Loose frosting and poor refrigerating effect may occur if excessive refrigerant has been
charged into the system. Excess refrigerant will occupy additional space in the evaporator.
This will reduce its heat dissipating area, and the phenomenon of “liquid striking” may
occur. Condensation may occur on the gas return tube, and the gas discharge pressure will
rise. When it reaches the threshold value, the protective relay will actuate and shut off the
power supply to the compressor.
Remedy
Open the tubing. Re-evacuate and charge the system with a proper quantity of refrigerant.
2) Air in the system
Analysis of Trouble
The residual air in the system will circulate with the refrigerant in the system. The major
symptoms are higher gas discharge pressure, higher discharged gas temperature, and poor
refrigerating effect. The gas discharge pressure will exceed its maximum value when the
compressor has run for an extended period, and activates the protective relay.
Remedy
Check the air has been in the refrigerating system. Generally, there are three possibilities.
First, is that the air has been sucked into the system during repairs due to carelessness.
Secondly, it has not been completely purged evacuating the system. The third possibility is
that there are leak points at the low-pressure end of the refrigerating system. Leak points
appear in low temperature parts or assemblies. This is because the evaporation temperature
is lower for such low temperature devices, especially at the low-pressure end; it is easier for
the air to go into the system. Once it has been ascertained that air does exist in the system,
you have to open the tubing, re-evacuate it and then charge it with refrigerant.
Stoppage due to electrical troubles
Thermostat is out of control due to electric troubles
Analysis of Trouble
In case the thermostat does not work in its good order or its temperature sensor has not
been installed properly, frequent stoppage is also likely to occur.
Remedy
Try to adjust the temperature sensor’s position until the compressor can be started and
stopped normally. If this cannot be achieved, and the stoppage still occurs repeatedly, it is
most likely that the mechanical parts or contacts are out of order, disassemble the
thermostat, make a thorough checkup and repair it.
Overload of electric motor
Analysis of Trouble
Probably, too many things have been put into the refrigerator, and hence the thermal load
exceeds its refrigerating capacity; or in case the power supply voltage drops considerably,
the current flowing through the motor will increase drastically making the thermal protector
actuate and the fuse blown, and hence the motor stops running. If the motor is still running
continuously in such a case, its windings will be burned out.
Remedy
Reduce the thermal load, pay attention to the variation in voltage of the power supply
.
Содержание RF-8888-279
Страница 1: ...1 HAIER REFRIGERATOR Service Manual PART RF 8888 279 HAIER AMERICA TRADING LLC www haieramerica com ...
Страница 3: ...3 Features Flat Back Design Freezer Compartment With Ice Cube Tray ...
Страница 4: ...4 Product code Explanation and Series Introduction ...
Страница 10: ...10 Parts and Functions ...
Страница 11: ...11 Function Schedule Flat Back Design Freezer Compartment With Ice Cube Tray ...
Страница 14: ...14 Maintenance Service and Troubleshooting 1 When the refrigerator does not get cold at all ...
Страница 15: ...15 2 The refrigerator is not sufficiently cold ...