Haier AU182AEEAA Скачать руководство пользователя страница 11

It shall use the vacuum p

ump of (lower than -755mmHg)high vacuum degree and large air

discharging (over 40l/min).
The vacuumizing time depends on the length of the connecting pipe, generally is 1~2 hours.
When vacuumizing, it shall be confirmed both gas and liquid side valves are closed.
If after 2 hours vacuumizing, it cannot reach the vacuum degree below -755mmHg, it can be
vacuumized for other 1 hour.
If after 3 hours vacuumizing, it still cannot reach the vacuum degree below -755mmHg, check
if there is any leaking point and repair the them.
If after over 2 hours vacuumizing, the vacuum degree is below -755mmHg, close the VL
and VH on the meter separator and stop vacuumizing. 1 hour later to confirm if the vacuum
degree changes. If changes, it indicates there is leaking point in the system. Check the leaking
point and repair.
After finishing the above vacuumizing, change the vacuum pump into refrigerant pump to
charge the refrigerant.

Use vacuum pump to perform vacuumizing. It is strictly forbidden to use the
refrigerant to remove the air inside the system.
After air tightness test and discharging all the nitrogen, connect the vacuum pump
as the following figure shown.

Refrigerant piping

10

When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is
unnecessary to charge additional refrigerant.
If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter.
That is: Refrigerant charging amount = (L-5) x M (g)
             

For AU182AEEAA, M=30

             For AU242AGEAA, AU282AHEAA, AU28NAHEAA, AU362AIEAA,
                   AU36NAIEAA , AU48NAIEAA, AU60NAIEAA, M=65

Only in COOLING operation can charge the additional refrigerant.
When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle.
Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the
additional refrigerant in liquid condition.

6. Piping and indoor unit vacuumizing

7. Charging amount of refrigerant

3-way valve totally closed
(Liquid side)

Indoor units

Indoor

Outdoor

Completely tightened

Completely tightened

Outdoor units

Vacuum pump

Discharging valve

3-way valve totally closed

     (Gas side)

Low pressure peizometer

High pressure peizometer

Meter separator

V L VH

Flare part

Flare part

P

Installation Procedure

Содержание AU182AEEAA

Страница 1: ...ad this manual carefully Please keep this manual properly for future use CONTENTS Name of Parts 1 Safety Cautions 2 3 Installation Procedure 4 13 INSTALLATION INSTRUCTIONS No 0010577959 D AU242AGEAA A...

Страница 2: ...unit Compressor AU36NAIEAA AU362AIEAA AU48NAIEAA AU60NAIEAA AU242AGEAA AU182AEEAA Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet In...

Страница 3: ...autions Carefully read the following information in order to operate the airconditioner correctly WARNING If any abnormal phenomena is found e g smell of firing please cut off the power supply immedia...

Страница 4: ...tioner Incorrect installation may cause water leak electrical shock and fire hazard Call the dealer to take measures to prevent the refrigerant from leaking If conditioner is installed in a small room...

Страница 5: ...b the neighborhood Place where there is not heavy snowfall in the winter time Place where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a st...

Страница 6: ...HEAA Install the unit so that the angle of inclination must be less than 3 degrees Note 1 Give enough room for the concrete foundation to fix by anchor bolts 2 Place the concrete foundation deep enoug...

Страница 7: ...ion Procedure AU182AEEAA AU282AHEAA AU28NAHEAA AU242AGEAA 730 630 308 335 Power Wiring Terminal Power Wiring Distribution Hole 860 Power Wiring Terminal Power Wiring Distribution Hole 25 780 640 500 2...

Страница 8: ...id pipe Flare connection Indoor unit Flare connection 3 way stop valve Outdoor unit 3 way stop valve Gas pipe Liquid pipe Flare connection Indoor unit Flare connection 2 way stop valve AU362AIEAAAU36N...

Страница 9: ...pe hold the pipe centre to centre then screw nut on by hand refer to Fig Be careful not to let foreign matters such as sands enter the pipe 4 Piping connection Forced fastening without centering may d...

Страница 10: ...ll in close state In order to prevent the nitrogen entering the circulation system of outdoor unit tighten the valve rod before giving pressure both gas and liquid valve rods Outdoor Completely tighte...

Страница 11: ...remove the air inside the system After air tightness test and discharging all the nitrogen connect the vacuum pump as the following figure shown Refrigerant piping 10 When the total length L of the t...

Страница 12: ...o contacts should be no less 3 mm If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person If the fuse on PC board is broken please chan...

Страница 13: ...on the side panel WARNING DO NOT CONNECT THE NEUTRAL WIRE TO OR PHASE INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG 1 FIG 2 FIG 3 INCORRECT WIRING CAUSE EQUIPMENT DAMAGE N R S T Installation Pr...

Страница 14: ...abnormal Temperature protection malfunction 0D Power LED flashes 13 times Drainage system malfunction 08 Power LED flashes 10 times 0B Power LED flashes 11 times Alarm of exterior annunciator 7 Troub...

Страница 15: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com...