EcoloAir Installation Manual

 

EA

OMSI/0620

09/re

v1/EN

ECOLO ODOR CONTROL

To replace a 5 gallon/22 liter bottle of odor solution (“Scentry”)

1.  Open enclosure cabinet door by unscrewing the two lock bolts. 

2.  Screw the cap off the empty bottle/reservoir. 

3.  Pull the dip tube assembly out of the empty bottle. 

4.  Remove the empty bottle from the cabinet 

5.  Refill bottle with concentrate and mix well as per instructions or refill with “ready to use, pre-mixed 

solution. 

6.  Place the bottle in the cabinet. 

7.  Put the dip tube assembly into the new bottle. Make sure the dip tube reaches the bottom of the 

bottle. 

8.  Place cap on bottle neck and make one turn. DO NOT TIGHTEN (Option: place low level probe in bottle). 

9.  Close the cabinet door and lock with locking bolts. 

NOTE: The standard EcoloAir unit comes with the Ecolo Odor Control pre-mounted and installed.

SCHEMATIC WIRING DIAGRAMS

For field wiring diagrams and field connections refer to Halton’s shop drawings shipped with unit or contact

factory.

Additional copies of shop drawings are available on request.

FAN SECTION

Important note:

Before starting the fan unit, remove fan isolator hold down brackets. The brackets are used for shipping 

purposes only. When the brackets are removed the fan should float freely on the spring isolators.

START UP NOTICE

The unit is now ready for start-up. The start up and initial check out are to be performed by an “authorized” 

service agent. If the start-up is performed by someone other than an “authorized” agent the Warranty is null 

and void.

Halton agent must have a minimum notice of five (5) days to schedule start-up. Should the equipment not 

be ready for start-up at the specified time any additional expenses incurred will be charged to the dealer who 

purchased the equipment.

For any questions please contact Halton Service Network at (270) 237-5600 for the U.S. and (905) 624-0301 for

Canada.

Содержание EcoloAir 10000CFM

Страница 1: ...URE ELECTRICAL SUPPLY CONFORMS WITH ELECTRICAL CHARACTERISTICS SHOWN ON THE RATING PLATE AND N E C REQUIREMENTS THE INSTALLATION OF THE HOOD AND DUCT WORK LEADING TO AND EXITING THE ECOLOAIR SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NFPA 96 AND LOCAL CODES UL 1978 Standard for Grease Ducts UL 710 Exhaust Hoods for Commercial Cooking Equipment ULC S647 05 and or UL197 ...

Страница 2: ... DETAIL LOCATED TOP OF FILTER OUTLET IF AN INLET B FAN TOP INSULATION LINING OPTION FOR EXTERIOR ICN INTERIOR FAN TOP PANEL BOTTOM FLOOR PANEL WITH TURNED UP FLANGE AT FAN INLET INTERIOR FLOOR CONNECTION FLANGE FILTER OUTLET 4 STRUCTURAL FLOOR BASE PLAN VIEW INLET PANEL CONNECTION FLANGE ACCESS SIDE INLET GASKET PROVIDED BY FACTORY FAN BOTTOM PANEL TURNED UP FLANGE FAN TOP PANEL LESS INSULATION FI...

Страница 3: ...CT CONNECTIONS 1 The exhaust duct connection at the inlet entrance to the EcoloAir system must be continuously welded all around See figure 2 2 The duct must be transitioned to the full opening of the filter module inlet 3 All fan outlet openings to which ducts are attached will be provided with discharge collars See figure 3 4 All openings are to be transitioned to the duct size 5 For filter modu...

Страница 4: ... the filters be properly seated against the support mullion as shown in figure 4 and 5 ECOLOAIR UNIT FILTER SUPPORTING FRAME PRE FILTER MERV 7 AIR FLOW EXHAUST FILTER INLET MEDIUM FILTER MERV 14 FIGURE 4 FILTER AIR SEAL GASKETING CLAMP HANDLE TAPED TO SIDE OF FILTER FOR SHIPPING ABSOLUTE FILTER MERV 16 FILTER CLAMP PULL OUT TO LOOSEN FILTER PUSH IN TO TIGHTEN FILTER AGAINST AIR SEAL CENTRE MULLION...

Страница 5: ...d installed SCHEMATIC WIRING DIAGRAMS For field wiring diagrams and field connections refer to Halton s shop drawings shipped with unit or contact factory Additional copies of shop drawings are available on request FAN SECTION Important note Before starting the fan unit remove fan isolator hold down brackets The brackets are used for shipping purposes only When the brackets are removed the fan sho...

Страница 6: ...ce charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that have been installed and maintained in accordance with the installation and Care Instruction Manuals Purchaser shall be solely responsible for adhering to the instructions and procedures set forth in th...

Отзывы: