background image

11

Capture Jet

®

  Operation & Maintenance Manual

 

OM-0

05/0520

17/re

v3/EN

Hood Wiring  Details 

The Halton hood is equipped with a Timer Panel which fulfils the International Mechanical Code required interlock 
which will turn on the exhaust fan serving the hood if an appliance is turned on without also turning on the fan.  This is 
accomplished with a temperature sensor in the hood that senses elevated temperature in the hood.  This temperature 
sensor closes a circuit at 95 degrees Fahrenheit which turns on the exhaust fan.  All hoods which are ducted to the same 
exhaust fan must have their temperature sensors wired in parallel with the sensor on the hood with the Timer Panel. 
This hood is typically the same hood that has the lights and/or fan switch.  This required interlock circuit is not intended 
to act as the primary means of turning on the exhaust fan.   The exhaust fan will always remain on for 15 minutes after 
the temperature sensor has cooled lower than 95 degrees Fahrenheit, even if the fan switch has been turned off.  This 
allows a cool down period for the appliance and removal of heat in the space protected by the hood.  The timer panel also 
has provision for a night circuit which can turn on the exhaust fan if the fire suppression system fires when the kitchen 
is unattended and the hood is off.  This circuit is wired through one of the micro switches in the fire suppression control 
cabinet.  Provision is also made for a Make Up Air interlock which can start the Make Up Air fan whenever the exhaust 
fan is operating.  This circuit is typically wired through one of the micro switches in the fire suppression control cabinet in 
order to turn off the Make Up Air during a fire event.  Please see the wiring diagram for details about these options.

 The Capture Jet fan will typically remain on in Fire Mode to assist with capture and containment of produced smoke.  The 
Halton Capture Jet hoods are tested and listed to allow the Capture Jet fan to remain on.  

Field Connection of Hood Power

Incoming 120 volt power for the hood lights and the Capture Jet fan is connected to terminals in the Timer Panel on top of 
the hood. 
 
When hoods are arranged end to end or back to back one switch panel often controls all of the lights in the hood group.  
The electrical power will then be field connected from the hood with the incoming power, the hood with the switch panel 
and/or timer panel, to the other hoods in the hood group.  Remove the cover from the junction box next to the Capture 
Jet intake, on top of the hood.  Remove wire nuts from green, white and the switched black for the light circuit and add 
field wiring to the same wire junctions on the next hood.  Not all hoods may have a timer panel or LED lights.  Please 
refer to the specific job submittal drawings for wiring diagrams customized to the product mix and arrangement of each 
jobsite.  Submittal drawings supersede the general wiring diagram found in this manual.

Содержание Capture Jet KCH

Страница 1: ...tors Manual for Capture Jet Manual provides Operation Maintenance and Service Instructions Form OM005_CAPTURE JET Date May 2017 Rev2 Capture Jet Hoods KVE SJ SK KVC SJ SK KVW SJ SK KVL KVM KVR KVO AND...

Страница 2: ...contractor to see that the system installation is completed in accordance with the project plans and specifications and that it meets all specific requirements of local code officials The local author...

Страница 3: ...to end or back to back see pg 8 for Installation of Splice Strips and U Channels 7 For hoods equipped with a supply fire damper it is very important to make sure that the fire damper is set in an open...

Страница 4: ...he Capture Jet plenum on top of the hood or mounted in an electrical enclosure The submittal drawings will detail the location of the speed controller s Information regarding the fan and speed control...

Страница 5: ...ew through top of flange to wall screw head will not interfere with hood Screw backsplash to wall or attach with adhesive Halton canopy hoods should be installed from 78 min 84 max above the finished...

Страница 6: ...e top of the hood using the turnbuckles will make final adjustments easier Hanging height of Canopy hoods should be per local building codes verify with Authority Having Jurisdiction for hanging heigh...

Страница 7: ...be attached to supply collar with sheet metal screws or pop rivets and sealed with duct tape Screws or Rivets are not to interfere with the operation of the fire damper if equipped Recommended Exhaust...

Страница 8: ...upply plenum Fig 1 Fig 2 U Channel For hood models that are placed back to back as shown in Fig 1 Slide the U Channel A up over the back of the hood systems and secure with sheet metal screws For hood...

Страница 9: ...nel and vertical flange on top of hood should line up 2 Hammer clips C over the two vertical flanges 3 Attach panels B to wall using appropriate hardware D 4 Slide front panel A into place 5 Attach pa...

Страница 10: ...AT ANY TIME FANS WILL REMAIN ON FOR 15 MIN AFTER EXHAUST FAN SWITCH IS TURNED OFF H TR 15 MIN DELAY OFF TIMER N 1 2 TR 1 3 4 TEMP SENSORS C R1 R1 1 R2 7 8 R2 1 120V ADDITIONAL RELAY NOTE THE USE OF R...

Страница 11: ...es in the fire suppression control cabinet Provision is also made for a Make Up Air interlock which can start the Make Up Air fan whenever the exhaust fan is operating This circuit is typically wired...

Страница 12: ...NEUTRAL INCOMING CIRCUIT 120 1 60 J BOX J BOX BLACK WHITE BY HALTON FIELD WIRING The KVL external Capture Jet fan has a fire damper in the collar that must be set to open before the fan is attached to...

Страница 13: ...ent screw The adjustment screw allows control of the fan and thus the amount of airflow from the Capture Jets 3 The Capture Jet fan should be adjusted to produce 0 25 of positive water column pressure...

Страница 14: ...the cooking equipment is in operation to create a thermal plume prior to the air balancer to be able to use theT A B ports For accurate results the balance contractor should receive a copy of the job...

Страница 15: ...and down Lift filter out of plenum Tilt top of filter out Lift filter into plenum Push filter in and down Tilt top of filter in Lift filter to the front Slide filter down Remove KFR tool To remove fi...

Страница 16: ...andescent or Fluorescent lighting available KSA Filters 78 84 A F F Standard Verify with Authority in project location for min hanging height 16 ga duct work all welded per code Standard top mounted C...

Страница 17: ...3 EN Model KVC Typical Installation Filtered MUA unit on the roof 40 min 120 min 16 ga duct work all welded per code Stainless Steel KSA filters Capture Jet air 78 84 A F F 78 Std Make up airflow Veri...

Страница 18: ...r restaurant cooking appliances 78 84 A F F 78 Std Side view of typical install Integrated Capture Jet location 40 min S S KSA Filters Exhaust Air LED lights T A B Ports Integrated Capture Jet fan Ver...

Страница 19: ...lation Capture Jet fan KSA filters LED lighting T A B Ports Exhaust Air S S Perf Low Velocity Supply Air W 2 Perf Plenum Capture Jet Air W 1 Perf Plenum Supply Air Exhaust Air Supply Air Capture Jet f...

Страница 20: ...Model KVL Typical Installation UL listed upblast fan for restaurant cooking appliances 40 min 58 64 A F F Capture Jet fan Stainless Steel KSA filters 16 ga duct work all welded per code Capture Jet ai...

Страница 21: ...Maintenance Manual OM 005 052017 rev3 EN Model KVM Typical Installation UL listed upblast fan for restaurant cooking appliances 40 min Capture Jet fan Stainless Steel KSA filters 16 ga duct work all w...

Страница 22: ...1 Panels A are placed at the outside ends of the hood at each end of the hood group 2 Align the weld studs on the upper edges of the side skirts with the holes in the lower edge of hood ends and hang...

Страница 23: ...lter angle 24 minimum height Model KVR Round and Oval hoods can be shipped in pieces for field assembly If pieces are shipped loose parts will be marked for easy assembly and an Operation and Installa...

Страница 24: ...24 Capture Jet Operation Maintenance Manual OM 005 052017 rev3 EN Model KCH Typical Installation...

Страница 25: ...p Date Product Serial Numbers Contact Information Contact Name Title Chef Kitchen Mgr Facility Mgr Property Mgr etc Facility Management Company Name if applicable Email Phone Number Cell Number Fax co...

Страница 26: ...ied third party No claims for labor charges will be approved for payment if work commences without prior authorization by Halton Purchaser shall pay incurred premium labor charge including overtime we...

Отзывы: