Seivice diagnosis
Domestic air conditioner
11.4.4 Outdoor DC fan motor fault
Check whether Terminal on the outdoor
mainboard is well inserted.
Is it normal?
Yes
NO
Reinsert the terminals
Electrify the machine again and turn
it on in the Cool state with the remote
controller. check whether motor can
run
˛
Yes
Measure the voltage between 3 and 6 of
the terminal about 0-5v.
Is it normal?
N0
the motor of the outdoor unit is damaged
and needs replacing.
Measure the voltage between 1 and 3 of the terminal of
fan motor on the mainboard about DC310V,Measure
the voltage between 3 and 4 of the terminal about
DC15V. Measure the voltage between 5 and 3 of the
terminal about 1-6v.
NO
Is it normal?
The mainboard of the outdoor unit is
damaged and needs replacing.
N0
Yes
Yes
Method of
malfunction detection
Malfunction detection
conditions
Troubleshooting
DC fan motor is detected by checking the fan running condition and so on
when the data of EEPROM
is error or
the EEPROM
is damaged
Ŷ
DC fan motor protection dues to the DC fan motor faulty
Ŷ
DC fan motor protection dues to faulty PCB
Supposed causes
* Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage
may be occurred.
LED1
flash
9
times
Outdoor diplay
31