Service diagnosis
38
Domestic air conditioner
10.3.5 IPM protection
Outdoor display:
ƶ ƾ ƾ
/ F1
LED1 flash 2 times
Method of IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
Malfunction
Ŷ
The system leads to IPM protection due to over current
Decision
Ŷ
The compressor faulty leads to IPM protection
Conditions
Ŷ
circuit component of IPM is broken and led to IPM protection
Supposed
Ŷ
IPM protection dues to the compressor faulty
Causes
Ŷ
IPM protection dues to faulty PCB of IPM module
Ŷ
Compressor wiring disconnected
Troubleshooting * Caution Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
12
<(6
12
<(6
Содержание 1U35YEGFRA
Страница 11: ...Piping diagrams Domestic air conditioner 4ˊPiping diagrams 9 ...
Страница 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40 ...
Страница 37: ...Service diagnosis 37 Domestic air conditioner ...
Страница 56: ...57 Do C omestic air ircuit Diagra conditioner ams r ...
Страница 59: ...Removal Procedure 1 Removal of Outdoor panel RPHVWLF LU RQGLWLR ...
Страница 60: ...Removal Procedure 2 Domestic Air Condition ...
Страница 61: ...4 Removal Procedure 3 Domestic Air Condition ...
Страница 62: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR ...
Страница 63: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR ...
Страница 64: ...Removal Procedure 4 Removal of fan motor brcked and partition RPHVWLF LU RQGLWLR ...
Страница 65: ...Removal Procedure 7 Domestic Air Condition ...
Страница 66: ...Removal Procedure 5 Removal of compressor and heat exchanger RPHVWLF LU RQGLWLR ...
Страница 67: ...Removal Procedure 9 Domestic Air Condition ...