5.6 Electric characteristics
Units
Power supply
Indoor fan motor
Power input (w)
Model
Phase
FQY
Voltage
Volt.
range
MCA
MFA
Output
(W)
FLA
Cooling Heating
AB052MCERA(M)
1
50/60
220
198~242 0.325
1.04
26
0.26
17
17
AB072MCERA(M)
1
50/60
220
198~242 0.325
1.04
26
0.26
17
17
AB092MCERA(M)
1
50/60
220
198~242 0.325
1.04
26
0.26
17
17
AB122MCERA(M)
1
50/60
220
198~242 0.325
1.04
26
0.26
18
18
AB162MCERA(M)
1
50/60
220
198~242 0.325
1.04
26
0.26
26
26
AB182MCERA(M)
1
50/60
220
198~242 0.325
1.04
26
0.26
35
35
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.