4.  Installation of indoor unit

Fix the indoor unit to the hanger bolts.
If required, it is possible to suspend the unit to the beam, etc.
Directly by use of the bolts without using the hanger bolts.

When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes
of hanging bracket.

Note

Adjusting to the levelness

(a)  Adjust the out-of levelness using a level or by
      the following method.

Make adjustment so that the relation between
the lower surface of the unit proper and water
level in the hose becomes as given below.

(b) Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float
      switch may occur.

PVC hose

Piping side

Supply water

Water level

0~5 mm

(0~0.2")

Bring the piping side slightly lower.

Hanging bolt

M10 nut

Main unit

M10 washer

M10 spring washer

Drain hose

Stage
difference
part

Drain socket

Drain socket

Main unit

VP 25 joint
(field purchased)

Pipe cover(large)
[for insulation]
(accessory)

VP 25
(field purchased)

Pipe cover
[for insulation]
(field purchased)

Drain hose
(accessory)

Pipe cover(small)
[for insulation]
(accessory)

Clamp
(accessory)

Adhesion

For drain pipe, use hard PVC general purpose pipe
VP-25(I.D.1") which can be purchased locally. When
connecting, insert a PVC pipe end securely into the
drain socket before tightening securely using the
attached drain hose and clamp. Adhesive must not
be used connection of the drain socket  and drain
hose (accessory).

(c)

5.  Drain Piping

(a) Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an
       elevation or making traps.

When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the  piping
on the unit side. Also, fix the piping at a point as close as possible to the unit.

Do not pipe under water

Keep free from traps

Avoid riding across an elevation

Air vent

Inproper piping

Good piping

1.5m ~ 2m

Suspension
bolts

Heat
insulation

A downhill grade
of 1/100 or more

(b)

Installation Manual For Indoor Unit

Содержание AD282AHEAA

Страница 1: ...A DUCT TYPE AIR CONDITIONER AD282AHEAA AD362AHEAA AD482AHEAA AD602AHEAA Operation Instruction Manual Please read this operation manual before using the air conditioner Please keep this manual careful...

Страница 2: ...intenance 9 For Preparation of Heating Hot Keep 10 Is The Unit Installed Correctly 11 Installation Manual For Indoor Unit 12 20 Installation Manual For Electric Wiring 21 Safety Precautions 3 5 Parts...

Страница 3: ...an appropriate anti pollution method of disposal Disposal of the packaging of your new air conditioner All the packaging materials employed in the package of your new air conditioner may be disposed w...

Страница 4: ...ident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending on the place of installation a circuit breaker may be necessary Drain pipe should be ar...

Страница 5: ...of such equip ment which generates steam condensed water may drip during cooling operation or it could cause a fault current or short circuit When operating the system simultaneously with a combustio...

Страница 6: ...e During installa tion when the connecting cables break off it must be assured that the grouding wire is the last one to be broken off 6 The breaker of the air conditioner should be all pole switch an...

Страница 7: ...6 Indoor Unit Air outlet Air inlet Duct Duct Drainpipe Parts and Functions...

Страница 8: ...cle exist at the air inlet or outlet Cooling is not sufficient Isn t sun shine invading direct Isn t any unexpected heating load generated Isn t the room much crowded Isn t the swing louver horizontal...

Страница 9: ...e FAN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode E...

Страница 10: ...the air inlet and air outlet of both indoor and outdoor units Make sure that the air filter is not dirty Cut in the power supply switch 12 hours before starting run Post Season Care Operate the unit...

Страница 11: ...RMING OPERATION Heat pump type warming Defrosting operation Atmospheric temperature and warming capacity Period of warm up With the heat pump type warming the mechanism of heat pump that concentrate h...

Страница 12: ...The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordina rily high The place where near the machine which radiates the electromagn...

Страница 13: ...can result from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes etc Improper installations can result...

Страница 14: ...he chosen installation place should meet the following requirements and get the user s consent Place ensures ideal airflow distribution The passage of airflow has no obstacles When importing outside a...

Страница 15: ...ion wire indoor and outdoor unit connection wire of indoor unit so that after installation they can be immediately connected with outdoor unit Cut the opening on the ceiling Maybe it needs to strength...

Страница 16: ...ain unit VP 25 joint field purchased Pipe cover large for insulation accessory VP 25 field purchased Pipe cover for insulation field purchased Drain hose accessory Pipe cover small for insulation acce...

Страница 17: ...nage where the gas with sulfur may be generated Backwater bend Because the drain spout is at the position which negative pressure may occur So with the rise of water level in the drain pan water leaka...

Страница 18: ...adrate air duct Presuming the unit length friction impedance of the duct is 1Pa m when the dimension of one side of the air duct is fixed as 250mm as shown below Note 1Pa m 0 1mmAg m The chosen chart...

Страница 19: ...d The result is because of the irregular outer air mass strong wind and sunshine the humidity is increased There may be water drop on the outside of duct For cement and other new constructions even if...

Страница 20: ...ory the capacity number of fan controller is set at No 5 Rotate this switch capacity number setting No 1 No 8 Once the fan controller has trouble this linker can perform emergency assistant control Wh...

Страница 21: ...pipe leaks then do heat insulation treatment as below figure shown Only use seal cushion to bind the joint part of air pipe and heat insulation parts Paste the refrigerant oil here Torque spanner Span...

Страница 22: ...low This table shows 20 m length wires with less than 2 voltage drop 2 Wiring connection Make wiring to supply power to the outdoor unit so that the power for the indoor unit is supplied by terminals...

Страница 23: ...for more than 2m continuously CT check abnormal 3 times in 30m Fault phase short of phase out of balance greatly High pressure switch acts 3 times in 30m Low pressure switch acts in normal running Co...