Haier HYCD-282 Скачать руководство пользователя страница 13

HYCD-282/282A/282C_Service Manual 

13 

 

a

 

Users parameter setting   

No. 

Parameter    Name 

Range   

HYCD-282/A/C   

default value 

Remark   

L0 

Temp set 

value 

Cool 

0~16 

 

Freeze 

-10~-45 

-40

HYCD-282C:-30

 

L1 

High temp 

alarm value 

Cool 

set value

L0+5

~+50 

10 

 

Freeze 

set value

L0+5

~+50 

-35

HYCD-282C:-25

 

 

L2 

Low temp 

alarm value 

Cool 

-60~set value

L0-5

 

 

Freeze 

-60~set value

L0-5

 

-45

HYCD-282C:-35

 

 

L3 

Inquire 

Voltage   

-- 

-- 

Show the voltage 

L4 

Inquire 

ambient temp 

-- 

-- 

Show the ambient temp 

L5 

Compressor 

stop set 

0 or 1 

“0”means off

“1”means 

on 

b

 

Defrosting function 

Status of defrost in refrigerator space

inner fan works

compressor stop working, it    is defrost   

Forced defrost in freezer space

unlock status

press “

”    for 5s

The freezer compressor stop work

the freezer

temp. zone will show “dF” for 3s and the cabinet temp for 5s alternately. 

If we want to stop the defrost function, we should press 5s again at unlock status, and the compressor begin to work.   

c

 

Safe mode of Sensor faulty 

When  the  temp.  sensor  is  faulty 

the  freezer  compressor  will  be  30mins  on  and  10mins  off  with  the  alarm

The 

refrigerator compressor will be 15mins on and 15mins off with alarm. 

d

 

USB storage function

HYCD-282C optional

 

Item   

Steps   

Display Msg 

Data 

export 

1

plug the  U-disk to the USB port, the data 

will be exported automatically

 

 

2

unlock  status

press“

”  and  “

” 

for3s to inquire the status of data export 

Refrigerator  temp  zone  show  “USb”

freezer  temp 

zone show “…”— means the data is exporting; 

Refrigerator  temp  zone  show  “USb”

freezer  temp 

zone show “OK”— means the data has been exported. 

Time 

setting 

1

unlock status

press“

”and “

”and  Refrigerator  temp.  zone  show  “1P”

freezer  temp. 

zone show the value of “1P”. 

Содержание HYCD-282

Страница 1: ...Combined Refrigerator and Freezer Model HYCD 282 282A 282C Pictures Service Manual ...

Страница 2: ...odel 3 2 Appearance and Parts 3 3 Product Technical Parameters 4 4 Electrical parts and circuit diagram 5 5 Spare parts of cooling system 6 6 Spare part list and exploded view 7 7 Instruction of operation 9 8 Replacement of main parts 15 9 The curve of temperature 17 ...

Страница 3: ...HYCD 282 282A 282C_Service Manual 3 1 Definition of the Model H Haier Y Medical CD cooling and freezer 282 capacity is 282L 2 Appearance and Parts ...

Страница 4: ...2 8A 400W 2 8A 400W 2 8A Controller Microprocessor Microprocessor Microprocessor Qty of sensor 3 3 3 Alarm type Buzzer light remote Buzzer light remote Buzzer light remote Alarm content High low temp sensor error power failed low battery door Ajar high ambient temp High low temp sensor error power failed low battery door Ajar high ambient temp High low temp sensor error power failed low battery do...

Страница 5: ...SB board 1 10years HYCD 282C optional 4 0074091430 Battery 1 12V 5 0274000232 Printer 8000 Pcs data Only in china 6 0064001173 LED 1 5V 7 0070401365 Transformer of door heater 1 AC 33V Only HYCD 282A 8 0270800323 Glass door with heater 1 AC 40V 25W Only HYCD 282A 9 0274000087A Thermostat 1 Only HYCD 282A 10 0074090544 Evaporator fan 1 EBM fan motor 19W 11 0074090544 Condenser fan 2 EBM fan motor 1...

Страница 6: ...90 Freeze compressor 1 SC12CLX 2 220V 60Hz 3 0070701944 Condenser 2 4 0270700046 Cool evaporator 1 In the foam layer can t be replaced 5 0270700100 Freezer evaporator 1 In the foam layer can t be replaced 5 0270100458A Freezer evaporator 1 HYCD 282C In the foam layer can t be replaced 6 0074180002A Drier filter 2 7 0070301474 R600a QTY R600a 50g 220V 50Hz cool system 0070301474 R134a QTY R134a 150...

Страница 7: ...0993 继电器 Relay 2 6 0274000087A 机械温控器 Thermostat 1 HYCD 282A only 7 0271800008 主控板 Control board 1 8 0270100491 电器支架 PCB support 1 9 0270100496 电控箱后盖 Back cover of electrical box 1 10 0270800305 箱体 Main body 1 HYCD 282 0270800327 箱体 Main body 1 HYCD 282A 0270803505 箱体 Main body 1 HYCD 282C 11 0070102180 止推架 Stopper 2 12 0270200052 锁扣 Lock catch 2 13 0070701944 冷凝器 Condenser 2 14 0074091262 冷藏压缩机 Co...

Страница 8: ...65 变压器 Transformer 1 HYCD 282 only 34 0270100489 上铰链 Upper hinge 1 35 0270100497 冷藏上隔板 Upper shelf in cool space 1 36 0270400077 环温传感器 Ambient temp sensor 1 37 0270100480 前面罩 Front cover 1 38 0271800009 显示板 Display panel 1 39 0270200184 显示板罩 Display cover 1 40 0270500140A 显示板贴 Display label 1 HYCD 282 282C 0270500140C 显示板贴 Display label 1 HYCD 282A 41 0074090884 冷藏传感器 Cool Temp sensor 1 42 0270100...

Страница 9: ...e parameters and alarm code for cool function Freezer temperature zone The temperature parameters and alarm code for cool function Alarm indicator light light flashing means alarm happened Lock indicator light light means the lock status Set setting parameters and confirm Digit Tran adjusting the bit of the parameter Temp adjust adjusting the temp Temp zone Tran swap the display between refrigerat...

Страница 10: ... the freezer are displayed on the displayed screen and the second digit flashes on the display screen if it is not used for the first time the temperature set last time will be displayed By pressing button the flashing digit changes and by pressing the value of the currently flashing digit can be changed Adjust to the required temperature and by pressing again the set value becomes valid and is st...

Страница 11: ...shes on the display screen the default normal start stop status of the compressor and if the refrigerator freezer is to be stopped press temperature adjustment and 1 is changed into 0 The refrigerator freezer cannot be used again until a change for 1 is done again 8 Setting inquiry In the state of being unlocked press the button set L0 appears on the display screen and digit 0 flashes Press temper...

Страница 12: ...L5 3 short press the second bit flash 3 short press adjust the bit of the LEDs short press to adjust the value Notice If the refrigerator temp zone show the temp and the freezer temp zone shows L0 we need to press then refrigerator temp zone will show L0 when we want to adjust the parameter L0 L5 we must change the L0 to the temp zone that we need Compressor Start delay 1 unlock status press and a...

Страница 13: ... work the freezer 冷 temp zone will show dF for 3s and the cabinet temp for 5s alternately If we want to stop the defrost function we should press 5s again at unlock status and the compressor begin to work c Safe mode of Sensor faulty When the temp sensor is faulty the freezer compressor will be 30mins on and 10mins off with the alarm The refrigerator compressor will be 15mins on and 15mins off wit...

Страница 14: ... power it enters the active state and temperature in the cabinet is displayed on the indicator Operating state reminder on the display panel Lock indicator lamp with the lamp on all settings are locked to avoid error operation Alarm if the lamp is on or flashing there is failure Button function Buzz cancel in the state of being locked or unlocked and during alarm by pressing the the alarming sound...

Страница 15: ...an go through the shelves 4 The freezer has 4 wheels and 2 feet After installation make the two feet back to the earth keep the freezer stably 8 Replacement of main parts a Checking the PCB USB board thermostat transformer and battery The control board thermostat USB board and the battery are in the top space of the freezer Step1 Remove the screws on the top of the freezer then we can remove the t...

Страница 16: ..._Service Manual 16 b The position of the temp sensor The position of the refrigerator temp sensor upper sensor The freezer sensor lower sensor c unpacking step1 Use a knife to cut down the packing belt and remove the box ...

Страница 17: ...pallet Tilt the freezer and pull out the pallet the angle of inclination should be less than 45 degree 9 The curve of temperature HYCD 282 HYCD 282A HYCD 282C temperature curve of refrigerator temp zone Remove the box belts Lift up the box Remove the pallet Remove the plates of pallet ...

Страница 18: ...HYCD 282 282A 282C_Service Manual 18 HYCD 282 HYCD 282A freeze temp curve HYCD 282Cfreeze temp curve ...

Страница 19: ...HYCD 282 282A 282C_Service Manual 19 Inspired living Haier Medical Laboratory Products Co Ltd Room 403D Brand Building Haier Industrial Park No 1 Haier Road Qingdao China Website www haiermedical com ...

Отзывы: