HAMWORTHY HEATING LTD
19
FLEET V series
500001213/G
High Fire Target
Nat Gas - 9.0% ±0.25% CO
2
If combustion level is outside of this range use the
Cross Head Throttle Screw to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti-clockwise.
Figure 7.6.1- Adjusting gas valve throttle
Low Fire Target
Nat Gas 9.0% ±0.25% CO
2
If combustion readings are outside target range use
Torx Bit to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 7.6.3 - Adjusting gas valve offset
Models - F40V/ F50V F60V & F70V
Models - F85V/ F100V/ F125V & F150V
4. If combustion is outside of the ranges defined below the factory sealed valves may be adjusted using
the following procedure .
High Fire Target
Nat Gas 9.0% ±0.25% CO
2
If combustion level is outside of this range use the
Cross Head Throttle Screw to adjust the mixture.
T
HIS
SETTING
MUST
BE
CORRECT
BEFORE
CONTINUING
To increase the CO
2
level, turn the adjustment
anti-clockwise.
Figure 7.6.2 - Adjusting gas valve throttle
Low Fire Target
Nat Gas 9.0% ±0.25% CO
2
If combustion readings are outside target range use
Torx Bit to make adjustments
To increase the CO
2
level, turn the adjustment
clockwise.
Figure 7.6.4 - Adjusting gas valve offset
Models - F40V/ F50V F60V & F70V
Models - F85V/ F100V/ F125V & F150V
Fig 7.6.1 - Combustion settings
Содержание F100V
Страница 2: ......
Страница 31: ...HAMWORTHY HEATING LTD 25 FLEET V series 500001213 G Figure 8 2 1 3 Operation and display philosophy ...
Страница 40: ...HAMWORTHY HEATING LTD 34 FLEET V series 500001213 G Figure 8 3 11 Operating phases ...
Страница 63: ...HAMWORTHY HEATING LTD 57 FLEET V series 500001213 G NOTES ...
Страница 65: ...Please complete the information on the Registration Card cut out and return to Hamworthy Heating Ltd ...
Страница 66: ......
Страница 67: ......