Outdoor unit

6.Purging Method:To use vacuum pump

Detach the service port's cap of 3-way valve, the

valve rod's cap for 2-way valve and 3-way's, connect

the service port into the projection of charge hose

(Iow) for gaugemanifold. Then connect the projection

of charge hose (center) for gaugemanifold into

vacuum pump.

3-way valve
Gas Side

2-way valve

2-way valve

Service port cap

Gaugemanifold(for R410A)

Vacuum pump(for R410A)

Open

Close

Liquid Side

Open the handle at Iow in gaugemanifold, operate

vacuum pump. If the scale-moves of gause (Iow)

reach vacuum condition in a moment, check         again.

Vacuumize for over 15min. And check the level gauge

which should read -0.1 MPa (-76 cm Hg) at Iow

pressure side. After the completion of vacuumizing,

close the handle 'Lo' in gaugemanifold and stop the

operation of the vacuum pump.

Check the condition of the scale and hold it for 1-2min.

If the scale-moves back in spite of tightening, make

flaring work again, the return to the beginning of         .

Open the valve rod for the 2-way valve to an angle of

anticlockwise 90 degrees.

After 6 seconds, close the 2-way valve and make

the inspection of gas leakage.

No gas leakage?

In case of gas leakage, tighten

parts of pipe connection. If

leakage stops, then proceed

steps.

Detach the charge hose from the service port, open

2-way valve and 3-way. Turn the valve rod anticlockwise

until hitting lightly.

To prevent the gas leakage, turn the service port's

cap, the valve rod's cap for 2-way valve and 3-way's

a little more than the point where the torque increases

suddenly.

After attaching the each caps, check the gas leakage

around the caps.

CAUTION:

1.If the refrigerant of the air conditioner leaks, it is necessary to

 discharge all the refrigerant. Vacuumize first, then charge the liquid

 refrigerant into air conditioner according to the amount marked on

 the name plate.

2.Please do not let other cooling medium, except specified one (R410A),

  or air enter into the cooling circulation system. Otherwise, there will be

 abnormal high pressure in the system to make it crack and lead to

  personal injuries.

If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder.

Anti countercurrent joint

3-way valve

2-way valve

7

6

6

6

1

2

3

1

3

4

5

6

7

8

7

3-way valve

2-way valve

To indoor
   unit A

To indoor
  unit B

Tube(for R410A)

3-way valve

Valve rod cap

Valve rod cap

7

7

Open

90

O

Содержание H2SM- - annexe 17

Страница 1: ...upporting plate No Accessory parts Remote controller R 03 dry battery Mounting plate Drain hose Screw Plastic cap Drain elbow Cushion 2 1 2 3 4 5 6 7 8 4 2 2 8 1 4 Number of articles Accessory parts 4...

Страница 2: ...left In the case of fixing the remote controller on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by rain or...

Страница 3: ...piping hole cover and seal it off with putty after installation When the mounting plate is fixed side bar and lintel Refer to the previous article When the mounting plate is first fixed for the posit...

Страница 4: ...or unit then take off wiring cover by removing its screws When connecting the cable after installing the indoor unit 1 Insert from outside the room cable into left side of the wall hole in which the p...

Страница 5: ...must be incorporated in the fixed wiring in accordance with the wiring rules The power plug is self provided the power plug must acquired the local attestation When connecting the cable before instal...

Страница 6: ...areful that matters such as wastes of sands etc shall not enter the pipe The standard pipe length is 5m If it is over 5m the function of the unit will be affected If the pipe has to be lengthened the...

Страница 7: ...kage No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed steps Detach the charge hose from the service port open 2 way valve and 3 way Turn the valve r...

Страница 8: ...ried out Please install the drain hose so as to be downward slope without fail Please don t do the drainage as shown below Please pour water in the drain pan of the indoor unit and confirm that draina...

Страница 9: ...tioning product is marked with this sym bol This means that electrical and electronic products shall not be mixed with unsorted household waste Do not try to dismantle the system yourself the dis mant...

Страница 10: ...los productos el ctricos y electr nicos no deben mezclarse con el resto de resi duos dom sticos no clasificados No intente desmontar el sistema usted mismo El des mantelamiento del acondicionador de...

Страница 11: ...oduct 2 the additional refrigerant amount charged in the field and 1 2 the total refrigerant charge on the refrigerant charge label supplied with the product The filled out label must be adhered in th...

Страница 12: ...refrigerante cargado en campo y 1 2 la carga total de refrigerante En la etiqueta de carga de refrigerante suministrada con el producto La etiqueta rellenada debe pegarse cerca de la conexi n de carga...

Отзывы: