OPERATIONS
PAGE 19
ENGLISH
The outdoor unit is capable of controlling up to 4 individual indoor units. The outdoor unit will vary compressor capacity and
outdoor fan motor speed to match the demand requirement from the indoor units. All capacity and diagnostic decisions are con
-
trolled by the outdoor unit ECU. During any period where the outdoor unit is running, all indoor units must be in the same mode
of operation. If any unit is energized in a mode that opposes the first indoor unit that was turned on and set to provide cooling or
heating, the opposing unit’s request will be ignored.
Throughout a call for either heating or cooling operation, the temperature sensors in the indoor and outdoor units will provide
critical temperature points to the outdoor unit ECU. If the temperatures being sensed are abnormal or trending to a level that is
potentially going to create overheating of the compressor or freezing of the indoor unit.
The frequency adjustments or system responses to temperature sensors readings are explained in the section Temperature
Sensor Responses.
On a call for cooling, the indoor unit will send the room tem
-
perature and set-point requirement to the outdoor unit ECU
via the data signal wire path. The data travels from the indoor
unit to the outdoor unit via the wire located on terminal 3.
The indoor unit’s louver will open and the indoor fan motor will
start.
The outdoor unit will energize the EEV’s that are controlling
refrigerant flow to the calling indoor units. The position of the
EEV valves will be set to a beginning position based upon the
outdoor air temperature.
The 4-way valve will be de-energized. After a 3 minute time
delay, the outdoor fan motor will be energized. Shortly after
the outdoor fan motor turns on, the compressor will start in
low frequency. The operating frequency of the compressor
will be displayed on the Service Monitor Board Display.
The refrigerant in the system will begin to flow. The com
-
pressor will discharge hot gas into the oil separator. Oil will be
trapped in the separator and returned to the suction inlet of
the compressor via the capillary tube assembly low pressure
path.
1
Temperature Sensor Td
The temperature of the compressor discharge hot gas will be
monitored by the Discharge Temperature Sensor. If the sensor
reads too hot or cool, the frequency/status of the operation will
potentially be altered.
The hot gas will leave the oil separator and enter the 4 way
4U36HS1ERE 4U36MS2VHB
Comp-
ressor
Discharge temp.
sensor
Oil
separator
Capillary tube
High pressure
switch
4-way valve
Pipe sensor
Toci
Suction temp.
sensor
Low pressure
switch
Accumulator
Gas stop valve
Outdoor
heat
exchanger
temp.
sensor
FAN-OUT
Outdoor
ambient
temp.
sensor
Defrost
sensor
Distributor
Strainer
Check valve
Receiver
Liquid stop vavle
5/8
3/8
Strainer
Unit A liquid pipe temp. sensor
Indoor unit A
Strainer
Unit B liquid pipe temp. sensor
Indoor unit B
Strainer
Unit C liquid pipe temp. sensor
Indoor unit C
Strainer
Unit D liquid pipe temp. sensor
Indoor unit D
Unit A gas pipe temp. sensor
Unit B gas pipe temp. sensor
Unit C gas pipe temp. sensor
Unit D gas pipe temp. sensor
Indoor unit A
Indoor unit B
Indoor unit C
Indoor unit D
4-way valve coil:
OFF
ON
Refrigerant flow in cooling
Refrigerant flow in heating
FAN-IN
Indoor
ambient
temp.
sensor
Indoor
heat
exchanger
temp.
sensor
EEV A
B
V
E
E
EEV C
EEV D
EEV O
φ2.7*φ1.0*55in
15
1
2
3
4
5
6
7
OUTDOOR UNIT SEQUENCE OF OPERATION
Cooling Mode Sequence of Operation
valve
Содержание AW07LC2VHA
Страница 3: ...PAGE 3 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Indoor...
Страница 4: ...PAGE 4 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Indoor...
Страница 5: ...PAGE 5 ENGLISH INTRODUCTION SPECIFICATIONS Multi Zone Outdoor...
Страница 72: ...REFERENCES PAGE 72 ENGLISH Problem Problems Solutions Length Limits Piping Length Limits REFERENCES...
Страница 73: ...REFERENCES PAGE 73 ENGLISH Component Ratings REFERENCES...
Страница 76: ...REFERENCES PAGE 76 ENGLISH Wiring REFERENCES...
Страница 77: ...REFERENCES PAGE 77 ENGLISH Wiring REFERENCES...
Страница 78: ...REFERENCES PAGE 78 ENGLISH Wiring REFERENCES...
Страница 79: ...REFERENCES PAGE 79 ENGLISH Wiring REFERENCES...
Страница 80: ...REFERENCES PAGE 80 ENGLISH Wiring REFERENCES...
Страница 81: ...REFERENCES PAGE 81 ENGLISH 2U Wiring REFERENCES...
Страница 82: ...REFERENCES PAGE 82 ENGLISH CN20 Connector for room card Wiring REFERENCES...
Страница 83: ...REFERENCES PAGE 83 ENGLISH SWI Wiring REFERENCES...
Страница 84: ...REFERENCES PAGE 84 ENGLISH Wiring REFERENCES...
Страница 86: ...REFERENCES PAGE 86 ENGLISH CIRCUIT DIAGRAMS REFERENCES...
Страница 87: ...REFERENCES PAGE 87 ENGLISH CIRCUIT DIAGRAMS REFERENCES...
Страница 88: ...REFERENCES PAGE 88 ENGLISH WIRING DIAGRAMS REFERENCES...
Страница 89: ...REFERENCES PAGE 89 ENGLISH WIRING DIAGRAMS REFERENCES...
Страница 90: ...REFERENCES PAGE 90 ENGLISH 2U Piping Installation Dimensions REFERENCES...
Страница 92: ...REFERENCES PAGE 92 ENGLISH Refrigerant Diagram REFERENCES...
Страница 93: ...REFERENCES PAGE 93 ENGLISH Refrigerant Diagram REFERENCES...
Страница 94: ...REFERENCES PAGE 94 ENGLISH 3U Piping Installation Dimensions REFERENCES...
Страница 95: ...REFERENCES PAGE 95 ENGLISH 4U Piping Installation Dimensions REFERENCES...
Страница 110: ...REFERENCES PAGE 110 ENGLISH SENSORS Value of Thermistor Indoor Unit...
Страница 111: ...REFERENCES PAGE 111 ENGLISH SENSORS...
Страница 112: ...REFERENCES PAGE 112 ENGLISH SENSORS...
Страница 113: ...REFERENCES PAGE 113 ENGLISH SENSORS...
Страница 114: ...REFERENCES PAGE 114 ENGLISH SENSORS...
Страница 115: ...REFERENCES PAGE 115 ENGLISH SENSORS...
Страница 116: ...REFERENCES PAGE 116 ENGLISH SENSORS...
Страница 117: ...REFERENCES PAGE 117 ENGLISH SENSORS...
Страница 118: ...REFERENCES PAGE 118 ENGLISH SENSORS...
Страница 119: ...REFERENCES PAGE 119 ENGLISH SENSORS...
Страница 120: ...REFERENCES PAGE 120 ENGLISH SENSORS...
Страница 121: ...REFERENCES PAGE 121 ENGLISH SENSORS...