halstrup-walcher PS27 Скачать руководство пользователя страница 10

 

Operating Instructions PS27 

 

10 

7. 

Display (Option)

 

To show up the readings, the PS27 can also be fitted out with a display. The readings 
will be shown in either Pa or kPa depending on the limiting value of the measuring 
range. The number of the measuring range selected is always shown on the bottom 
line of the display. 
On switching on a display-equipped appliance, the first thing shown is the PS27 
programme version followed by a 1.5 second screening of the limiting value of the 
selected measuring range and then the actual readings. 

 

8. 

Setting the Relay Operating Point (Option)

 

The relay operating point can be adjusted with the aid of the potentiometer P2.1 (Set 
Relay). Adjustment is easiest when the desired switching pressure is applied and the 
potentiometer set so that the relay is just triggered. 

Please note: The relay is connected to the sensor's output so that any adjusted 
time delay will also cause a delay in relay triggering. 

 

9. 

In case of Malfunctions 

 

Fault description 

Possible cause 

Corrective action 

No output signal 

• Supply voltage is not 

 

connected 

• Incorrect supply voltage 

 

connected 

• Defective input protection diode

 

Only for DC power: 

• defective reverse polarity diode

 

 

• Connect correct supply 

 

voltage 

• Connect correct supply voltage 

 

(see rating plate) 

• Send the appliance to the 

manufacturer for repairs 

• Send the appliance to the 

manufacturer for repairs  

 

 

Output signal is 
constant despite 
change in pressure 

• Defective output protection 

diode 
 

• Pressure ports reversed

 

• Send the appliance to the 

manufacturer for repairs 

• Connect the pressure as described in 

 

"3. Installation" 

Output signal 
incorrect 

 

• Faulty pressure sensor 

 

 

• Zeroing with pressure applied

 

For current output: 

• load too high

 

For voltage output 

• Load resistance too low

 

• Send the appliance to the 

manufacturer for repairs  

• Renewed zeroing without pressure

 

• Note maximum 500 

 load 

 

• Note minimum 50 k load resistance

 

 

(see "7 Specifications") 

10. 

Specifications

 

 

Содержание PS27

Страница 1: ...ial Pressure Transducer PS27 halstrup walcher GmbH Stegener Stra e 10 79199 Kirchzarten Germany Phone 49 0 76 61 39 63 0 Fax 49 0 76 61 39 63 99 E mail info halstrup walcher com Internet www halstrup...

Страница 2: ...Transducer 6 3 Startup 6 3 1 Functional Description 6 3 2 Connections for Four Wire version standard in the device 7 3 3 Connections for Two Wire System Option 8 4 Resetting Offset 8 5 Configuring th...

Страница 3: ...service life of the transducer They must be passed on to the succeeding personnel charged with operations Any additions coming from the manufacturer must be inserted The manufacturer reserves the rig...

Страница 4: ...sons as assigned by the plant operator are to operate the transducer Do not perform any functional test involving compressed or breathable air This would otherwise damage those transducers with low me...

Страница 5: ...ndling the equipment WARNING It points to a hazard possibly extending from injures through to death should the instructions not be followed CAUTION It points to a hazard which could cause considerable...

Страница 6: ...as this may lead to measurement errors arising Ideally the appliance should be vertically mounted on a wall not subject to any vibrations To stop any condensed water entering the measurement cell the...

Страница 7: ...gram on the appliance cover circuit board mount The transducer outputs are protected from short circuits The DC supplied appliances are protected from reverse polarity of the supply voltage ST4 Pin Co...

Страница 8: ...ser must ensure that the appliance is not subjected to any pressure during the calibration process as this might lead to a wrong offset value which in turn would result in a wrong output signal The 24...

Страница 9: ...aching of 4 measuring ranges into the appliance has been undertaken by the manufacturer The switches 1 and 2 of SW can be used to select the measuring range in question before the transducer is switch...

Страница 10: ...t so that any adjusted time delay will also cause a delay in relay triggering 9 In case of Malfunctions Fault description Possible cause Corrective action No output signal Supply voltage is not connec...

Страница 11: ...500 Ohm 4 20 mA two wire 17 32 V RL 500 Ohm Switching contact optional max 230 VAC 6 A min 500 mW Display optional 3 digit LCD Overload range Range 2 0kPa 10 kPa Range 10 kPa 200kPa Range 100 kPa 500k...

Страница 12: ...27 12 11 Dimensional Drawing For additional specifications and dimension drawings please visit our website at http www halstrup walcher de en products measurement technology index php 7100 004354I_PS2...