background image

1. If the fuse on PC board is broken please change it with the type of 

T. 3.15A/250V (indoor unit), 25A/250V(outdoor unit).

2. The wiring method should be in line with the local wiring standard.

3. After installation, the power plug should be easily reached.

4.  A  breaker should be incorporated into fixed wiring. The breaker should be

all-pole switch.

Outdoor unit

Install according to

Drawing for the installation of indoor and outdoor units

ƽ

and the bending radius should be 30(1 1/6) to 40 mm(1 4/7) or longer.

Connecting the pipe of gas side first makes working easier.

ƽ

The connection pipe is specialized for R410A.

ƽ

Installation of Outdoor Unit

Half union

Flare nut

Torque wrench

The standard pipe length is 7m(27 9/16)

. If it is over 7m(27 9/16), the function of

the unit will be affected. If the pipe has to be lengthened, the refrigerant should

be charged, according to 50 g/m(0.045 oz/inch).But the charge of refrigerant must
be conducted by professional air conditioner servicer. Before adding additional

refrigerant,

perform air purging from the refrigerant pipes and indoor unit using a vacuum

pump,then

Spanner

Forced fastening without careful centering may
damage the threads and cause a leakage of gas.

Pipe Diameter(ǿ)

Fastening torque

Liquid side6.35mm(1/4")

18N.m

Liquid/Gas side9.52mm(3/8")

42 N.m

Gas side 12.7mm(1/2")

55N.m

Gas side 15.88mm(5/8")

60 N.m

Connection of pipes

charge additional refrigerant.

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

A

B

Outdoor unit

Indoor unit

Oil trap

CAUTION

Max.Elevation: Amax=15 m

In case the elevation A is more

than 5m, oil trap shoud be

installed every 5~7m

Max. Length: Bmax=

5m

In case the pipe length  B  is

more than 10m, the refrigerant

should be charged, according

to 50 g/m.

3

Connection

If the drain-elbow is used,

ƽ

please attach it as figure. (Note:
Only for heat pump unit.)

Detach the service port’s cap of

1.

3-way valve, the valve rod’s cap for 2-way valve

and 3-way’s, connect the service port into the projection of charge hose (Iow)

for gaugemanifold. Then connect the projection of charge hose (center) for gau-

gemanifold into vacuum pump.

Open the handle at Iow in

2.

gaugemanifold, operate vacuum pump. If the scale-

moves of gause (Iow) reach vacuum condition in a moment, check 1. again.

3.

(76 cm Hg) at Iow pressure side. After the completion of vacuuming, close the

handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check

condition of the scale and hold it for 1-2min. If the scale-moves back in spite of

tightening, make flaring work again, the return to the beginning of 3 .

Attaching Drain-Elbow

Purging Method:To use vacuum pump

Open the valve rod for the 2-way valve counterclockwise to 90 degrees.

4.

After 6 seconds, close the 2-way valve and make the inspection of gas leakage.

ƽ

ƽ

ƽ

ƽ

ƽ

ƽ

Take off the panel(top), by removing the 5 screws. 

Remove the plugs on the conduit plate.

Temporarily mount the conduit tubes on the conduit plate.

Connect both the power supply and unit wire harness to

the corresponding terminals on the terminal board.

Ground the unit in accordance with local codes.

Allow several extra inches of wire for making wiring

connections.

Use lock nuts to secure conduit tubes.

ƽ

To bend a pipe, be careful not to crush the pipe,

Ensure that on dirt or debris enters the pipe.

Vacuum for over 15min. And check the gauge which should read -0.1MPa

HSU24VCK-W

Power cable:

2wire with ground  14AWG

HSU18VCK-W

Power cable:

2wire with ground  14AWG

Содержание HSU18VCK

Страница 1: ...f the unit are not disturbed Possible to drain easily where piping can be connected with the outdoor unit Where cold air can be spread in a room evenly Nearby a power receptacle Refer to drawings Not less affected by rain or direct sunlight and is sufficiently ventilated Strong enough to bear the unit where vibration and noise are not increased Please be subject to the actual product purchased the ...

Страница 2: ...pull it out on the front side then connect them 3 Coat the flaring seal face with refrigerant oil and connect pipes Fixing the indoor unit body ƽ In order to fix the body onto the mounting plate hold up ƽ the body aslant from the underside and then put it down perpendicularly Connecting the indoor outdoor Electric Cable Removing the wiring cover Remove terminal cover at right bottom corner of indoor...

