33
Function
Parameter Range
Default
Zone 1 Compensation Temp. of Cooling
-15~15°C
0°C
Zone 1 Compensation Temp. of Heating
-15~15°C
0°C
Zone 2 Compensation Temp. of Cooling
-15~15°C
0°C
Zone 2 Compensation Temp. of Heating
-15~15°C
0°C
DHW Compensation Temp.
-15~15°C
0°C
Swimming Pool Compensation Temp.
-15~15°C
0°C
Note: Actual target temperature of system=Set target temperature of cont Compensation temperature
③
System installation
Tap “SYSTEM INSTALLATION” icon in Picture 22 to enter the system control parameters setting interface. You can set
the operating parameters for the system.
Picture 25
Function
Parameter Range
Default
Control Mode of Zone1
Main controller, Third party controller, IDU ambient Temp. sensor
Main controller
Control Mode of Zone2
Main controller, Third party controller, IDU ambient Temp. sensor
Main controller
Control Mode of DHW
Main Controller, Third Party Controller
Main Controller
Control Mode of Pool
Main Controller, Third Party Controller
Main Controller
Zones Water Temp. Control Mode
Direct, Auto curve, Set curve
Direct
Auxiliary Heat Source
IDU Electric Heater, Boiler, IDU Electric Boiler
IDU electric
Heating
Outdoor Temp. for (Heat to Cool)
0~30°C
15°C
Outdoor Temp. for (Cool to Heat)
0~30°C
10°C
DHW On Temp.
30~55°C
45°C
Ambient Temp. of Heating Off
5~35°C
27°C
△
T for Heating On
0~15°C
6°C
Outdoor Temp. for Heater On
-20~15°C
0°C
Heater On Delay Time
0~120min
60min
Heater On
△
T of Target Temp.
-10~2°C
-3°C
Heater Off
△
T of Target Temp.
-8~0°C
-1°C
Tank Re-heat Temp.
-12~2°C
-3°C
△
T for Cooling On
1~15°C
5°C
Target Temp. of DHW IO Board
25~75°C
45°C
Target Temp. of Pool IO Board
20~30°C
24°C
Travel Time of Mixing Valve
30s~90s
60s
Operation instructions for controller