Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating):
20
℃
DB/14.5
℃
WB Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating):
7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values in the semi-anechoic chamber,
using a Real Time Analyser calibrated sound intensity meter. It is a sound pressure noise level.
Equivalent HP
8
10
12
Model
AV08NMSETA
AV10NMSETA
AV12NMSETA
Nominal cooling capacity(
kW
)
22.6
28
33.50
Nominal heating capacity(
kW
)
25
31.5
37.50
Heating capacity at low temp.(
kW
)
21.2
25.6
29.00
Power source
3N
~
.380-400V.50/60Hz
IP level
IP24
IP24
IP24
Electrical characteristics
cooling
Operating/Max.current(A)
9.6
/
17.2
13.2
/
23.8
16.4/26
Operating/Max.consumption(
kW
)
5.79
/
10.42
8.0
/
14.4
9.
82
/15.4
heating
Operating/Max.current(A)
9.0
/
16.2
12.4
/
22.3
16.2/25.3
Operating/Max.consumption(
kW
)
5.43
/
9.78
7.5
/
12.4
9.62/15.0
Power consumption when heating at low temp.(
kW
)
6.5
9
11.5
Output power of outdoor motor(
kW
)
0.145+0.18
0.145+0.18
0.145+0.18
Exterior dimensions(mm)
1636×1050×400 1636×1050×400 1636×1050×400
Weight(Kg)
168
168
168
Exterior colour
ivory white
ivory white
ivory white
Compressor type
Twin rotary
Compressor model
LNB53F
LNB53F
LNB53F
Oil charge(ml)
2000
2000
2000
Oil model
FV50S
FV50S
FV50S
Outdoor motor rate(rpm)
770+850
770+850
770+850
Outdoor air
fl
ow(m
)
10000
10000
10000
Refrigerant (R410A) charge(Kg)
7.4
7.4
7.4
Gas piping(mm)
φ
19.05
φ
22.22
φ
25.4
Liquid piping(mm)
φ
9.52
φ
12.7
φ
12.7
Noise level(dB(A)
55
58
60
Max. indoor units
13
16
19
2. Specification
4