DIP SWITCH SETTING
(B) Definition and description of SW02
• SW02_1-8 is used to set indoor unit address on system. Set address only if using central controller YCZ-A004 and
HC-LA1CDBT. Leave default if no central controller is used.
SW02_1
Adress setting
mode
[1] Address setting mode
[0] Automatic setting (default)
[1] Code-set address
SW02_2
~
SW02_8
Code-set indoor
unit address
and centralized
controller
address
[2] [3] [4] [5] [6] [7] [8] Address of indoor unit Address of centralized controller
0
0
0
0
0
0
0
0# (Default)
0# (Default)
0
0
0
0
0
0
1
1#
1#
0
0
0
0
0
1
0
2#
2#
…
…
…
…
…
…
…
…
…
0
1
1
1
1
1
1
63#
63#
1
0
0
0
0
0
0
0#
64#
1
0
0
0
0
0
1
1#
65#
1
0
0
0
0
1
0
2#
66#
…
…
…
…
…
…
…
…
…
1
1
1
1
1
1
1
63#
127#
Note:
• Set the address by code when connecting the centralized controller or gateway or charge system.
• Address of centralized controller=communication a 0 or + 64.
• SW02_ 2=OFF, address of centralized controller = communication a 0 =c ommunication address
• SW02_ 2=ON, address of centralized controller = communication a 64 (applies when centralized controller is
used and there are more than 64 indoor units)
(C) Definition and description of SW01
SW01_1
Model selection
0
Reserved
1
Model selection 42K/54K
SW01_2
Has filter or not
0
Filter reminder cancelled (Default)
1
Filter reminder (EE: time 750h)
SW01_3
~
SW01_4
Electric heating
parameter
setting
[3][4]
ΔT and ∆Tp
0
0
Default value EE group 1: ΔT=2F and ∆Tp=10min
0
1
Group 2: EE ΔT=3F and ∆Tp=15min
1
0
Group 3: EE ΔT=4F and ∆Tp=20min
1
1
Reserved