Indoor unit

1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar
   qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.

5

When connecting the cable before installing the indoor unit

Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and tightened.
After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring
       is not correct, proper operation can not be carried out and will cause defect.

5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the
    distance between its two contacts should be not less than 3mm.

Connecting the indoor/outdoor Electric Cable

Removing the wiring cover

Remove terminal cover at right bottom corner of indoor unit, then

take off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit

1. Insert from outside the room cable into left side of the wall hole, in which

    the pipe has already existed.

2. Pull out the cable on the front side, and connect the cable making a loop.

HSU-09CRA03-T

1(L

)

3

4

2(N)

Indoor unit

1(L
)

2(N)

Outdoor unit

HSU-12CRA03-T

Indoor unit

Outdoor unit

1(L

)

3

4

2(N)

connecting wiring:
-mod 09-12:    3G1.0mm

Power cable:
-mod 09-12:     3G1.0mm

HSU-18CRA03-T

-mod      18:    3G2.

5

mm

-mod      18:     3G2.

5

mm

Содержание HSU-18CRA03-T

Страница 1: ...Drain hose Heating insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance betw...

Страница 2: ...ptacle with enough space around Refer to drawings Place where the distance of more than lm from televisions radios wireless apparatuses and fluorescent lamps can be left In the case of fixing the remo...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...ody aslant from the underside and then put it down perpendicularly 1 Insert the drain hose into the dent of heat insulation materials of indoor unit 2 Insert the indoor outdoor electric cable from bac...

Страница 5: ...h the wiring cover Note When connecting the cable confirm the terminal number of indoor and outdoor units carefully If wiring is not correct proper operation can not be carried out and will cause defe...

Страница 6: ...wiring is not correct proper operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Drawing for the installat...

Страница 7: ...ing to the following list Piping length Additional amount 5m 7m No need 40g 10m 100g for 9k 12k 18k Push the air out of the indoor unit and piping as followes 1 Remove the valve cap on 2 way valve in...

Страница 8: ...pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly expla...

Отзывы: