background image

HALYTECH 

 

meterwatch User Manual  

 

 

 

 
 
 
 
 
 
 

Non-urban Water Metering

 

 

 
 
 

 

 
 

Installation Guide 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

microSpider meterwatch User Manual Version 3 

Copyright © Halytech 

All rights reserved 

 

 

 

Содержание HMW-002

Страница 1: ...HALYTECH meterwatch User Manual Non urban Water Metering Installation Guide microSpider meterwatch User Manual Version 3 Copyright Halytech All rights reserved...

Страница 2: ...o the software images photographs animations video audio and music are owned by Halytech You may not reverse engineer decompile or disassemble this software for any purpose No part of this software ma...

Страница 3: ...dic reports and real time alarms to a centrally managed government website meterwatch is weatherproof has an integrated long life battery pack and communicates via the mobile telephone network Connect...

Страница 4: ...ts Security HMW 003 External antenna Pulse Probe Connector Halytech supplied and terminated meter pulse unit None External antenna with SMA connector Examples Halytech HAN 001 Benelec 024585 Benelec 0...

Страница 5: ...e probe unit from Halytech please specify the required cable length and the water meter model For meterwatch variant with a flying lead you need to source the appropriate pulse probe and join it to th...

Страница 6: ...poor or no signal conditions While doing the mobile signal test try repositioning the antenna and changing its orientation until you get a good signal It is important to wait approximately 15 seconds...

Страница 7: ...ink over soldered joints to reduce the risk of shorts occurring in the connector Pin meterwatch Meter Pulse Probe Signal 1 Meter Input Pulse output 2 Do Not Use 3 Ground Pulse Common Ground 4 Tamper I...

Страница 8: ...or termination practices will result in unreliable operation of the system The following table lists the flying lead colours and the corresponding pulse probe cable connections You may need to refer t...

Страница 9: ...ptional antenna and connected it to the meter you are ready to configure it Log in Plug the Lanlink Cable into the connector with the red ring Plug the LAN and USB connectors into your computer Using...

Страница 10: ...ry adjust the antenna location and or orientation The mobile signal test will run for around 2 minutes so you have time to make antenna adjustments It is important to wait approximately 15 seconds aft...

Страница 11: ...synchronise the reading in meterwatch with the actual meter reading Enter the value shown on the meter dial into the desired reading and click Set If the meter is turning we suggest you enter a value...

Страница 12: ...Manual 12 4 Activate meterwatch Activation is possible only if all 3 steps above are successful the enclosure is secure AND the meter cable is connected Once activated meterwatch will commence loggin...

Страница 13: ...signal test the data link You need to secure meterwatch before leaving the site by fitting the following as per the images below 1 sealing cap on comms connector lock by turning a quarter turn 2 stai...

Страница 14: ...Local connection IP address 192 168 0 177 Logging period 1 hour Reporting frequency Daily Report offset time as specified by Water NSW Report destination as specified by Water NSW Logged Channels Met...

Страница 15: ...CH microSpider meterwatch User Manual 15 Appendix B Support Information Halytech Contact Details Email support halytech com au Phone 02 8814 5235 Maintenance Requirements No routine maintenance is req...

Страница 16: ...t short circuit Protect wiring from damage Do not attempt to recharge Do not open crush deform or try to disassemble Do not expose to water Do not solder anything to battery Do not incinerate Do not l...

Страница 17: ...r other transit 6 This Warranty is void in the event of a The device being installed by anyone other than a duly qualified person as defined by NSW non urban water metering framework and or by not fol...

Страница 18: ...Halytech for repair or replacement at their own cost 12 If a warranty claim is not accepted a Halytech will inform the Customer b if requested to do so by the Customer Halytech will repair the Product...

Отзывы: