Figure 34
Login dialogue window
3.14 2-LOGOUT
From the normal mode screen, pressing 2-LOGOUT key, the current user will lo-
gout.
3.15 4-LOGIN
Pressing 4-LOGIN key a login window will ask for the user password to allow en-
tering one of the three user levels: OPERATOR, MAINTENANCE or ENGINEER
level (see the related paragraph User levels).
For the OPERATOR level, login is only required for acknowledging active events,
as described in the previous chapter.
After logging in, according to the user level the next window will be in OPERA-
TOR, MAINTENANCE or ENGINEER level. In the right and upper corner of the
screen, it will be displayed what user level is it: “O” for Operator, “M” for Mainte-
nance and “E” for Engineer.
3.16 3-SYSTEM
In the main window in Normal mode, at any user level, one may view the sys-
tem’s configuration details, by pressing 3-System. The Zones screen will appear.
The Zones screen shows the list of the defined zones. One may move the cursor
up and down by using the up/down arrow keys. In the bottom side, the available
function buttons depend on the user level.
3.17 ZONES
In the zones screen, moving up and down with the arrow keys through the zones
list and pressing ENTER one gets into the modules screen.
In the modules screen, moving up and down with the arrow keys through the
modules list and pressing ENTER one gets into the detectors or outputs screens
In the bottom side, the available function buttons depend on the user level.
In the Maintenance or the Engineer level it is possible to Set or Unset and put in
TEST/Maintenance parts of the system.
In the “Operator” level, the SET/Unset and Test/Maintenance options are not ac-
tive. The user should be in “Maintenance” or “Engineer” level to use the options.