HAMWORTHY HEATING LTD
44
FLEET V series
500001213/G
APPENDIX B - ELECTRICAL CONNECTIONS AND CONTROLS
B1.1 Electrical Supply
IMPORTANT: Individual boilers must be earthed.
The boiler must be isolated from the mains electricity supply in the event of electric arc
welding being carried out on any connecting pipe work.
1. Wiring external to the boiler must be installed in accordance with the IEE Regulations and any local regulations
which apply. Wiring must be completed in heat resistant 3-core cable of 1.0mm² cross sectional area. Boilers are
normally supplied for connection to a 230 volts, 50Hz mains supply. The boiler control is supplied with a
replaceable fuse (T4A). External fuses should be 6A for all boilers.
2. 3-Phase Electrical Supplies. Individual modules of Fleet boilers and any boilers installed in close proximity to
each other
MUST NOT
be supplied from different phases of a 3 phase supply. The method of connection to the
mains electricity supply must facilitate complete electrical isolation of the single boiler / battery with a separation of
at least 3mm in all poles.
3. A mains isolator must be provided adjacent to the boiler in a readily accessible position. The supply should only
serve the boiler.
4. Multiple modules. It is highly recommended that each boiler is connected via its own mains isolator to facilitate
servicing and maintenance of the individual boiler whilst leaving the remaining boilers in operation.
5. Further details regarding connection to the electricity supply are given in BS EN 60335, Part 1 or BS 3456, Part
201.
WARNING: THE MAINS POWER SUPPLY MUST NOT BE SWITCHED
BY A TIME-CLOCK CONTROL.
CAUTION: DO NOT FEED MAINS VOLTAGE ONTO THE TIMER TERMINALS
6. The mains power supply must be maintained at all times. Each Fleet boiler module incorporates a remote
enable link, which can be used to operate the boiler(s) under a timed regime. The boiler controls provide a 24V
DC signal that can be fed through a volt free contact for operation. Refer to BS 6644 for further information on
installing the electrical supply.
7. The integral pump in Fleet boilers is managed by the LMU boiler control.
NOTE: FOR BASIC TERMINATION DIAGRAM SEE FIGURE 4.6
ELECTRICAL DATA - per boiler module
BOILER MODEL
F40V
F50V
F60V
F70V
Nominal supply voltage
230V ~ 50Hz
Power Consumption (maximum)
-
W
160 160 160 160
Start and Run Current (per module)
-
A 0.85/0.35 0.85/0.35 0.85/0.35 0.85/0.35
F85V
F100V
F125V
F150V
Nominal supply voltage
230V ~ 50Hz
Power Consumption (maximum)
-
W
350 450 350 600
Start and Run Current (per module)
-
A
2.1/1 2.1/1 2.1/1 2.4/1.2
Figure B1.1 - Electrical supply
Содержание F40V
Страница 2: ......
Страница 31: ...HAMWORTHY HEATING LTD 25 FLEET V series 500001213 G Figure 8 2 1 3 Operation and display philosophy...
Страница 40: ...HAMWORTHY HEATING LTD 34 FLEET V series 500001213 G Figure 8 3 11 Operating phases...
Страница 63: ...HAMWORTHY HEATING LTD 57 FLEET V series 500001213 G NOTES...
Страница 65: ...Please complete the information on the Registration Card cut out and return to Hamworthy Heating Ltd...
Страница 66: ......
Страница 67: ......