Hampton H200 Cast Freestanding Woodstove

INSTALLATION

Method A

: 12" (304.8 mm) Clearance to Combustible Wall Member:

Using a minimum thickness 3.5" (89 mm) brick and a 5/8" (15.9 mm) 
minimum wall thickness clay liner, construct a wall pass-through.  
The clay liner must conform to ASTM C315 (Standard Speci

fi

 cation 

for Clay Fire Linings) or its equivalent. Keep a minimum of 12" (304.8 
mm) of brick masonry between the clay liner and wall combustibles.  
The clay liner shall run from the brick masonry outer surface to the 
inner surface of the chimney 

fl

 ue liner but not past the inner surface.  

Firmly grout or cement the clay liner in place to the chimney 

fl

 ue liner.  

Method B

: 9" (228.6 mm) Clearance to Combustible Wall Member:

Using a 6" (152.4 mm) inside diameter, listed, factory-built Solid-Pak 
chimney section with insulation of 1" (25.4 mm) or more, build a wall 
pass-through with a minimum 9" (228.6 mm) air space between the 
outer wall of the chimney length and wall combustibles.  Use sheet 
metal supports fastened securely to wall surfaces on all sides, to 
maintain the 9" (228.6 mm) air space.  When fastening supports to 
chimney length, do not penetrate the chimney liner (the inside wall 
of the Solid-Pak chimney).  The inner end of the Solid-Pak chimney 
section shall be 

fl

 ush with the inside of the masonry chimney 

fl

 ue, and 

sealed with a non-water soluble refractory cement.  Use this cement 
to also seal to the brick masonry penetration.

Minimum

12 in. (304.8mm)

to combustibles

Masonry chimney

Chimney

Flue

Minimum chimney clearance to brick

and combustibles 2 in. (50.8mm)

Minimum clearance

12 in. (304.8mm)

of brick

Chimney

connector

Fire clay

liner

Method C

: 6" (152.4 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gage (.024" [.61 mm]) 6" (152.4 mm) metal 
chimney connector, and a minimum 24 gage ventilated wall thimble 
which has two air channels of 1" (25.4 mm) each, construct a wall 
pass-through. There shall be a minimum 6" (152.4 mm) separation 
area containing 

fi

 berglass insulation, from the outer surface of the 

wall thimble to wall combustibles.  Support the wall thimble, and cover 
its opening with a 24-gage minimum sheet metal support. Maintain 
the 6" (152.4 mm) space.  There should also be a support sized to 

fi

 t and hold the metal chimney connector. See that the supports are 

fastened securely to wall surfaces on all sides.  Make sure fasteners 
used to secure the metal chimney connector do not penetrate chimney 

fl

 ue liner.  

Method D

: 2" (50.8 mm) Clearance to Combustible Wall Member:

Start with a solid-pak listed factory built chimney section at least 
12" (304 mm) long, with insulation of 1" (25.4 mm) or more, and an 
inside diameter of 8" (2 inches [51 mm] larger than the 6" [152.4 
mm] chimney connector). Use this as a pass-through for a minimum 
24-gage single wall steel chimney connector. Keep solid-pak section 
concentric with and spaced 1" (25.4 mm) off the chimney connector 
by way of sheet metal support plates at both ends of chimney section.  
Cover opening with and support chimney section on both sides with 
24 gage minimum sheet metal supports. See that the supports are 
fastened securely to wall surfaces on all sides. Make sure fasteners 
used to secure chimney 

fl

 ue liner.

COMBUSTIBLE WALL CHIMNEY

CONNECTOR PASS-THROUGHS

Содержание H200

Страница 1: ...G 1H4 918 427a MODEL H200 Freestanding Woodstove 10 25 11 Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for...

Страница 2: ...manual please contact the HAMPTON DEALER in your area Keep those HAMPTON FIRES burning SAFETY NOTE If this woodstove is not properly installed a house fire may result For your safety follow the insta...

Страница 3: ...Mobile Home Installation 16 Listed Components For Mobile Home Installation 17 Brick Installation 18 Door Removal 18 Optional Short Leg Installation 18 Optional Blower Fan Installation 19 Optional Sid...

Страница 4: ...ND MANUFACTURER S INSTRUCTIONS FOR PRECAUTIONS REQUIRED FOR PASSING A CHIMNEY THROUGH A COMBUSTIBLE WALL OR CEILING DO NOT PASS CHIMNEY CONNECTOR THROUGH COMBUSTIBLE WALL OR CEILING DO NOT CONNECT THI...

Страница 5: ...Hampton H200 Cast Freestanding Woodstove 5 DIMENSIONS UNIT DIMENSIONS WITH STANDARD LEGS...

Страница 6: ...6 Hampton H200 Cast Freestanding Woodstove DIMENSIONS UNIT DIMENSIONS WITH OPTIONAL SHORT LEGS...

Страница 7: ...sed only on Vertical Installations 1 Loosen the bolts that secure the elbow to the unit Ensure elbow does not fall off 2 Bendthetabsontherearheatshieldinwards 90 degrees Rear Heat Shield Slide tabs in...

Страница 8: ...Some areas may require a larger size floor protector However when installing the unit with the short leg option there is a requirement of 0 84k of floor protector beneath the non combustible finished...

Страница 9: ...m 27 686 mm 12 1 8 308 mm 15 7 8 403mm Mobile Home Close Clearance To be installed with required pipe components C Vent single wall pipe is not approved for Mobile Home installations refer to Mobile H...

Страница 10: ...m Flue Min Min Hearth Unit with Heat Shield Unit Center line Width to Rear Wall G H I J K L H200 15 381 mm 13 330 mm 27 686 mm 15 1 8 384 mm 54 1372 mm 50 1270 mm ADDITIONAL CLEARANCES FOR BACKWALL EX...

Страница 11: ...te R of proposed system 4 brick of C 1 25 therefore Rbrick 1 C 1 1 25 0 80 1 8 mineral board of k 0 29 therefore Rmin bd 1 0 29 x 0 125 0 431 Total R Rbrick Rmineral board 0 8 0 431 1 231 Step c Compa...

Страница 12: ...optimum efficiency when installing into a masonry chimney size accordingly i e the 6 152mm flue dia is 28 28 sq in 8 Tocompleteyourchimneyinstallation install the double wall connector pipe from the s...

Страница 13: ...stallation MASONRY CHIMNEY Ensurethatamasonrychimneymeetstheminimum standardsoftheNationalFireProtectionAssociation NFPA by having it inspected by a professional Make sure there are no cracks loose mo...

Страница 14: ...mney clearance to brick and combustibles 2 in 50 8mm Minimum clearance 12 in 304 8mm of brick Chimney connector Fire clay liner Method C 6 152 4 mm Clearance to Combustible Wall Member Starting with a...

Страница 15: ...ample b 0 18 21 1000 18 72 21 84 2000 19 44 22 68 5000 21 60 25 20 8000 23 76 27 72 TABLE 1 MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET Measured from the top of the unit OF ELBOWS ELEVATION FT ABOVE SEA...

Страница 16: ...yshouldprojectatleast2ft 610mm above the highest elevation of any part of the Mobile Home within 10 ft 3048mm of the chimney 7 ThechimneysystemshallcomplywithLocal Requirements 8 Any openings in a chi...

Страница 17: ...3 Chimney Length 1 SL1 Chimney Length 1 RCSA Rain Cap SECURITY ASHT Qty Part Description 1 DL42A 6 Connector Kit 1 6SS Shield Support 1 6FAMH Flashing 1 6L3 Chimney Length 1 6L1 Chimney Length 1 CPE R...

Страница 18: ...oor lifts right out Bottom part of door fits into slot Optional Ash Plug shown OPTIONAL SHORT LEG INSTALLATION 1 Remove the cast lid from the top of the stove 2 Remove fan if installed 3 Carefully lay...

Страница 19: ...nding prong from the power cord Do not use an adaptor plug CAUTION Movingpartsmaycauseinjury Do not operate unit with blower housing removed DANGER Risk of electric shock Discon nect power before serv...

Страница 20: ...of Right Hand Side Shelf Shown Gusset Side Casting Left side of stove shown Front Casting Bracket Cut Out Bracket Cut Out NOTE Ensure that the Bracket cut out is towards the back of the stove NOTE Whe...

Страница 21: ...2 nuts and bolts holding the 2 plates together from underneath the stove 4 Re install bottom tray and then install the 2 ash drawer rails to the bottom tray using 4 bolts 5 Slide the ash drawer on top...

Страница 22: ...mporary condition exists Burning the stove at a very high temperaturethefirstfewtimesmaydamage the paint Burn fires at a moderate level the first few days 8 Do not place anything on the stove top duri...

Страница 23: ...he stove is in use 9 Do not connect this unit to a chimney flue serving another appliance 10 Do not use grates or andirons or other methods for supporting fuel Burn directly on the bricks 11 Open the...

Страница 24: ...ing lid The closed container of ashes should be placed on a non combustible floor or on the ground well away from all combustible materials pending final disposal If the ashes are disposed of by buria...

Страница 25: ...ill produce In the event that you break your glass by impact purchase your replacement from an authorized Hampton dealer only and follow our step by step Glass Installation Replacement instructions re...

Страница 26: ...behind screws Allen Key Hex Head Bolt Lock Washer Handle Spacer Front Door Handle Shown LATCH ADJUSTMENT METHOD The door bracketry may require adjustment as thedoorgasketmaterialcompressesafterafew f...

Страница 27: ...rom the Firebox Top Assembly and lift off Top Hob 3 Remove the left and right baffle caps by removing the 2 bolts 7 16 socket 1 4 20 x 1 2 hex head on each side and lift out 4 Remove the three 7 16 so...

Страница 28: ...ed Paper Test Test the seal on the loading door with a paper bill Place a paper bill in the gasketed area of the door on a cold stove close the door Try to remove the paper by pulling The paper should...

Страница 29: ...IMBERLINE BROWN 18 200 960 BRICK SET 19 200 110 FIREBOX FRONT 20 200 160 ANDIRON X2 21 200 120 FIREBOX INNER 22 200 217 BRACKET HINGE 23 200 361 FRONT VENTS CHARCOAL GREY 200 365 FRONT VENTS TIMBERLIN...

Страница 30: ...30 Hampton H200 Cast Freestanding Woodstove PARTS LIST 2 2 2 22 2 2 2 2 2 2 2 0 2 0 20...

Страница 31: ...Cast Freestanding Woodstove 31 H200 DOOR ASSEMBLY PARTS LIST PART DESCRIPTION 2 0 2 200 2 F 2 200 2 F 2 200 220F 2 0 mm C 2 2 2 H 200 CH C 200 W 220 H 220 0 CH 0 220 0 C H 2 0 0 F W H 0 2 C W H 0 202...

Страница 32: ...32 Hampton H200 Cast Freestanding Woodstove PARTS LIST H200 ASH DRAWER ASSEMBLY PART DESCRIPTION 200 H W C 2 0 H 2 2 2 200 2 2 H W H 200 2 H W F 20 2 H H 2...

Страница 33: ...LIST RED LOW WHITE COMMON CONNECTION DIAGRAM BLACK HIGH 115V 60HZ 1 1A J250 150 O44003 T P 3000 RPM JAKEL INC DATE T P L B 200 F C 220 02 F H F 2 220 022 F H 220 0 200 22 F C H H 200 22 F C F H 200 22...

Страница 34: ...34 Hampton H200 Cast Freestanding Woodstove NOTES...

Страница 35: ...hree days of installation Reported damage after this time will be subject to rejection Any part or parts of this unit which in our judgement show evidence of such defects will be repaired or replaced...

Страница 36: ...__________________________ Serial No __________________________________________________________ Register your Regency warranty online www regency fire com Reasons to register your product online today...

Отзывы: