Open

No gas leakage?

5.

Detach the charge hose

6.

from the service port, open 2-way valve and 3-way. Turn

Anti countercurrent joint

Gaugemanifold(for R410A)

2-way valve Liquid Side

3-way valve Gas Side

Vacuum pump(for R410A)

Tube(for R410A)

Close

2-way valve

3-way valve

Open 90

O

2-way valve

3-way valve

2-way valve 3-way valve

2-way valve

3-way valve

Valve rod cap

Valve rod cap

Service port cap

To prevent the gas leakage, turn the service port’s cap, the valve rod’s cap for 2-way

valve and 3-way’s a little more than the point where the torque increases suddenly.

After attaching the each caps, check the gas leakage around the caps.

7.

8.

Step 1.

Step 2.

Step 3.

Step 7.

Step 6.

Step 4.

The power source must be exclusively used for air

ƽ

conditioner. (Over I0A)

In the case of installing an air conditioner in a moist place,

ƽ

please install an ea-

For installation in other places, use a circuit breaker as far

ƽ

as possible.

Pipe cutting is carried out with  a  pipe cutter and burs must

ƽ

be removed.

After inserting the flare nut, flaring  work is carried out.

ƽ

If the refrigerant  of  the air conditioner leaks, it is necessary to discharge all the

ƽ

refrigerant. Vacuum first, then charge the liquid refrigerant into air conditioner
according to the amount marked on the name plate.

Please do not let  other cooling medium, except specified one  (R410A), or air

ƽ

enter into the cooling circulation system. Otherwise, there will be abnormal

Power Source Installation

Cutting and Flaring Work of Piping

Flare tooling die

1.Cut pipe

2.Remove burs

3.Insert the flare nut

CAUTION

rth leakage breaker (GFCI).

4.Flare pipe

Lean

Damage of flare Crack

Partial

Too outside

Correct

Incorrect

On Drainage

It becomes

high midway.

The gap with the

ground is too small

There is the bad
smell from a ditch

It waves.

The end is imm-
ersed in water.

Please install the drain hose so as to be downward slope without fail.
Please don’t do the drainage as shown below.

ƽ
ƽ

Please pour water in the drain pan  of  the indoor unit, and

ƽ

is carried out surely to outdoor.

In case that the attached drain hose is in a room, please

ƽ

apply heat insulation to

Less than

5cm

confirm that drainage

it without fail.

4

Check Items for Test Run

Put check mark

in boxes

Gas leak from pipe connecting?

Heat insulation of pipe connecting?

Are the connecting wirings of indoor and outdoor firmly

Is the connecting wiring of indoor and outdoor firmly fixed?
Is drainage securely carried out?
Is the earth line securely connected?
Is the indoor unit securely fixed?
Is power source voltage abided by the code?

Is there any noise?

Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?

Is the operation of room temperature regulator normal?

Please kindly explain to our customers how to operate
through the instruction manual.

Check for Installation and Test Run

Ƶ

inserted to the terminal block?

Ƶ

1

1+2=

kg

R410A

2

kg

2=

1=

B

C

D

F

E

kg

A

This product contains fluorinated greenhouse gases covered by 
the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A
GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1      the factory refrigerant charge of the product
• 2      the additional refrigerant amount charged in the field and
• 1+2  the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop valve cover).
A  contains fluorinated greenhouse gases covered by the Kyoto 
Protocol
B  factory refrigerant charge of the product: see unit name plate
C   additional refrigerant amount charged in the field
D   total refrigerant charge
E   outdoor unit
F   refrigerant cylinder and manifold for charging 

Contains fluorinated greenhouse gases
covered by the Kyoto Protocol

Refrigerant charge label

Ƶ

the valve rod counterclockwise.

In case of gas leakage, tighten parts of pipe connection. If leakage stops,
then proceed

Flare tool for R410A

Conventional flare tool

Clutch-type

clutch-type(Rigid-type) Wing-nut type (Imperial-type)

A

0~0.5mm

1.0~1.5mm

1.5~2.0mm

step 6. If leak continues, remove the refrigerant used for the 

leakage check and flare tubes again. Repeat vacuum and leak and if no 
leakage, proceed to step 6.

0~1/51 inch

3/76 ~1/17 inch

1/17 ~1/8 inch

high pressure in the system casuing damage and possibly personal injuries.

Содержание HSU18VCK

Страница 1: ...f the unit are not disturbed Possible to drain easily where piping can be connected with the outdoor unit Where cold air can be spread in a room evenly Nearby a power receptacle Refer to drawings Not less affected by rain or direct sunlight and is sufficiently ventilated Strong enough to bear the unit where vibration and noise are not increased Please be subject to the actual product purchased the ...

Страница 2: ...pull it out on the front side then connect them 3 Coat the flaring seal face with refrigerant oil and connect pipes Fixing the indoor unit body ƽ In order to fix the body onto the mounting plate hold up ƽ the body aslant from the underside and then put it down perpendicularly Connecting the indoor outdoor Electric Cable Removing the wiring cover Remove terminal cover at right bottom corner of indoor...

Страница 3: ...7m Max Length Bmax 5m In case the pipe length B is more than 10m the refrigerant should be charged according to 50 g m 3 Connection If the drain elbow is used ƽ please attach it as figure Note Only for heat pump unit Detach the service port s cap of 1 3 way valve the valve rod s cap for 2 way valve and 3 way s connect the service port into the projection of charge hose Iow for gaugemanifold Then co...

Страница 4: ...se ƽ apply heat insulation to Less than 5cm confirm that drainage it without fail 4 Check Items for Test Run Put check mark in boxes Gas leak from pipe connecting Heat insulation of pipe connecting Are the connecting wirings of indoor and outdoor firmly Is the connecting wiring of indoor and outdoor firmly fixed Is drainage securely carried out Is the earth line securely connected Is the indoor unit s...

Страница 5: ... la unidad no cause una molestia a los vecinos Coloque la unidad en un lugar en el que pueda disponerse de la distancia de separación marcada en la figura anterior Herramientas necesarias para realizar la instalación Fuente de alimentación Selección del lugar de instalación diagrama de instalación de unidades interiores y exteriores Los modelos cumplen la norma R410A sobre refrigerantes libres de H...

Страница 6: ...con la posición del orificio en la pares Tenga cuidado de no romper los tubos al doblarlos Conecte previamente el cable eléctrico de interior exterior y tire de la conexión al aislante de calor del componente de conexión Conexión de los cables eléctricos de interior exterior Accesorios Selección de tubo Al fijar por primera vez la placa de montaje Al montar la placa de montaje fijándola a una barra l...

Страница 7: ... 7m 27 9 16 se verán afectadas las funciones de la unidad Si es necesario alargar el tubo deberá cargarse refrigerante adicional a razón de 50 g m 0 045 oz pulgada No obstante la carga de refrigerante deberá ser realizada por un ingeniero profesional en aire acondicionado Antes de añadir refrigerante adicional realice una purga de aire desde los tubos refrigerantes y la unidad interior utilizando ...

Страница 8: ...nvernadero regulados por el Protocolo de Kioto B Carga de refrigerante que contiene el producto de fábrica consulte la placa de características de la unidad C Cantidad de refrigerante adicional cargada durante la instalación D Carga total de refrigerante E Unidad exterior F Botella de refrigerante y colector de carga Prueba de instalación y ejecución de la prueba Explique al cliente cómo utilizar ...

Страница 9: ...acement où le vent et le bruit ne risquent pas de gêner les voisins Choisir un endroit dans lequel les distances marquées illustrées dans le schéma ci dessus sont disponibles Outillage requis pour l installation Source d alimentation Sélection de l emplacement pour l installation schéma d installation des unités intérieures et extérieures Les modèles utilisent le réfrigérant R410A sans HCFC Dispos...

Страница 10: ...le pour la tuyauterie en fonction de la direction de la tuyauterie et cintrez ensuite le tuyau selon la position du trou dans le mur Lors du cintrage prenez soin de ne pas écraser les tuyaux Connectez au préalable le câble des unités intérieures extérieures et recouvrez ensuite les câbles connectés avec l isolation Connexion du câble des unités intérieures extérieures Accessoires Sélection du tuya...

Страница 11: ... entrés dans le tuyau La longueur standard du tuyau est de 7 m 27 9 16 Au delà de 7 m 27 9 16 l unité ne fonctionnera pas correctement S il faut rallonger le tuyau le réfrigérant doit être chargé selon 50 g m 0 045 oz pouce Toutefois la charge de réfrigérant doit être exécuté par un professionnel de la climatisation Avant d ajouter du réfrigérant purgez l air des tuyaux de réfrigération et de l un...

Страница 12: ...unité voir sur la plaque signalétique de l unité C Quantité supplémentaire de réfrigérant chargée sur place D Charge totale de réfrigérant E Unité extérieure F Cylindre réfrigérant et collecteur de chargement Vérification de l installation et test de fonctionnement Expliquez le fonctionnement à vos clients en vous servant du manuel Cochez les cases 9 Fuite de gaz dans le raccordement du tuyau Isola...

Отзывы: