In the first to third test steps, if the pressure drops, check the leakage in each joint
use sense of hearing, feeling and soap water, etc. methods to find the leaking point.
After confirming the leaking point, welding it again or tighten the nut tightly again.

Checking the leaking point

First step: 0.3MPa (3.
0kg/cm

2

g) pressurize

over 3 minutes.

Second step: 1.5Mpa
(15kg/cm

2

g) pressurize

over 3 minutes.  Large
leakage will be found.

Third step:  3.0 MPa
(30kg/cm

2

g) pressurize

about 24 hours. Little
leakage will be found.

After finishing connection of refrigerant pipe, it shall perform air tightness test.
The air tightness test adopts nitrogen tank to give pressure according to the pipe connection
mode as the following figure shown.
The gas and liquid valve are all in close state. In order to prevent the nitrogen entering the
circulation system of outdoor unit, tighten the valve rod before giving pressure (both gas
and liquid valve rods).

Outdoor

Completely tightened

Completely tightened

Flare part

Outdoor units

Manhole

Discharging valve

3-way valve totally closed
(Gas side)

Low pressure peizometer

High pressure peizometer

Meter separator

Dropping valve

3-way valve totally closed
(Liquid side)

Nitrogen tank

VL VH

Indoor units

Indoor

Flare part

9

From pressurizing to 24 hours later, each

 1* 

difference of ambient temperature

will make 0.01MPa(0.1kg/cm

2

g) pressure change. It shall be corrected during test.

Check if the pressure drops

The pressure does not drop-passed
The pressure drops-check the leaking point.

5. Air discharging method

CYLINDER
OF
NITROGEN

SERVICE
HOUSE

LARGE
SLIP-ON
CONNECTOR

SWEAT
JOINT

TUBING
BRING
BRAZED

LINE
PRESSURE
GAUGE

CYLINDER
PRESSURE
GAUGE

Installation Procedure

Refrigerant piping

Содержание AU182AEEAA

Страница 1: ...ad this manual carefully Please keep this manual properly for future use CONTENTS Name of Parts 1 Safety Cautions 2 3 Installation Procedure 4 13 INSTALLATION INSTRUCTIONS No 0010577959 D AU242AGEAA A...

Страница 2: ...unit Compressor AU36NAIEAA AU362AIEAA AU48NAIEAA AU60NAIEAA AU242AGEAA AU182AEEAA Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet In...

Страница 3: ...autions Carefully read the following information in order to operate the airconditioner correctly WARNING If any abnormal phenomena is found e g smell of firing please cut off the power supply immedia...

Страница 4: ...tioner Incorrect installation may cause water leak electrical shock and fire hazard Call the dealer to take measures to prevent the refrigerant from leaking If conditioner is installed in a small room...

Страница 5: ...b the neighborhood Place where there is not heavy snowfall in the winter time Place where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a st...

Страница 6: ...HEAA Install the unit so that the angle of inclination must be less than 3 degrees Note 1 Give enough room for the concrete foundation to fix by anchor bolts 2 Place the concrete foundation deep enoug...

Страница 7: ...ion Procedure AU182AEEAA AU282AHEAA AU28NAHEAA AU242AGEAA 730 630 308 335 Power Wiring Terminal Power Wiring Distribution Hole 860 Power Wiring Terminal Power Wiring Distribution Hole 25 780 640 500 2...

Страница 8: ...id pipe Flare connection Indoor unit Flare connection 3 way stop valve Outdoor unit 3 way stop valve Gas pipe Liquid pipe Flare connection Indoor unit Flare connection 2 way stop valve AU362AIEAAAU36N...

Страница 9: ...pe hold the pipe centre to centre then screw nut on by hand refer to Fig Be careful not to let foreign matters such as sands enter the pipe 4 Piping connection Forced fastening without centering may d...

Страница 10: ...ll in close state In order to prevent the nitrogen entering the circulation system of outdoor unit tighten the valve rod before giving pressure both gas and liquid valve rods Outdoor Completely tighte...

Страница 11: ...remove the air inside the system After air tightness test and discharging all the nitrogen connect the vacuum pump as the following figure shown Refrigerant piping 10 When the total length L of the t...

Страница 12: ...o contacts should be no less 3 mm If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person If the fuse on PC board is broken please chan...

Страница 13: ...on the side panel WARNING DO NOT CONNECT THE NEUTRAL WIRE TO OR PHASE INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG 1 FIG 2 FIG 3 INCORRECT WIRING CAUSE EQUIPMENT DAMAGE N R S T Installation Pr...

Страница 14: ...abnormal Temperature protection malfunction 0D Power LED flashes 13 times Drainage system malfunction 08 Power LED flashes 10 times 0B Power LED flashes 11 times Alarm of exterior annunciator 7 Troub...

Страница 15: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com...

Отзывы: