- 12 -
When the system is in test run, emergency operation, silencing operation mode, the DASH will be
stopped.
2.4.5 Temperature adjustment section
˄
DASH operation condition in the different mode
˅
2.4.6 Frequency in the different mode
In this area, the frequency (from indoor to outdoor) indication as following:
When the system is in the cool and dry mode, the frequencies between A area and B area are same.
In the silencing operation mode, the frequencies between A-E area and F area are same.
Indication frequency
Scope of
frequency
Temperature
changing area
Heating
FQHOT [0—7]
30-140Hz
A—H
Heat in Silence mode
FQSHOT [0—2]
30-72Hz
F—H
Dry
FQDRY [0—7]
30-98Hz
B—H
Cooling
FQCOOL [0—7]
30-98Hz
B—H
Cooling in silence mode
FQSCOOL [0—2]
30-64Hz
F—H
The maximum frequency is the maximum frequency value as above table.
The max or min frequency in the cool or heat mode is corresponding with the max or min frequency
value as the above table.
2.4.7 Control frequency in the same area
The compressor operating by the identity frequency for 3minutes that its area has no change, the
indication frequency will be changed.
The timer will be reset when you input the different frequency. The system’s temperature area have no
change when the system operating by new frequency for 3 minutes, please changing its indication
frequency (add FQUPH or FQUPL).