Hampton® H15-1 Direct Vent Freestanding Gas Stove

13

INSTALLATION

EXTERIOR VENT TERMINAL LOCATIONS

Minimum Clearance Requirements

Canada

1

USA

2

A

Clearance above grade, veranda, porch, deck, or balcony

12"(30cm)

12"(30cm)

B

Clearance to window or door that may be opened

 12"(30cm)

9" (23cm)

C

Clearance to permanently closed window

*

*

D

Vertical clearance to ventilated soffi t located above the terminal within a horizontal distance of 2 feet (61cm)
 from the center line of the terminal (check with the local code)

22"(56cm)

22"(56cm)

E

Clearance to unventilated soffi t

12"(30cm)

12"(30cm)

F

Clearance to outside corner: with 

AstroCap

 and Vent Riser Termination Cap

  6"(15cm)

6"(15cm)

Clearance to outside corner: with all other approved Termination Caps.

12"(30cm)

12"(30cm)

G

Clearance to inside corner: with 

AstroCap 

and Vent Riser Termination Cap 

 6"(15cm) 

6"(15cm)

Clearance to inside corner: with all other approved Termination Caps

12"(30cm)

12"(30cm)

H

Clearance to each side of center line extended above meter/regulator assembly

 36"(90cm)

a

*

J

Clearance to service regulator vent outlet

36"(90cm)

*

K

Clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance

12"(30cm)

9" (23cm)

L

Clearance to a mechanical air supply inlet 
 

#3' (91cm) above if within 10' (3m) horizontally.

 72"(1.8m)

36"(90cm)

b

M

Clearance above paved sidewalk or a paved driveway located on public property 

   84"(2.1m)

*

N

Clearance under veranda, porch, deck, or balcony 

  12"(30cm)

*

1

  In accordance with current CSA B149.1, 

Natural Gas and Propane Installation Code

2

  In accordance with the current 

ANSI Z223.1/NFPA 54, National  Fuel Gas Code

 A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the fl oor.

*

  Clearance in accordance with local installation codes and the requirements of the gas supplier

a

  

3 feet (91cm) within a height of 15 feet (4.5m) above the meter / regulator assembly

b

 3 feet (91cm) above  - if within 10 feet (3m) horizontally      

Содержание H15

Страница 1: ...Y What to do if you smell gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Fol...

Страница 2: ...fted appliance and has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch The model H15 1 has been approved by Warnock Hersey for both safety and e...

Страница 3: ...Hampton H15 1 Direct Vent Freestanding Gas Stove 3 Hampton H15 1 Direct Vent Freestanding Gas Stove 3 SAFETY LABEL DIMENSIONS UNIT DIMENSIONS...

Страница 4: ...ATION Important Message 7 Specifications 7 Manufactured Homes After First Sale 7 Before You Start 7 General Safety Information 8 Installation Checklist 8 Clearances to Combustibles 9 Locating Your Gas...

Страница 5: ...CUATION PROPANE GAS STOVE Model H15 LP1 L APPAREIL FONCTIONNANT AU PROPANE CONCU POUR ETRE POELE Mod le H15 LP1 MAY BE INSTALLED IN MANUFACTURED MOBILE HOMES AFTER FIRST SALE DO NOT REMOVE THIS LABEL...

Страница 6: ...directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT...

Страница 7: ...Electrical Code CSA C22 1 in Canada BEFORE YOU START Safe installation and operation of this appliance re quires common sense however we are required by theCanadianSafetyStandardsandANSIStandards to...

Страница 8: ...ts and circulating air passageways of the appliance be kept clean and free from excessive lint from carpeting 4 See general construction and assembly in structions The appliance and vent should be enc...

Страница 9: ...OMBUSTIBLES The clearances listed are MINIMUM distances Measure the clearance to both the appliance and the chimney connector The farthest distance is correct if the two clearances do not coincide For...

Страница 10: ...f 2 bolts at the top Take care not to cut wires when lower ing the panel 2 Disconnect the red and grey wires Top Control Panel Assembly Fan Speed Controller 4 Remove the nylon hole plug from the contr...

