Instruction manual PS11/PK11 

10 

 

Electrical data 

 

power consumption 

max. 1.4 W 

supply voltage 

24 VDC +20% / -15% 
     (smoothed, permissible peak-to-valley ratio = 1000 
mV) 

load resistance R

L

 

R

L

 

 2 k

 at output voltage 0...10 V 

effect of change from the minimal resistance  
to 

: max. 0.2 % 

working resistance 

R

B

 

R

B

 

=

 500 

 

effect of change from 500 Ω to 0 Ω: max. 0.2% 

output signal 

0 to 10 V and 4 to 20 mA 
(voltage limited to 10 V) 

contact points 

single-pole switching relay 
max. load capability 230 VAC, 5 A 
can be adjusted over the complete measurement range 
using the potentiometer  

 

 

Physical data 

 

pressure port 

FESTO elbow (AN) quick connector for PVC tubing 
(external Ø 6mm) 

electrical connection 

screw terminals for cables up to 2.5 mm

2

 

mounting orientation 

mounted vertically on 35mm DIN top hat rails 

dimensions (w x l x h) 

45 x 111 x 73 mm 

protection class 

IP40 

weight 

0.25 kg 

Appendix A: Parts in contact with measurement medium 

 Beryllium bronze  CuBe2 

 Araldite CY236 / HY988 

 Mu metal (nickel alloy) 

 Loctite 242e 

 Brass  CuZn39Pb3 

 Carbonyl iron 

 Aluminium  AlCuMgPb / AlMg3 

 KEL  (FPM: fluorinated rubber) 

 Silicon (tubing), optional: Viton 

 Vepuran Vu 4457/51 

 Crastin (PTBP) 

 UHU-Plus endfest 300 binder 

 

Содержание PK11

Страница 1: ...l Mounting Type PS11 Type PK11 with Contact Point halstrup walcher GmbH Stegener Stra e 10 D 79199 Kirchzarten Phone 49 0 76 61 39 63 0 Fax 49 0 76 61 39 63 99 E mail info halstrup walcher com Interne...

Страница 2: ...ctions and start up 4 1 3 Troubleshooting maintenance repairs disposal 4 1 4 Symbols 5 2 Instrument description 6 3 Start up 6 3 1 Features 6 3 2 Supply voltage connections in the instrument 7 4 Calib...

Страница 3: ...ly available throughout the lifecycle of the instrument It must be provided to any individuals who assume responsibility for operating the instrument at a later date It must include any supplementary...

Страница 4: ...ised by the operator of the facility The instrument may only be operated by appropriately trained individuals who have been authorized by the operator of the facility Do not carry out a function test...

Страница 5: ...r operation could result in the following hazards WARNING This warns you of a potential hazard that could lead to bodily injury up to and including death if the corresponding instructions are not foll...

Страница 6: ...ictional parts or parts subject to mechanical wear 3 Start up 3 1 Features Although the PS11 PK11 pressure transducer is highly robust it is nevertheless a precision instrument and should be handled w...

Страница 7: ...uments are calibrated by the manufacturer before delivery During assembly it should only be necessary to correct any positional errors However the following tools are required if calibration is still...

Страница 8: ...point with the NO contact function The same instructions apply to setting the NC contact function only the function is inverted You can access the P6 potentiometer through a bore in the front of the i...

Страница 9: ...defective pressure measurement cell send the instrument to the manufacturer for repair 7 Technical data Measurement data measurement ranges 300 Pa to 200 kPa overload capacity 10 x the final value of...

Страница 10: ...an be adjusted over the complete measurement range using the potentiometer Physical data pressure port FESTO elbow AN quick connector for PVC tubing external 6mm electrical connection screw terminals...

Страница 11: ...ion drawings 111 45 U OUT 20 I OUT 19 5 UB GND GND 31 25 73 111 Verschlu stopfen f r Schlauch au en 6 2x L Steckverschraubung 7100 003754B_PS11_PK11_eng doc 02 11 2021 Ze cover seal FESTO elbow AN qui...

Отзывы: