PFC circuit error (9/12RLS3) / 

Active filter error (15RLS3, 

30RLXEH)

PFC Circuit Error (9/12RLS3) – When inverter output DC voltage is higher than 415V for over 3 seconds, the 

compressor stops. If the same operation is repeated 5 times, the compressor stops permanently. 

-Check external cause at the indoor and outdoor (voltage drop or noise). 

-Check connection of connector, loose, erroneous connection. 

-Replace Main PCB.  

Active Filter Error (15RLS3, 30RLXEH) – When inverter input DC voltage is higher than 425v or lower than 80V. 

When a momentary power cut off occurred on low voltage. 

-Check external cause at the indoor and outdoor (voltage drop or noise). 

-Check connection of connector, loose, or erroneous connection. Check Active Filter Module resistance values.

6 Times

5 Times Continuous

65

IPM error

IPM Error – Abnormal current value at the IPM is detected. Heat radiation is blocked (inlet/outlet). 

-Check connections of outdoor unit electrical components. 

-Check outdoor fan, heat exchanger. -Check compressor resistance values.

6 Times

10 

Times

Continuous

6A

Display PCB communication error Display P.C.B. Error – Communication not received from I/O PCB for more than 10 seconds. 

-Check molex plug connection for loose or erroneous connection.

7 Times

1 Time

Continuous

71

Discharge thermistor error

Discharge Thermistor Error – When discharge pipe temperature thermistor open or short-circuit is detected at 

power up or while running the compressor. 

-Check connection of connector, loose, erroneous connection. 

-Check thermistor for open for open or short. Check thermistor resistance value (Refer to “Thermistor 

characteristics table”). -Check voltage of Main PCB.

7 Times

2 Times Continuous

72

Compressor thermistor error

Compressor Thermistor Error – Compressor temperature thermistor is open or short-circuited while power is on 

or running the compressor. 

-Check for erroneous connection or removed connector. 

-Check resistance on thermistor. -Check voltage to thermistor.

7 Times

3 Times Continuous

73

Heat Ex. (Pipe) thermistor error

Heat Exchanger (Pipe) Thermistor Error – When heat exchanger temperature thermistor open or short-circuit is 

detected at power on or while running the compressor. 

-Check connection of connector, loose, or erroneous connection. 

-Check thermistor for open or short. Check thermistor resistance value (Refer to “Thermistor characteristics 

table”). -Check voltage of Main PCB.

7 Times

4 Times Continuous

74

Outdoor thermistor error

Outdoor Thermistor Error – When outdoor temperature thermistor is open or a short-circuit is detected at power 

on or while running the compressor.  

-Check connection of connector, loose, erroneous connection. 

-Check thermistor for open or short. Check thermistor resistance value (Refer to “Thermistor characteristics 

table”).

7 Times

5 Times Continuous

75

Suction gas thermistor error

Suction Gas Thermistor Error – Suction gas temperature thermistor has shorted or open detected. 

-Check the connection of the molex plug, loose or erroneous connection. 

-Check ohm resistance readings of thermistor. -Check voltage of Main PCB.

7 Times

6 Times Continuous

76

2-Way valve thermistor error

2-Way Valve Thermistor Error – When 2-way valve temperature thermistor is open or short-circuited while 

power is on or while running the compressor.  

-Check for erroneous connection or removed connector. 

-Check resistance of thermistor. -Check voltage to thermistor.

Содержание 9RLS3

Страница 1: ...SHOOTING GUIDE FUJITSU GENERAL AMERICA INC 353 Route 46 West Fairfield NJ 07004 866 952 8324 973 575 03881 Service Dept Phone 973 836 0449 Service Dept Fax servicehvac fujitsugeneral com Service Dept...

Страница 2: ...Wired Remote Controller System When the address number set by auto setting manual setting are mixed in on RC group When the duplicated address number exists in one RC group Check for wrong wiring conn...

Страница 3: ...rror Evaporator pipe thermistor detected an abnormal temperature Check thermistor for open for open or short Check thermistor resistance value Refer to Thermistor character istics table Controller PCB...

Страница 4: ...or resistance value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error When the compressor temper...

Страница 5: ...out of phase with actual rotor location more than 90 degrees the compressor stops After the compressor restarts if the same operation is repeated within 40 seconds the compressor stops again Check if...

Страница 6: ...times within 24 hours Check if 3 way valve is open Check EEV strainer Check outdoor unit fan heat exchanger Check discharge thermistor Check refrigerant amount leak check 10 Times 3 Times Continuous...

Страница 7: ...orator Check for correct voltage at panel condenser and evaporator Refer to the Service Instructions manual Serial Signal Troubleshooting for further details 8 Times 0 Wire remote controller error Com...

Страница 8: ...or is loose defective contact Rotate fan motor by hand to ensure it is not locked Controller PCB defective 7 Times 2 Times 0F Discharge temperature error The discharge temperature error is activated H...

Страница 9: ...ing or piping 2 Times 2 Times Continuous 22 Indoor unit capacity error Indoor Unit Capacity Error The total capacity of the indoor units has been exceeded or is under the minimum acceptable range Chec...

Страница 10: ...ch is on for more than 3 minutes error will trigger Check operation of float switch blockages dust etc Remove float and check on off switching operation by using a meter Check connector of CN9 wire Ch...

Страница 11: ...value Refer to Thermistor characteristics table Check voltage of Main PCB 7 Times 2 Times Continuous 72 Compressor thermistor error Compressor Thermistor Error Compressor temperature thermistor is ope...

Страница 12: ...tance of thermistor Check voltage to thermistor 8 Times 4 Times Continuous 84 Current sensor error Current Sensor Error When input current sensor has detected 0A while the inverter compressor is opera...

Страница 13: ...es 1 Time Continuous A1 Discharge temperature error Discharge Temperature Error Protection stop by discharge temperature 230 F 110 C during compressor operation generated 2 times within 24 hours Check...

Страница 14: ...Control System Error Manual Auto button error 4 flashes 2 flashes Off Off 20 Power supply 50 HZ 60 HZ detection error 4 flashes 4 flashes Off Off 08 Electronic air clean filter error 4 flashes 7 flash...

Страница 15: ...oor unit B Off 6 flashes Off Off 3 way valve thermistor error for indoor unit C Off Off 6 flashes Off 3 way valve thermistor error for indoor unit D Off Off Off 6 flashes Compressor thermistor error 7...

Страница 16: ...6 2 Inverter error 6 3 IPM error trip terminal L error 6 5 Discharge temp sensor error 7 1 Compressor temp sensor error 7 2 Heat Ex liquid sensor error 7 3 Outdoor temp sensor error 7 4 Valve sensor...

Страница 17: ...mistor error 2 7 2 Heat Ex middle temp sensor error 2 7 3 Heat Ex liquid temp sensor error 2 7 3 Outdoor thermistor error 2 7 4 Heat sink temp sensor error 2 7 7 Current sensor error 2 8 4 Pressure se...

Страница 18: ...or unit and branch box Serial communication error between branch boxes 4 Serial communication error between branch boxes 5 Serial communication error between indoor unit A and branch box Serial commun...

Страница 19: ...t EX gas inlet thermistor error E212 Number of wires and pipe error E882 Sub cool heat EX gas outlet thermistor error E221 Indoor unit capacity error E831 Liquid pipe thermistor error E242 Number of i...

Страница 20: ...shes Continuous blink Continuous blink Outdoor communication error forward reverse transfer error 6 flashes Continuous blink OFF Indoor fan abnormal Continuous blink 2 flashes OFF Outdoor power source...

Страница 21: ...or 08 Power source connection error 09 Float switch operated 0A Outdoor temperature sensor error 0c Discharge pipe temperature sensor 11 Model abnormal indoor EPROM abnormal 12 Indoor fan abnormal 13...

Страница 22: ...5 ft 49 ft 2 oz ft 9 ft 53A 12RLQ 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RL 1 lb 12 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS 2 lbs 9 oz 49 ft 66 ft 2 oz ft 9 ft 26A 12RLS2 12RLS2H 2 lbs 10 oz 49 ft 66...

Страница 23: ...164 ft 21 oz ft 16 ft 24A 24RLXFZH 4 lbs 14 oz 98 ft 229 ft 21 oz ft 16 ft 49 ft combined N A 30CLX 30CLX1 4 lbs 10 oz 66 ft 165 ft 43 oz ft 16 ft 36A 34A 30RLXB 4 lbs 10 oz 66 ft 164 ft 43 oz ft 16...

Страница 24: ...12 7 67 80 3 68 20 12 54 5 86 62 91 28 14 64 5 62 55 6 1 12 64 6 1 62 9 77 25 10 5 24 49 7 25 15 51 27 49 84 4 89 10 4 89 49 7 86 30 8 04 4 64 39 57 22 26 41 07 40 01 3 95 7 97 3 95 39 6 95 35 6 51 3...

Отзывы: