27
Control
520
R/W
The integral control gain in the PDF control algorithm
(controllers only) This is an integer 0–65535. Note that this
register is scaled differently from legacy integral gain registers.
Added in V2.4.0.
521–522
R/W
Desired volume for the current totalizer batch (controllers only)
This is an integer in the current instrument total volume units,
indicated in register 49 and scale, formatted with the factory-set
number of decimals.
Added in V3.0.0.
524–525
R/W
The maximum setpoint ramp (controllers only) This is an integer
where 100% / msec = 1000000000. If 0, all ramping is disabled;
the setpoint will instantly step to the newly requested value.
If nonzero, this is the maximum ramp rate of the setpoint per
millisecond. The value should be the ramp in percentage of full
scale per millisecond, multiplied by 10^7.
Added in V3.0.0.