Domestic Air Conditioner
5.2.3
˖
The control of the outdoor electronic expansion valve
When starting the compressor: the opening size of the valve must be guaranteed to have entered into
the standard opening size, and then the compressor can be started.
When refrigeration is in vain (the machine is shut down or is in the state of retrograde operation), the
opening size of the expansion valve of the indoor unit is 5 steps;
When heating is in vain, the opening size of the expansion valve of the indoor unit is 55 steps;
When the outdoor unit is shut down, the valve is opened completely for 2 minutes, and then begin
initialization.
The scope of refrigerationg valve 90-----480 steps
The scope of heating valve 80-----480 steps
The valves are adjusted according to the degree of superheat —SHa
ˈƸ
SHa.
5.2.4
˖
Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or changed
to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the four-way
valve.
5.2.5
˖
Protection function
5.2.5.1
˖
TTC high temperature-preventing protection
Once the machine is started, it can run TTC overheating protection of air-blowing, but air-blowing
sensor malfunction must alarm after 4 minutes during which the compressor is started (during the
course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the
mean value of the middle 2 values), take the mean value.
TTC
˄ć˅
Abnormal stop
110
Decreasing the frequency rapidly
˄
1HZ/second
˅
100
Decreasing the frequency slowly (1HZ/10seconds)
98
The frequency doesn’t change.
93
Increasing the frequency (1HZ/10second)
90
Increasing the frequency
˄
1HZ/1second
˅
TTC>=110
ć
lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
Содержание HSU12VHG-B
Страница 16: ...HSU12 HG DB SM Connector Wring Diagram 13 Domestic Air Conditioner PCB 2 CN1 CN2 CN3 CN4 CN5 CN6 CN7 CN11 CN10 ...
Страница 43: ...Domestic Air Conditioner HSU12 HG DB SM System Configuration 40 ...
Страница 71: ...68 Domestic air conditioner Removal of procedure 9 1 HSU12 HG DB SM ...
Страница 74: ...71 Domestic air conditioner Removal of procedure three two HOOKS HSU12 HG DB SM ...
Страница 75: ...72 Domestic air conditioner Removal of procedure horizontal flap flap flap flap flap 9 3 HSU12 HG DB SM ...
Страница 76: ...73 Domestic Air Conditioner Removal of procedure 9 4 HSU12 HG DB SM ...
Страница 77: ...74 Removal of procedure 9 5 HSU12 HG DB SM Domestic Air Conditioner ...
Страница 78: ...75 Domestic air conditioner Removal of procedure 9 6 HSU12 HG DB SM ...
Страница 79: ...76 Domestic air conditioner Removal of procedure 9 7 HSU12 HG DB SM ...
Страница 80: ...Domestic air conditioner 77 Removal of procedure HSU12 HG DB SM ...
Страница 81: ...Domestic air conditioner Removal of procedure 78 HSU12 HG DB SM ...
Страница 82: ...79 Domestic air conditioner Removal of procedure HSU12 HG DB SM ...
Страница 83: ...80 Removal Procedure 9 HSU12 HG DB SM ...
Страница 84: ...81 Removal Procedure HSU12 HG DB SM ...
Страница 85: ...Removal Procedure 82 4 HSU12 HG DB SM ...
Страница 86: ...83 Removal Procedure HSU12 HG DB SM 9 10 ...
Страница 87: ...84 Removal Procedure 11 HSU12 HG DB SM ...
Страница 88: ...85 Removal Procedure 12 HSU12 HG DB SM ...
Страница 89: ...86 Removal Procedure HSU12 HG DB SM ...
Страница 90: ...87 Removal Procedure HSU12 HG DB SM 9 13 ...
Страница 91: ...88 Removal Procedure HSU12 HG DB SM ...
Страница 98: ...Wu Hongjin Shi Longfei Yu Huali Wang Fei 86 532 88936935 The end Sincere Forever Haier Group HSU12 HG DB SM ...