background image

Do not wash the air conditioner with water.

Do not install the system where the air outlet

reaches directly the flora and fauna.

Make sure to use a fuse of proper electric rating.

Do not operate the system while the air outlet grill

is removed.

It is strictly prohibited to place a container of

combustible gas or liquid near the air conditioner

or to spray it directly with the gas or liquid.

Neither stand on the air conditioner nor

place something on it.

Do not use the power switch to turn on or off the

system.

Do not touch the air outlet section while the swing

louver is operating.

Do not use such equipment as a water heater, etc.

around the indoor unit or the wire controller.

ON

OFF

It could cause electric shocks.

It will not be good for their health.

Use of steel or copper wire in place of a fuse is

strictly prohibited because it could result in a trouble

or fire accident.

There is a risk of injury.

It could cause a fire accident.

There are risks of falling or injury by collapsed

object.

It could cause a fire or water leakage.

There is a risk of injury.

If the system is operated at the vicinity of such

equipment which generates steam, condensed

water may drip during cooling operation or it could

cause a fault current or short-circuit.

When operating the system simultaneously with

a  combustion  apparatus,  indoor  air  must  be

ventilated frequently.

Check occasionally the support structure of the

unit for any damage after a use of long period of

time.

Insufficient ventilation could cause an oxygen

deficiency accident.

If the structure is not repaired immediately, the

unit could topple down to cause a personal injury.

When cleaning the system, stop the operation and

turn off the power switch.

Do not put water containers on the unit such as a flower vase, etc.

Cleaning should never be done while the internal

fans are running with high speed.

If the water enters into the unit and damages the electric insulation material, it may cause electric shock.

WARNING

CAUTION

CAUTIONS FOR OPERATION

You should refrain from exposing your body directly

to cool wind for a long time.

Do not poke the air inlet or outlet with a bar, etc. When any abnormal condition (scorching smell or

others) is found, stop the operation immediately

and turn off the power switch. Then consult your

dealer.

It could affect your physical condition or cause

some health problems.

Since the internal fan is operating with a high

speed, it could cause an injury.

If you continue the operation without removing the

cause, it could result in a trouble, electric shock

or fire.

The system should never be used for any other

purposes than intended such as for preservation

of food, flora and fauna, precision devices or work

of art.

Do not handle switches with a wet hand.

Combustion  apparatus  should  not  be  placed

allowing a direct exposure to wind of air conditioner.

Incomplete combustion could occur on the

apparatus.

It could cause electric shocks.

It could cause deterioration of food or other

problems.

5

Safety Precautions

Содержание AD24MS1ERA

Страница 1: ...DUCT TYPE AIR CONDITIONER OPERATION MANUAL AND INSTALLATION MANUAL Please read this manual carefully before installation Keep this operation manual for future reference No 0150510323 B ...

Страница 2: ......

Страница 3: ......

Страница 4: ... instructions set forth in the User s Guide Installation shall be done by professional people don t install unit by yourself For the purpose of safety the air conditioner must be properly grounded in accordance with specifications Always remember to unplug the air conditioner before opening inlet grill Never unplug your air conditioner by pulling on the power cord Always grip plug firmly and pull ...

Страница 5: ...jury or death Installation by yourself is not encouraged because it could cause such problems as water leakage electrical shock or fire accident by some improper handing Installationbyyourselfisnotencouragedbecauseitcould cause such problems as water leakage electrical shock or fire accident by some improper handing Do not install nearby the place where may have leakage of flammable gas Depending ...

Страница 6: ...ture of the unit for any damage after a use of long period of time Insufficient ventilation could cause an oxygen deficiency accident If the structure is not repaired immediately the unit could topple down to cause a personal injury When cleaning the system stop the operation and turn off the power switch Do not put water containers on the unit such as a flower vase etc Cleaning should never be do...

Страница 7: ...n following situation 6 Safety Precautions Cooling Heating Indoor temperature Outdoor temperature Indoor temperature Outdoor temperature max DB WB min DB WB max DB WB min DB WB max DB WB min DB WB max DB WB min DB WB 32 23 C 18 14 C 46 26 C 10 6 C 27 C 15 C 24 18 C ...

Страница 8: ...7 Parts and Functions ...

Страница 9: ...8 ...

Страница 10: ...9 ...

Страница 11: ... controller or switches by sharp objects The temperature is on the basis of the setting value The wind temperature may not reach the setting value because of the outer air conditioner and system protection When the wired controller is power on the screen fully displays it for two seconds and clock zone 8888 888 88 8 flicker for 30 seconds All the switches are invalid at the time Remarks Note Opera...

Страница 12: ...ation HIGH C ROOM TEMP The timing is based on the real time Thus the real time should be regulated in advance The clock regulation steps are as follows 3 Press setting switch The setting is achieved If not in timing the screen displays the real time If in timing the screen displays the timing time If you want to know the real time go to the first step CLOCK flickers and the time displayed is the r...

Страница 13: ...h If you want to change the timing mode to normal operation press timing until there is no timing display When the timing is invalid the mode is in normal operation Cancel timing 1 The unit starts or stops at the setting time Meanwhile it displays the timing time 2 ON Timing OFF timing and circulation means that the unit is on and off at the setting time everyday When timing ON or timing OFF flick...

Страница 14: ...ction if normal it will display YY stands for the latest time malfunction The failure code of every unit will display for 3 seconds After the failure codes of all indoor units in the whole group are displayed the mode will quit automatically Operation How to change the function switches Master wire controller Slave wire controller Function All of functions Only with below functions ON OFF MODE FAN...

Страница 15: ...Communication wiring length m Dimensions of wiring 100 0 3mm2 x3 core shielded wire 100 and 200 0 5mm2 x3 core shielded wire 200 and 300 0 75mm2 x3 core shielded wire 300 and 400 1 25mm2 x3 core shielded wire 400 and 600 2mm2 x3 core shielded wire One side of the shielded sheet of communication wire must be earthed A B C A B C A B C A B C Indoor 1 Wire controller A B C Wire controller Polar wire I...

Страница 16: ...ver to ordinary heating operation Heat pump type warming With the heat pump type warming the mechanism of heat pump that concentrate heat of outdoor air with the help of refrigerant to warm the indoor space is utilized Defrosting operation When a room is warmed with a heat pump type air conditioner frost accumulates on the heat exchanger of outdoor unit along with the drop of indoor temperature Si...

Страница 17: ... is consumed even the air conditioner is in stop Clean the air filter and set it in the place Care and Cleaning of the unit Clean with soft and dry cloth If it is very dirty dissolve neutral detergent in the lukewarm water and make the cloth wet with the water After wiping clean off the detergent using clean water 1 Clean the air filter by lightly tapping it or with the cleaner It is more effectiv...

Страница 18: ...supply power in normal Isn t the signal receiving section exposed to the direct sunlight or strong illumination Isn t the earth leakage breaker in action It is dangerous Turn off the power supply switch immediately and contact the sales dealer Power supply switch is not ON Cooling or heating is not sufficient Is the thermostat adjust as required Isn t the air filter dirty Isn t any doors or window...

Страница 19: ...AN mode during cooling To prevent frost from being accumulated on the indoor unit heat exchanger it is sometimes automatically switched to the FAN mode but it will soon return to the cooling mode Even if the operation switch is turned on cooling dehumidifying or heating is not operable for three minutes after the conditioner is stopped Because the protecting circuit is activated During this time a...

Страница 20: ... 1D Outdoor unit abnormal 3 0 1E Outdoor unit abnormal 3 1 1F Outdoor unit abnormal 3 2 20 Outdoor unit abnormal 3 3 21 Outdoor unit abnormal 3 5 23 Outdoor unit abnormal 3 6 24 Outdoor unit abnormal 3 7 25 Outdoor unit abnormal 3 8 26 Outdoor unit abnormal 3 9 27 Outdoor unit abnormal 4 3 2B Outdoor unit abnormal 4 4 2C Outdoor unit abnormal 4 7 2F Outdoor unit abnormal 4 8 30 Outdoor unit abnorm...

Страница 21: ...sult from a falling of the unit Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes etc Improper installations can result in accidents due to a violent falling over of the unit For electrical work please see that a licensed electrician executes the work while following the safety standards related to electrical equipment and l...

Страница 22: ...The place where salt breeze blows Seaside etc The place where dense soot smoke exists The place where humidity is extraordinarily high The place where near the machine which radiates the electromagnetic wave The place where voltage variation is considerably large For details consult your sales dealer The electric work must be burden on the authorized engineer with qualification for electric work a...

Страница 23: ... INSTALLATION FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH EQUIPMENT MALFUNCTION AND OR PROPERTY DAMAGE Preparation of indoor unit Before or during the installation of the unit assemble necessary optional panel etc depending on the specific type Select places for installation satisfying following conditions and at the same time obtain the consent on the part of your cli...

Страница 24: ...sed by employing such option as the high performance filter etc change the connection of connectors provided at the flank of control box as shown below PVC hose Piping side Supply water Water level 0 5 mm 0 0 2 Bring the piping side slightly lower Hanging bolt M10 nut Main unit M10 washer M10 spring washer Red Yellow White Standard tap at shipping High speed tap Black White Connector white Connect...

Страница 25: ...tion A downhill grade of 1 100 or more b c VP 30 Secure the elevation as high as possible approx 100 mm A downhill grade of 1 100 or more Right overhead Drain hose Joint for VP 25 Local procurement 600 Maximum local drain up dimension 290 325mm Avoid positioning the drain piping outlet at a place where generation of odor may be stimulated Do not lead the drain piping direct into a sewer from where...

Страница 26: ...Conduct a drainage test after completion of the electrical work During the trial make sure that drain flows properly through the piping and that no water leaks from connections In case of a new building conduct the test before it is furnished with the ceiling Be sure to conduct this test even when the unit is installed in the heating season Attached drain hose clamp Drain piping Main unit Drain si...

Страница 27: ...ng Electrical wiring work should be conducted only by authorized personnel Do not connect more than three wires to the terminal block Always use round type crimped terminal lugs with insulated grip on the ends of the wires Use copper conductor only Select wire sizes and circuit protection from table below This table shows 20 m length wires with less than 2 voltage drop Wiring connection Make wirin...

Страница 28: ......

Отзывы: