HSU-09/12H03/R(QXF) Functions and control
14
Domestic Air Conditioner
Trial run function
Emergency
running mode
Temperature
compensation
Sleeping function
When the air conditioner is in OFF state, press the emergency switch for 5 seconds till
hearing 2 sounds of click from the buzzer, then the air conditioner will turn to the trial run
state. The unit will run in the refrigerating mode and the indoor fan will run in high wind
speed mode.
When the air conditioner is in stand-by state, press the emergency switch till hearing a
sound from the buzzer, then the air conditioner will turn to the emergency run state. The
rules of emergency run are as follows:
Tr
23
ć
, running refrigerating mode, Ts = 26
ć
;
Tr<23
ć
, running heating mode, Ts = 23
ć
.
There is the function of automatic temperature compensation when heating,
with heating temperature setting = Ts(remote setting) + 4
ć
.
After setting the sleeping function, the refrigerating mode and dehumidification mode will
run as per the following rules:
6hours
T(
ć
)
1 hour
Ts+2
Ts+1 1 hours
Ts
Sleep
OFF
t(hour)
a.
After setting the sleeping function, the heating mode will run as per the
following rules:
T(
ć
)
Ts 3hours 3hours
Ts-2
Ts-3
Ts-4
1 hour
As shown in the above diagram, after running for 1 hour under refrigerating mode and
dehumidification mode, the setting temperature will increase 1
ć
; after another 1 hour, it
will increase 1
ć
again, and after 6 hours, it will cease; after running for 1 hour under
heating mode, the setting temperature will decrease 2
ć
, after another 1 hour, it will
decrease the 2
ć
again, and after 3 hours, it will increase 1
ć
, and after other 3 hours, it
will cease.