Страница 11: ...properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug 12 Slide fan into place and secure with the two screws removed in step 9 13 Connect long black red wir...

Страница 12: ...s of combustion to the outside while the outer pipe draws outside combustion air into the combustion chambertherebyeliminatingtheneedtouseheated room air for combustion and losing warm room air up the...

Страница 13: ...center line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inl...

Страница 14: ...N A N A Adjustable Length 3 10 Galvanized N A N A N A 4DAL N A TC 4DLT Adjustable Length 3 10 Black N A N A N A 4DALB N A TC 4DLTB Adjustable Length 7 Galvanized N A N A 4D7A N A N A N A Adjustable Le...

Страница 15: ...ntal Termination Kit A Disc 4DT HKA 4DHTK2 4DHTKA SV SHK N A Horizontal Termination Kit B 46DVA KHA Changed Components 4DT HKB 4DHTK1 4DHTKB SV HK N A Vertical Termination Kit Disc 4DT VKC 4DHTK 4DHTK...

Страница 16: ...nt SelkirkDirect Temp Ameri Vent Direct venting and Security Secure Vent systems Use of these systems with the Rigid Pipe adaptor is deemed acceptable and does not affect the Intertek WHI listing of c...

Страница 17: ...with min of 8 feet total vertical and max 8 feet total horizontal Please note min 1 foot between 90o elbows is required With these options maxi mum total pipe length is 30 feet with minimum of 6 feet...

Страница 18: ...al Please note min 1 foot between 90o elbows is re quired A 2 Max 2 Min B 3 Max 3 Min C 4 Max 4 Min D 5 Max 5 Min E 6 Max 6 Min Withtheseoptions max total pipelengthis30feetwithmin of6feettotalvertica...

Страница 19: ...bustibles May be installed in Manufactured Mobile Homes after first sale Horizontal Terminations for All Venting Systems The shaded areas in the diagram below show all allowable combinations of vertic...

Страница 20: ...aximum flue lengths See chart below for minimumdistancesfromroof Periodicallycheck that the vent is unrestricted Masonry chimneys may take various contours which the flexible liner will accommodate Ho...

Страница 21: ...e to length Attachthe 45o elbowtotherigid pipe and ensure that the pipe length when cut with the 45o elbow will seat onto both the starter collar and the 90o elbow Crimpedsectionofrigidpipe seats into...

Страница 22: ...andoff to prevent water from entering and to make a tight seal between the cap and the standoff 7 Stretch the 4 dia flex liner out fully and get a trial fit of the liner onto the 4 dia starter collar...

Страница 23: ...Vent 1 946 202 Wall Penetration Heat Shield Wall Thimble 2 pcs 1 640 530 P Riser Vent Terminal 1 640 545 P Decorative Wall Trim Black 1 948 128 Tube Mill Pac Screws 380 946 Horizontal Termination Kit...

Страница 24: ...ible surfaces is 1 1 4 inch Be sure to check the vent termination clearance requirements fromdecks windows soffits gasregulators air supply inlets and public walkways as specified inthe ExteriorVentTe...

Страница 25: ...run of vent should have a 1 4 inch rise for every 1 foot of run towards the termination Never allow the vent to run downward Thiscouldcausehightemperatures and may present the possibility of a fire b...

Страница 26: ...ighly recommended to apply Mill Pac sealant supplied to every inner pipe connection Failure to do so may result in drafting or performance issues notcoveredunderwarranty Silicone red RTV is optional D...

Страница 27: ...onnection Failure to do so may result in drafting or performance issues not covered under warranty Silicone red RTV is optional and elbows necessary to reach from the appliance adapter up though the R...

Страница 28: ...cured in place and sealed before installing a Direct Vent system within the chimney If the appliance shuts off during operation contact a qualified service person to determine if a negative pressure a...

Страница 29: ...nd frame a hole in the roof for the support The sides of this hole must be vertical with 1 1 4 clearance 2 Place the support in the opening Lower it to the correct height as determined by the table an...

Страница 30: ...finished reading manometer turn off the gas valve disconnect the hose and tighten the screw clockwise with a 1 8 flat screwdriver Note Screwshouldbesnug butdonotover tighten Valve Description 1 Gas on...

Страница 31: ...0 in 904 781 Velcro Hook Black 904 782 Velcro Hook Black 1 Shut off the gas supply 2 Lift off Cast Top remove Cast Front and Glass Door refer to the glass replace ment section in the manual and carefu...

Страница 32: ...ontrol panel Before After 12 Pull off the pilot cap to expose the pilot orifice 13 Unscrew the pilot orifice with the allen key and replace with the LP pilot orifice in the kit 14 Remove burner orific...

Страница 33: ...iezo ignition wire to the DC Sparker Piezo Ignitor 31 Attach the heat shield to the DC sparker then mount onto the stove using the velcro already attached to the DC Sparker mounting bracket Note We re...

Страница 34: ...t Side Front Log d Center Front Log e Embers f Platinum Embers 946 669 supplied with packaged manual Left Front Log 3 Remove Cast Front by removing the 2 screws using a 7 16 wrench Pull front out and...

Страница 35: ...re is any flame hesitation check that area for any blockage of the burner ports 11 Re install the Glass Front Cast Front and Top 8 Take the embers and place on the burner in the space between the 2 fr...

Страница 36: ...L approved may be used Thermostat Wire Table 1 Choose a convenient location on the wall to install the receiver and the receptacle box protectionfromextremeheatisveryimportant Run wires from the firep...

Страница 37: ...ase of a power failure the burner switch and the optional remote control thermostat will continue to operate However a 120V A C power supply is needed for the fan blower operation Caution Ensure that...

Страница 38: ...ton H15 1 Direct Vent Freestanding Gas Stove INSTALLATION For PROPANE Units and Units Equipped with DC Spark Boxes For installation of the DC Spark Box refer to the LP Conversion instructions in this...

Страница 39: ...ss should be cleaned or the film will bake on and become very difficult to remove Use a non abrasive cleaner and NEVER clean the glass while it is hot I M PORTANT Gas on off knob cannot be turned from...

Страница 40: ...floor WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbors phone Fo...

Страница 41: ...timetheapplianceislit itmaycause condensation and fog the glass This condensa tion and fog is normal and will disappear in a few minutes as the glass heats up Never operate the appliance without the g...

Страница 42: ...ssuch as Wall Straps or plumbers tape for rigidity LOG REPLACEMENT Theunitshouldneverbeusedwithbrokenlogs Turn off the gas valve and allow the unit to cool before opening door to carefully remove the...

Страница 43: ...lace the burner tray assembly simply reverse these instructions Toremovevalvefromvalveassembly continue 14 Remove two 2 thermopile wires 15 Remove thermocouple with a 9 mm metric wrench 16 Remove pilo...

Страница 44: ...Deflector Left 17 910 142 Thermodisc Switch 20 380 012 Rear Panel 25 910 330 Fan Speed Control 120V 26 904 569 Knob Fan Speed Control 28 910 241 Burner ON OFF Switch 29 260 037 Rear Control Panel 35 3...

Страница 45: ...t 64 908 672 Control Panel Decal 65 490 061 Switch Plate 936 170 Orifice Gasket 66 910 038 Pilot Assy S I T 3 flame NG 910 039 Pilot Assy S I T 3 flame LP 67 380 013 Pilot Holder 68 W840470 Pilot Asse...

Страница 46: ...46 Hampton H15 1 Direct Vent Freestanding Gas Stove NOTES...

Страница 47: ...requested It is the general practice of FPI to charge for larger higher priced replacement parts and issue credit once the replaced component has been returned to FPI and evaluated for manufacturer d...

Страница 48: ...___________________________________________________ Phone ___________________________________________________________ Date Installed ______________________________________________________ Serial No __...

Отзывы: