Halcyon 9RLS3 Скачать руководство пользователя страница 12

7 Times

6 Times Continuous

76

3-Way valve thermistor error

3-Way Valve Thermistor Error – When 2-way valve temperature thermistor is open or short-circuited while 

power is on or while running the compressor.  

-Check for erroneous connection or removed connector. 

-Check resistance of thermistor. 

-Check voltage to thermistor.

7 Times

7 Times Continuous

77

Heat sink thermistor error 

Heat Sink Thermistor Error – When heat-sink temperature thermistor is open or a short-circuit is detected at 

power up or while running the compressor.  

-Check for erroneous connection or removed connector. 

-Check resistance of thermistor. 

-Check voltage to thermistor.

8 Times

2 Times Continuous

82

Sub-cool heat ex. gas inlet 

thermistor error / Sub cool heat 

ex. gas outlet thermistor error

Sub-Cool Heat Ex. Gas Inlet Thermistor Error / Sub Cool Heat Ex. Gas Outlet Thermistor Error – Sub cooling heat 

exchanger gas inlet temperature thermistor short or open detected.  

-Check for erroneous connection or removed connector. 

-Check resistance of thermistor. 

-Check voltage to thermistor.

8 Times

3 Times Continuous

83

Liquid pipe thermistor

Liquid Pipe Thermistor Error - Heat exchanger liquid pipe thermistor short or open detected. 

Check for erroneous connection or removed connector. 

-Check resistance of thermistor. 

-Check voltage to thermistor.

8 Times

4 Times Continuous

84

Current sensor error

Current Sensor Error – When input current sensor has detected 0A, while the inverter compressor is operating 

at higher than 56rps, after 1 minute upon starting the compressor. (Except during defrost operation) 

-Check if terminal connection is loose. 

-Check if connector is removed. 

-Check if erroneous connection.

8 Times

6 Times Continuous

86

High pressure switch error

High Pressure Switch Error – When the pressure switch is detected open for longer than 10 seconds after the 

power is turned on. 

-Reset power to disconnect for 3-5 minutes. 

-Check voltage to pressure switch. 

-Check ohm resistance to high pressure switch.

9 Times

4 Times Continuous

94

Over current error

Trip Detection – Protection stop by overcurrent generation after inverter compressor start processing completed 

generated consecutively 10 times. The number of generations is reset if the compressor is able to start up.  

-Clogged heat exchanger. 

-Condenser fan motor defective. 

-Discharged air not sucked in.

9 Times

5 Times Continuous

95

Compressor control error

Compressor Motor Control Error – If the detected rotor location is out of phase with actual rotor location more 

than 90 degrees, the compressor stops. After the compressor restarts, if the same operation is repeated within 

40 seconds, the compressor stops again. 

-Check if connector is removed. 

-Check erroneous connection. 

-Check if cable is open.

Содержание 9RLS3

Страница 1: ...SHOOTING GUIDE FUJITSU GENERAL AMERICA INC 353 Route 46 West Fairfield NJ 07004 866 952 8324 973 575 03881 Service Dept Phone 973 836 0449 Service Dept Fax servicehvac fujitsugeneral com Service Dept...

Страница 2: ...Wired Remote Controller System When the address number set by auto setting manual setting are mixed in on RC group When the duplicated address number exists in one RC group Check for wrong wiring conn...

Страница 3: ...rror Evaporator pipe thermistor detected an abnormal temperature Check thermistor for open for open or short Check thermistor resistance value Refer to Thermistor character istics table Controller PCB...

Страница 4: ...or resistance value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error When the compressor temper...

Страница 5: ...out of phase with actual rotor location more than 90 degrees the compressor stops After the compressor restarts if the same operation is repeated within 40 seconds the compressor stops again Check if...

Страница 6: ...times within 24 hours Check if 3 way valve is open Check EEV strainer Check outdoor unit fan heat exchanger Check discharge thermistor Check refrigerant amount leak check 10 Times 3 Times Continuous...

Страница 7: ...orator Check for correct voltage at panel condenser and evaporator Refer to the Service Instructions manual Serial Signal Troubleshooting for further details 8 Times 0 Wire remote controller error Com...

Страница 8: ...or is loose defective contact Rotate fan motor by hand to ensure it is not locked Controller PCB defective 7 Times 2 Times 0F Discharge temperature error The discharge temperature error is activated H...

Страница 9: ...ing or piping 2 Times 2 Times Continuous 22 Indoor unit capacity error Indoor Unit Capacity Error The total capacity of the indoor units has been exceeded or is under the minimum acceptable range Chec...

Страница 10: ...ch is on for more than 3 minutes error will trigger Check operation of float switch blockages dust etc Remove float and check on off switching operation by using a meter Check connector of CN9 wire Ch...

Страница 11: ...value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error Compressor temperature thermistor is ope...

Страница 12: ...tance of thermistor Check voltage to thermistor 8 Times 4 Times Continuous 84 Current sensor error Current Sensor Error When input current sensor has detected 0A while the inverter compressor is opera...

Страница 13: ...es 1 Time Continuous A1 Discharge temperature error Discharge Temperature Error Protection stop by discharge temperature 230 F 110 C during compressor operation generated 2 times within 24 hours Check...

Страница 14: ...Control System Error Manual Auto button error 4 flashes 2 flashes Off Off 20 Power supply 50 HZ 60 HZ detection error 4 flashes 4 flashes Off Off 08 Electronic air clean filter error 4 flashes 7 flash...

Страница 15: ...oor unit B Off 6 flashes Off Off 3 way valve thermistor error for indoor unit C Off Off 6 flashes Off 3 way valve thermistor error for indoor unit D Off Off Off 6 flashes Compressor thermistor error 7...

Страница 16: ...6 2 Inverter error 6 3 IPM error trip terminal L error 6 5 Discharge temp sensor error 7 1 Compressor temp sensor error 7 2 Heat Ex liquid sensor error 7 3 Outdoor temp sensor error 7 4 Valve sensor...

Страница 17: ...mistor error 2 7 2 Heat Ex middle temp sensor error 2 7 3 Heat Ex liquid temp sensor error 2 7 3 Outdoor thermistor error 2 7 4 Heat sink temp sensor error 2 7 7 Current sensor error 2 8 4 Pressure se...

Страница 18: ...or unit and branch box Serial communication error between branch boxes 4 Serial communication error between branch boxes 5 Serial communication error between indoor unit A and branch box Serial commun...

Страница 19: ...t EX gas inlet thermistor error E212 Number of wires and pipe error E882 Sub cool heat EX gas outlet thermistor error E221 Indoor unit capacity error E831 Liquid pipe thermistor error E242 Number of i...

Страница 20: ...shes Continuous blink Continuous blink Outdoor communication error forward reverse transfer error 6 flashes Continuous blink OFF Indoor fan abnormal Continuous blink 2 flashes OFF Outdoor power source...

Страница 21: ...or 08 Power source connection error 09 Float switch operated 0A Outdoor temperature sensor error 0c Discharge pipe temperature sensor 11 Model abnormal indoor EPROM abnormal 12 Indoor fan abnormal 13...

Страница 22: ...5 ft 49 ft 2 oz ft 9 ft 53A 12RLQ 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RL 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS 2 lbs 9 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS2 12RLS2H 2 lbs 10 oz 49 ft 66...

Страница 23: ...164 ft 21 oz ft 16 ft 24A 24RLXFZH 4 lbs 14 oz 98 ft 229 ft 21 oz ft 16 ft 49 ft combined N A 30CLX 30CLX1 4 lbs 10 oz 66 ft 165 ft 43 oz ft 16 ft 36A 34A 30RLXB 4 lbs 10 oz 66 ft 164 ft 43 oz ft 16...

Страница 24: ...12 7 67 80 3 68 20 12 54 5 86 62 91 28 14 64 5 62 55 6 1 12 64 6 1 62 9 77 25 10 5 24 49 7 25 15 51 27 49 84 4 89 10 4 89 49 7 86 30 8 04 4 64 39 57 22 26 41 07 40 01 3 95 7 97 3 95 39 6 95 35 6 51 3...

Отзывы: