23
English
Operating functions
23
Installer settings
Parameters
Description
- To open the installer settings, press s
witch off the
system, then press and
at the same time for 10 seconds.
- When menu is open, press or to change the value of the settings.
- Press to c
onfirm the se
ttings.
- Press to close the menu.
O
ff
-peak signal type
When you use o
ff
-peak time clock contr
ol, fi
rst determine
the type of signals,Only allow professional installers to operate.
Off-peak
logic type
- In two ways using heat pump,should set in the installer
settings
-01 manually set o
ff
-peak time;
-02 switch signals by power companies.
-03 PV signal
.
-04 SG signal.
NO
01
ON
12h
5-23h
NO , NC
01 , 02
03 , 04
ON , OF
,
Factory
setting
Adjustment
range
Avoid Legionella
- This parameter is used to activate the legionella protection
mode.
- Once every 7or 30 days, all domestic hot water is heated to
65~75°C.
- NO corresponds to Normally Open Signal.
- NC corresponds to Normally Close Signal.
,
23
Compressor maximum continuous working time
- If the maximum continuous working time of the compressor
more than Set Time, start auxiliary power.
-
,
,
/
d1-d7
Set the day of the week
- Set the day of the week, d1 to d7 for Monday to Sunday, and
remember the day of the week.
-
Auxiliary Heating in o
ff
-peak time
- ON corresponds to turned on auxiliary Heating.
- OF corresponds to turned o
ff
auxiliary Heating.
,
ON
ON , OF
65
65-75
Anti-legionella temperature setting
- The Avoid Legionella temperature is adjustable between
65°C and 75°C.
-
07
07,30
The frequency of Anti-legionella
- The frequency of Anti-legionella is adjustable ,7 days and
30 days are optional.
,
Содержание HP150M5
Страница 29: ......
Страница 30: ......
Страница 57: ......
Страница 58: ......
Страница 85: ......
Страница 86: ......
Страница 113: ......
Страница 114: ......
Страница 141: ......
Страница 142: ......
Страница 169: ......
Страница 170: ......
Страница 197: ......
Страница 198: ......
Страница 225: ......
Страница 226: ...0040510552 20220526 V ...