Indoor unit

1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar
   qualified person. The type of connecting wire is H05/07RN-F or 245IEC57(YZW).
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.

5

When connecting the cable before installing the indoor unit

Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and tightened.
After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring
       is not correct, proper operation can not be carried out and will cause defect.

5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the
    distance between its two contacts should be not less than 3mm.

HSU-09LE04

Indoor unit

Outdoor unit

4

HSU-12LE04

HSU-18LE04

Indoor unit

Outdoor unit

4

Indoor unit

Outdoor unit

4

1

2

N

L

HSU-22LE04

Indoor unit

Outdoor unit

4

L

N

POWER PLUG

{

1(L)

2(N)

{

power

connecting wiring:
-mod 07-12:    3G1.0mm
-mod 18:    3G1.5mm
-mod 22:    4G0.75mm

Power cable:
-mod 07-12:     3G1.0mm
-mod 18:    3G1.5mm
-mod 22:     3G2.5mm

-mod 24:    3G1.5mm

-mod 24:    3G1.5mm

FJT-12L

FJT-18L

FJT-24L

HSU-07LD03

Содержание HSU-09LE04

Страница 1: ...Drain hose Heating insulating material Piping hole cover Arrangement of piping directions Rear left Rear right Left Below Right The marks from to in the figure are the parts numbers The distance betw...

Страница 2: ...rom televisions radios wireless apparatuses and fluorescent lamps can be left In the case of fixing the remote controller on a wall place where the indoor unit can receive signals when the fluorescent...

Страница 3: ...ticle When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a...

Страница 4: ...aslant from the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable a...

Страница 5: ...e sure the cables have been properly inserted and tightened After the cable connection never fail to fasten the connected cable with the wiring cover Note When connecting the cable confirm the termina...

Страница 6: ...operation can not be carried out and controller may be damaged If the drain elbow is used please attach it as figure Note Only for heat pump unit Drawing for the installation of indoor and outdoor un...

Страница 7: ...onal amount 5m 7m No need 40g 10m 100g for 7k 9k 12k 18k Push the air out of the indoor unit and piping as followes 1 Remove the valve cap on 2 way valve in outdoor unit 2 Loosen by 1 2 turn the flare...

Страница 8: ...nfirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly explain to our customers how to ope...

Отзывы: