Assembly and installation
NOTICE
Installation according to manufacturer’s instructions
1. Install the control unit in accordance with the manufacturer’s instructions and the respective
national regulations and provisions as well as the relevant installer provisions.
2. The protective conductor must always be laid alongside and connected.
Target group
Unless assigned otherwise, the assembly and installation are carried out by skilled per-
sonnel of HAINKE Filteranlagen GmbH .
Work on the electrical installation is only carried out by electrically skilled personnel.
Work on live parts is not planned.
Safety instructions
After assembly and connection of the control, it must be ensured that degree of pro-
tection IP65 to EN 60529 is achieved again for the enclosure.
WARNING
Control is not suitable for operation in this use case
According to its marking, the equipment must be suitable for the existing hazardous
area, otherwise there is a risk of explosion.
–
Compare the technical data and ambient conditions exactly
General
The control is suitable for mounting in an industrial installation.
Mount the control in a vibration-free location.
Mounting enclosure
The control in the mounting enclosure is suitable for mounting in the installation.
The operation is permitted for:
• Hazardous area Zone 22
• non-conductive dust
• the potentially explosive medium does not occur or only rarely/for a short time
due to air/dust mixtures
• outside potentially explosive atmospheres
Installation
1. Compare the equipment marking and case of application.
2. Remove the cover.
ð
The fixing holes are accessible.
3. Mount the control in the visible area.
4. Protect from mechanical damage.
5. Close off cable entries properly.
6. After installation, screw on the cover with all the screws provided.
7. Explosion protection to EN 60079-14 must be established.
ð
The control is mounted.
Outdoor installation
1. Take suitable measures to protect the enclosure from the weather, e.g. by a canopy or sim-
ilar.
Installation in poten-
tially explosive atmo-
spheres
All cables must be routed properly through cable entries, which are approved for use in
potentially explosive atmospheres.
The mounting must be done properly.
Cable entries that are not required must be fitted with plugs, which are approved for
use in potentially explosive atmospheres.
The requirements of EN 60079-14 must be met.