Haier air conditioner
Edition:20070116
- 20 -
When the system switch from other mode to auto mode, if the operation status change (i.e. first
determine and then operation), it will stop for 3 minutes and then determine temperature based on the
indoor ventilation temperature.
9.2 Full-automation operation
After system is on and the operation mode will switches to auto mode, the system determine operating
mode by the difference between current set temperature and the room temperature, and then operate
in the determined mode. In the following selection condition, Tr indicate room temperature
ˈ
Ts indicate
set temperature.
In First enter auto mode, select operating mode as following condition:
Tr=Ts-3
select cool mode
ć
Tr
˘
Ts-3
select heat mode
ć
When system enter the auto mode, the operation mode will switch between cool and heat according to
change of the indoor temperature: if the unit operating in the cool mode, when system temperature
arrive at stop value of compressor, the compressor to off and stop continuously for 15 minutes, and
then to detect the room temperature, at this point, if Tr
˘
Ts-3
, then the system enter the heat mode,
ć
otherwise it will operate continuously in the cool mode; if the unit operating in the heat mode, when
system temperature arrive at stop value of compressor, the compressor to off and stop continuously
for 15 minutes, and then to detect the room temperature, at this point, if Tr
˚
Ts+3
, then the system
ć
enter the cool mode, otherwise it will operate continuously in the heat mode.
This mode has timer and sleep function, if the system enter the cool mode, then enter the cool+ sleep
mode, if enter the heat mode then enter heat + sleep mode.
Select swing or sticking on one position for the fan blade, and fan speed including: low, middle, high
and auto fan, you can select any one of them without control.
Ē
. Running-in
In the Running-in mode the indication frequency is 58Hz, the air capacity is enhanced.
Running-in is off after 30 minutes. When the system received the remote control signal in the
running-in mode, the system will exit this mode.
No taking activities under low load protection.
Ēĉ
. Low load protection controlling
The standard of heat alternating temperature sensor
B destiny=3700 R (25 degrees) =10KO
When it operates for coolness making or defrosting, low load protection will be taken based on Heat
exchange temperature as the following picture shows
Controlling under low load protection
If selection model is GANGDA communication, the indoor unit have not this function.