PAGE 8
ENGLISH
INTRODUCTION
OVERVIEW & INTRODUCTION
Auto Mode
When the running mode is turned to auto after starting the
system, the system will first determine the running mode
according to the current room temperature and then will
run according to the determined mode: Tr means room
temperature; Ts means temperature setting; Tp means
temperature of indoor coil pipe
Tr≥73°F Choose Cooling Mode
Tr<73°F Choose Heating Mode
After turning to the auto mode, the running mode will be
switched between cooling mode, fan mode, and heating mode
according to the change of the indoor ambient temperature.
There is a 15 minute delay between mode changes.
Cooling operation mode
Temperature control range: 60°F---86°F
Temperature difference: ±2°F
*
Control features: When Tr (input airflow)>Ts (set
temperature) °F, the indoor fan will operate at the set speed,
the mode signal will be sent to the outdoor system, and
the compressor will start. When Tr (input airflow)< Ts (set
temperature)°F, the indoor fan will operate at the set speed,
and the mode signal will be sent to the outdoor system, and
the compressor will stop. The system will keep the original
status if Tr= Ts.
Airflow speed control: (temperature difference ±2°F)
Automatic:
When Tr≤Ts +4°F high speed.
When Ts+2°F≤Tr<Ts+5°F, medium speed
When Tr<Ts+2°F, low speed
When the sensor is off, low speed
When the airflow speed has no delay from the high to low
switching, the speed should be delayed for 3 minutes (remain
at high speed for 3 minutes.) before the next switch.
When the system is operating, you can set the high, medium
or low speed manually. (When the sensor is on or off, the
system will change the speed 2 seconds after receiving the
signal.)
*Louver control: the location for the louver can be set
according to your needs.
*Defrosting function: preventing the frosting on the indoor
heat exchanger (when cooling or dehumidifying). When the
compressor works continuously for
1 to 6 minutes (adaptable
in EEPROM) and the temperature of the indoor coils has been
below 32°F for 10 seconds, the compressor will be stopped
and the malfunction will be recorded in the malfunction list.
The indoor system will continue to run. When the temperature
of the indoor coil is raised to 45°F, the compressor will be
restarted again (the requirement of 3 minutes’ delay should
be satisfied.)
Dry Mode (Dehumidifying mode)
*
temperature control range: 60---86°F
*
temperature difference: ±2°F
Control feature: Send the dehumidifying signal to the outdoor
system.
When Tr>Ts+4°F, the compressor will be turned on, the indoor
fan will operate at the set speed. When Tr is between the
Ts and Ts+4°F, the outdoor system will operate at the high
dehumidifying frequency for 10 minutes and then at the low
dehumidifying mode for six minutes. The indoor fan will
operate at low speed.
When Tr< Ts, the outdoor system will be stopped, the indoor
fan will be stopped for 3 minutes and then turned to the low
speed option.
All the frequency conversions have a ±2°F difference.
* Wind speed control: Automatic:
When Tr≥ Ts+ 9°F, high speed.
When Ts+5°F≤Tr< Ts+9°F, medium speed.
When Ts+4°F≤Tr< Ts+5°F, low speed.
When Tr<Ts+4°F, light speed.
If the outdoor fan is stopped, the indoor fan will be paused for
3 minutes.
If the outdoor fan is stopped for more than 3 minutes and the
outdoor system still operates, the system will be changed into
light speed mode.
When the airflow speed has no delay from the high to low
switching, the speed should be delayed for 3 minutes (remain
at high speed for 3 minutes.) before the next switch.
When the sensor is off or Tr< Ts+5°F, the manual operation can
not be made. (obligatory automatic operation.)
*Louver location control: the location for the louver can be set
according to your needs.
*Defrosting function: preventing the frosting on the indoor
heat exchanger (when cooling or dehumidifying). When the
compressor works continuously for 16 minutes (adaptable in
EEPROM) and the temperature of the indoor coils has been
below 32°F for 10 second, the compressor will be stopped and
the malfunction will be recorded in the malfunction list. The
indoor system will continue to run. When the temperature
of the indoor coil is raised to 45°F, the compressor will be
restarted again (the requirement of 3 minutes’ delay should
be satisfied.)
Functions and Controls
Содержание AW07LC2VHA
Страница 3: ...PAGE 3 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Indoor...
Страница 4: ...PAGE 4 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Indoor...
Страница 5: ...PAGE 5 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Outdoor...
Страница 72: ...REFERENCES PAGE 72 ENGLISH Problem Problems Solutions Length Limits Piping Length Limits REFERENCES...
Страница 73: ...REFERENCES PAGE 73 ENGLISH Component Ratings REFERENCES...
Страница 76: ...REFERENCES PAGE 76 ENGLISH Wiring REFERENCES...
Страница 77: ...REFERENCES PAGE 77 ENGLISH Wiring REFERENCES...
Страница 78: ...REFERENCES PAGE 78 ENGLISH Wiring REFERENCES...
Страница 79: ...REFERENCES PAGE 79 ENGLISH Wiring REFERENCES...
Страница 80: ...REFERENCES PAGE 80 ENGLISH Wiring REFERENCES...
Страница 81: ...REFERENCES PAGE 81 ENGLISH 2U Wiring REFERENCES...
Страница 82: ...REFERENCES PAGE 82 ENGLISH CN20 Connector for room card Wiring REFERENCES...
Страница 83: ...REFERENCES PAGE 83 ENGLISH SWI Wiring REFERENCES...
Страница 84: ...REFERENCES PAGE 84 ENGLISH Wiring REFERENCES...
Страница 86: ...REFERENCES PAGE 86 ENGLISH CIRCUIT DIAGRAMS REFERENCES...
Страница 87: ...REFERENCES PAGE 87 ENGLISH CIRCUIT DIAGRAMS REFERENCES...
Страница 88: ...REFERENCES PAGE 88 ENGLISH WIRING DIAGRAMS REFERENCES...
Страница 89: ...REFERENCES PAGE 89 ENGLISH WIRING DIAGRAMS REFERENCES...
Страница 90: ...REFERENCES PAGE 90 ENGLISH 2U Piping Installation Dimensions REFERENCES...
Страница 92: ...REFERENCES PAGE 92 ENGLISH Refrigerant Diagram REFERENCES...
Страница 93: ...REFERENCES PAGE 93 ENGLISH Refrigerant Diagram REFERENCES...
Страница 94: ...REFERENCES PAGE 94 ENGLISH 3U Piping Installation Dimensions REFERENCES...
Страница 95: ...REFERENCES PAGE 95 ENGLISH 4U Piping Installation Dimensions REFERENCES...
Страница 110: ...REFERENCES PAGE 110 ENGLISH SENSORS Value of Thermistor Indoor Unit...
Страница 111: ...REFERENCES PAGE 111 ENGLISH SENSORS...
Страница 112: ...REFERENCES PAGE 112 ENGLISH SENSORS...
Страница 113: ...REFERENCES PAGE 113 ENGLISH SENSORS...
Страница 114: ...REFERENCES PAGE 114 ENGLISH SENSORS...
Страница 115: ...REFERENCES PAGE 115 ENGLISH SENSORS...
Страница 116: ...REFERENCES PAGE 116 ENGLISH SENSORS...
Страница 117: ...REFERENCES PAGE 117 ENGLISH SENSORS...
Страница 118: ...REFERENCES PAGE 118 ENGLISH SENSORS...
Страница 119: ...REFERENCES PAGE 119 ENGLISH SENSORS...
Страница 120: ...REFERENCES PAGE 120 ENGLISH SENSORS...
Страница 121: ...REFERENCES PAGE 121 ENGLISH SENSORS...