hours after a cold start-up in order to 

evaporate condensates that are inevitably formed in any boiler during cold start-up. 

Содержание Melbury HE 530

Страница 1: ...Manual Melbury GB doc edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF Installation and operating instructions Melbury HE C 530 3000...

Страница 2: ......

Страница 3: ...al equipment 20 5 4 Heating regulators 20 5 5 Cable sets 20 6 Installation guide 21 6 1 Boiler room and boiler room ventilation 21 6 2 Planning dimensions 21 6 3 Hydraulic connection 23 6 4 Electrical...

Страница 4: ...parts of the body or without wearing shoes When the unit is not to be used for a longer period the main power switch on the electrical control panel must be switched off and the manual valve on the un...

Страница 5: ...e control and safety mechanisms required by local regulations in force The line must be free from all impurities take particular care that foreign matter does not enter the line during installation Oi...

Страница 6: ...kept down to a minimum and thermal radiation can be further reduced A revolving door gives easy access to parts of the boiler that are in contact with combustion gases This allows cleaning of combusti...

Страница 7: ...pe of supply Boiler body with recuperator in Melbury HE C version flue gas collector and flue gas tube Gas tight boiler door with insulation and burner connection and flue gas fan connection if ordere...

Страница 8: ...es must be thoroughly cleaned The purpose of this initial cleaning is to eliminate germs and residue that can cause deposits to form In new installations in particular residue from grease oxidized met...

Страница 9: ...uipment materials and quickly disappears Without refreshing the oxygen through significant contributions of water the unit might not experience any damage whatsoever However it is important to follow...

Страница 10: ...ations of the boiler must be as low as possible to ensure the highest service life The first heating must allow the evacuation of moisture from concrete doors it is necessary to avoid any heat shock a...

Страница 11: ...0 150 150 200 200 200 238 238 274 292 318 344 Distance supply return j mm 950 950 950 1150 1150 1150 1493 1493 1727 1844 2000 2168 Discharge height k mm DN 80 1 100 1 100 1 115 1 115 1 125 1 110 1 110...

Страница 12: ...25 1 1 1 0 1 1 1 0 1 1 07 1 1 03 1 1 00 1 1 1 0 1 Distance recuperator water studs recup backside m mm 285 285 285 305 305 335 385 385 455 flow return recuperator n DN 65 80 80 80 80 100 100 100 125...

Страница 13: ...for the operating pressures of 4 8 and 10 bar g Their dimensions and performances are identical to those of the standard range of 6 bar g but their weights are different Empty weights Melbury HE 530 5...

Страница 14: ...2674 2854 3096 3356 b mm 1000 1060 1130 1210 1300 1375 1445 1570 1645 c1 mm 661 712 740 790 863 875 905 965 1027 c2 mm 480 552 565 605 650 690 779 840 845 d mm 900 900 1000 1070 1210 1290 1360 1480 1...

Страница 15: ...60 80 min qF 94 8 94 9 94 9 94 9 94 9 95 0 95 0 95 0 95 0 95 0 95 1 95 0 E C fficiency DIN4702 8 60 75 C N 94 4 94 6 94 5 94 8 94 6 94 8 94 8 94 7 94 6 94 7 94 8 94 7 Mass flows Fuel oil flow max 1 kg...

Страница 16: ...low NG type E max 1 2 nm 3 h 58 7 63 4 69 3 76 2 87 9 97 0 125 2 142 7 182 1 208 6 273 4 331 1 min 1 2 10 0 12 9 12 9 18 1 18 1 27 4 33 5 33 5 38 5 47 8 75 9 74 9 Exhaust gas mass flow max wet kg s 0...

Страница 17: ...5 16 0 17 5 21 5 22 5 29 5 34 5 37 0 45 0 55 0 73 0 84 0 Values at 3zugskessel V 01 07 lamda 1 2 CO2 12 7 OG T air 20 C rel humidity 60 p baro 100kPa 1 Boiler at 60 80 C 2 Boiler at 50 70 C Technical...

Страница 18: ...ght to make changes to dimensions and construction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF 4 7 2 Water resistance of recuperators for Melbury C Pressure resistance in relation to wat...

Страница 19: ...an average boiler water temperature of tm 70 C Since the minimum power of the boiler is limited by the minimum allowable flue gas temperature the modulation range increases when the average boiler tem...

Страница 20: ...temperatures TR at boiler nominal loads as well as 50 load for 180 C nominal inlet temperature Values at CO2 12 7 t water 5 K Rel humidity 60 p baro 100 kPa Condensate amount per kg of fuel oil and f...

Страница 21: ...at CO2 10 t water 5 K Rel humidity 60 p baro 100 kPa Condensate amount per nm3 of gas and flue gas temperatures for different flue gas inlet temperatures and recuperator return temperatures TR at boi...

Страница 22: ...tic hot water etc The steel sheet housing is ready to be mounted on top of the boiler cover or on the carrier located on the side cover The electrical diagram is attached to the control panel 5 2 Basi...

Страница 23: ...are found in spray cans thinners cleaning agents degreasing agents and solvents among others In addition halogen emissions are strongly suspected in the vicinity of dry cleaners hair dressing salons s...

Страница 24: ...4 4 4 4 6 6 6 U girder width S1 mm 50 50 50 55 55 55 55 55 55 55 55 55 Melbury C 530 580 630 700 800 895 1150 1300 1650 1900 2500 3000 Distance wall boiler body front D mm 1600 1700 1700 1900 1900 200...

Страница 25: ...nd the water heater Boiler s maximum operating pressure and the maximum operating temperature are indicated in chapter 4 1 No minimum level of the amount of circulating water is required Damage can oc...

Страница 26: ...delayed action fuse burner boiler and by an additional 6 3A delayed action fuse for each additional governor or module The quality of the supply must respect norm EN50160 voltage 10 max frequency 1 A...

Страница 27: ...5 3265 Diameter FR mm 516 549 614 640 675 71 2 750 811 870 Burner connection Burner admittance diameter M mm 230 3 0 0 330 3 8 0 Burner tube lenght min max qN max max qN low NOx P mm 195 2 6 5 280 330...

Страница 28: ...s oil tubes etc must not be attached to the boiler casing 6 7 3 1 Gas burner Observe the separate instructions of the burner The gas installation must be dimensioned in accordance with the gas flow ra...

Страница 29: ...t flanges and cleaning covers remain accessible The chimney must be designed so that it is gas and pressure tight as well as moisture insensitive and acid resistant 6 8 3 Flue gas tubes Melbury C Depe...

Страница 30: ...n pumps should be switched off and all ventilating valves opened so that the air in the system can completely escape The filling process is finished when the operating pressure has been reached 7 4 Pr...

Страница 31: ...has been filled with insulation material Whether the boiler door is closed properly Whether the heating system has been filled up with water and completely vented Whether the thermostats are properly...

Страница 32: ...onnect supply and burner plug Burner LED is on Press burner reset button No oil Gas pressure insufficient Add oil Call the gas board Overheat temperature LED is on Safety thermostat has come into oper...

Страница 33: ...nance according to the recommendations given in the burner manual Check fuel oil level Clean boiler and chimney 9 2 Boiler cleaning Boiler should be cleaned by your chimney sweeper and engineer The cy...

Страница 34: ...Melbury HE C 530 3000 32 We reserve the right to make changes to dimensions and construction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF 10 Spare parts 10 1 Melbury HE 530 895...

Страница 35: ...40058 140058 140058 140058 Turbulators 3 120284 120284 120284 120284 120284 120285 Smoke tube brush 404 120236 120236 120236 120236 120236 120237 Key 119 160235 160235 160235 160235 160235 160235 Sigh...

Страница 36: ...Melbury HE C 530 3000 34 We reserve the right to make changes to dimensions and construction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF 10 3 Melbury HE 1150 3000...

Страница 37: ...oke tube brush 404 120237 120237 120238 120238 120238 120239 Key 119 160235 160235 160234 160234 160234 160234 Sight glass 117 171523 171523 171523 171523 171523 171523 Flat spring 108 122503 122503 1...

Страница 38: ...nstruction edition 12 2020 Hamworthy Heating Limited Dorset BH17 ONF Wessex House New Fields Business Park Stonsford Road Poole Dorset BH17 ONF Tel 01202662500 Fax 01202 662522 seNice hamworthy heatin...

Отзывы: