light should be off for 5 seconds.
b) For the units’ malfunctions Annex 1
If there’s malfunction with the units, this will not affect the run of the complete appliance, but this
can be displayed by the malfunction light, the light flashing frequency is 0.5HZ, the number of
times is according to the malfunction table of the indoor units. When a round of flashing is
finished, the light should be off for 10 seconds. Then report according to the order : unit A
unit B
unit C unit D, that is, if there’s malfunction with several units, then just report the indoor unit
with the highest priority level. Among the unit malfunctions, the priority level of the
communication malfunction is the highest, for others, that appears first will have the priority.
Remarks: in 3 minutes when the compressor stops, the units’ malfunctions are not displayed;
the complete appliance’s malfunctions are prior to the units’ malfunctions.
Annex 1 Malfunction codes of the out unit
Remarks: under the mode of refrigeration, the malfunctions of each unit’s thin pipe temperature
sensor are not reported, under the mode of heating, the malfunctions of each unit’s thick pipe
temperature sensor are not reported.
F12
1
Outdoor EEPROM error
F1
2
The protection of IPM
F22
3
Overcurrent protection of AC electricity for the outdoor model
F3
4
Communication fault between the IPM and outdoor PCB
F19
6
Power voltage is too high or low
F4
8
Overheat protection for Discharge temperature
F21
10
Defrost temperature sensor failure
F6
12
Ambient temperature sensor failure
F25
13
Discharge temperature sensor failure
E7
15
Communication fault between indoor and outdoor units
F11
18
deviate from the normal for the compressor
----
19
Loop of the station detect error
E9
21
High work-intense protection
---
24
Overcurrent of the compressor
---
25
Overcurrent protection for single-phase of the compressor
----
36
The socket protect
Outdoor Unit
Ambient Sensor, Defrost Sensor, Pipe sensor
R25 =10K
3% B25 /50 =3700K 3%
Temp.( )
Max.(K
Ω
)
Normal(K
Ω
)
Min.(K
Ω
)
Tolerance( )
-30
165.2170
147.9497
132.3678
-1.94
1.75
-29
155.5754
139.5600
125.0806
-1.93
1.74
-28
146.5609
131.7022
118.2434
-1.91
1.73
Functions and Control
Domestic air conditioner
7.2 Value of thermistor
21
Содержание 2U14CS4ERA
Страница 10: ... Pinping diagrams Domestic air conditioner 4ˊPinping diagrams 8 ...
Страница 11: ... Operation range Domestic air conditioner 5ˊOperation range 9 ...
Страница 15: ...PCB 2 CN1 CN5 CN6 CN7 CN10 CN11 CN8 CN9 CN2 CN3 CN4 Domestic air conditioner Wiring diagram ...
Страница 16: ...0 Wiring diagram Domestic air conditioner ...
Страница 35: ...WARNING CAUTION Installations Domestic air conditioner 33 ...
Страница 36: ...Installations Domestic air conditioner 34 ...
Страница 37: ...Installations Domestic air conditioner 35 ...
Страница 38: ...Installations Domestic air conditioner 36 ...
Страница 39: ...Installations Domestic air conditioner 37 ...
Страница 40: ...Installations Domestic air conditioner 38 ...
Страница 41: ...Installations Domestic air conditioner 39 ...
Страница 85: ...1 Removal Procedure 1 Domestic Air Conditioner p ...
Страница 86: ...Loosen the top panel screws 1 2 Lift the top panel Removal Procedure 2 Domestic Air Conditioner ...
Страница 87: ...Loosen the screws and pull the panel Removal Procedure 3 Domestic Air Conditioner ...
Страница 89: ...Removal Procedure 5 Domestic Air Conditioner 2 ...
Страница 90: ...Removal Procedure 6 Domestic Air Conditioner 3 ...
Страница 91: ...2 Loosen the fixing screws and remove the motor Removal Procedure 7 Domestic Air Conditioner ...
Страница 92: ...Removal Procedure 8 Domestic Air Conditioner 4 F M P B ...
Страница 93: ...and remove the reactor Loosen the screw Removal Procedure 9 Domestic Air Conditioner ...
Страница 94: ...Loosen the marked screws and pull out the backgurd Removal Procedure 10 Domestic Air Conditioner 5 C H E 1 ...
Страница 96: ...4 Remove the compre ssor and pipe assay 5 Remove the conden ser Removal Procedure 12 Domestic Air Conditioner ...