Страница 3: ...7m Max Length Bmax 5m In case the pipe length B is more than 10m the refrigerant should be charged according to 50 g m 3 Connection If the drain elbow is used ƽ please attach it as figure Note Only for heat pump unit Detach the service port s cap of 1 3 way valve the valve rod s cap for 2 way valve and 3 way s connect the service port into the projection of charge hose Iow for gaugemanifold Then co...

Страница 4: ...se ƽ apply heat insulation to Less than 5cm confirm that drainage it without fail 4 Check Items for Test Run Put check mark in boxes Gas leak from pipe connecting Heat insulation of pipe connecting Are the connecting wirings of indoor and outdoor firmly Is the connecting wiring of indoor and outdoor firmly fixed Is drainage securely carried out Is the earth line securely connected Is the indoor unit s...

Страница 5: ... la unidad no cause una molestia a los vecinos Coloque la unidad en un lugar en el que pueda disponerse de la distancia de separación marcada en la figura anterior Herramientas necesarias para realizar la instalación Fuente de alimentación Selección del lugar de instalación diagrama de instalación de unidades interiores y exteriores Los modelos cumplen la norma R410A sobre refrigerantes libres de H...

Страница 6: ...con la posición del orificio en la pares Tenga cuidado de no romper los tubos al doblarlos Conecte previamente el cable eléctrico de interior exterior y tire de la conexión al aislante de calor del componente de conexión Conexión de los cables eléctricos de interior exterior Accesorios Selección de tubo Al fijar por primera vez la placa de montaje Al montar la placa de montaje fijándola a una barra l...

Страница 7: ... 7m 27 9 16 se verán afectadas las funciones de la unidad Si es necesario alargar el tubo deberá cargarse refrigerante adicional a razón de 50 g m 0 045 oz pulgada No obstante la carga de refrigerante deberá ser realizada por un ingeniero profesional en aire acondicionado Antes de añadir refrigerante adicional realice una purga de aire desde los tubos refrigerantes y la unidad interior utilizando ...

Страница 8: ...nvernadero regulados por el Protocolo de Kioto B Carga de refrigerante que contiene el producto de fábrica consulte la placa de características de la unidad C Cantidad de refrigerante adicional cargada durante la instalación D Carga total de refrigerante E Unidad exterior F Botella de refrigerante y colector de carga Prueba de instalación y ejecución de la prueba Explique al cliente cómo utilizar ...

Страница 9: ...acement où le vent et le bruit ne risquent pas de gêner les voisins Choisir un endroit dans lequel les distances marquées illustrées dans le schéma ci dessus sont disponibles Outillage requis pour l installation Source d alimentation Sélection de l emplacement pour l installation schéma d installation des unités intérieures et extérieures Les modèles utilisent le réfrigérant R410A sans HCFC Dispos...

Страница 10: ...le pour la tuyauterie en fonction de la direction de la tuyauterie et cintrez ensuite le tuyau selon la position du trou dans le mur Lors du cintrage prenez soin de ne pas écraser les tuyaux Connectez au préalable le câble des unités intérieures extérieures et recouvrez ensuite les câbles connectés avec l isolation Connexion du câble des unités intérieures extérieures Accessoires Sélection du tuya...

Страница 11: ... entrés dans le tuyau La longueur standard du tuyau est de 7 m 27 9 16 Au delà de 7 m 27 9 16 l unité ne fonctionnera pas correctement S il faut rallonger le tuyau le réfrigérant doit être chargé selon 50 g m 0 045 oz pouce Toutefois la charge de réfrigérant doit être exécuté par un professionnel de la climatisation Avant d ajouter du réfrigérant purgez l air des tuyaux de réfrigération et de l un...

Страница 12: ...unité voir sur la plaque signalétique de l unité C Quantité supplémentaire de réfrigérant chargée sur place D Charge totale de réfrigérant E Unité extérieure F Cylindre réfrigérant et collecteur de chargement Vérification de l installation et test de fonctionnement Expliquez le fonctionnement à vos clients en vous servant du manuel Cochez les cases 9 Fuite de gaz dans le raccordement du tuyau Isola...

Отзывы: