Functions and control 

  15 

                            Domestic air conditioner

 

7. Functions and control 

7.1 Main functions and control specification 

7.1.1 The operation frequency of outdoor unit and its control 

7.1.1.1 The operation frequency control of compressor

The operation frequency scope of compressor

Mode 

Minimum operation frequency 

Maximum operation frequency 

Heating 12K

31Hz 

75Hz 

Refrigeration 12K

7.1.1.2 The starting of compressor 

When  the  compressor  is  started  for  the  first  time,  it  must  be  kept  under  the  conditions  of 

38Hz,58Hz,88Hz for 30second,one minute, one minute (the overheating protection of the outdoor unit 
air-blowing temperature, immediately decrease the frequency when the compressor is overflowing and 
releasing the pressure) then it can be operated towards the target frequency. When the machine runs 
normally, there’s no such process. After starting the compressor for operation, the compressor should 
run according to the calculated frequency, and every determined frequency for protection should be 
prior to the calculated frequency.   

7.1.1.3 The speeds of increasing or decreasing the frequency of the compressor   

The speed of increasing or decreasing the frequency rapidly 1 -----------1HZ/second 
The speed of increasing or decreasing the frequency slowly 2 -----------1HZ/10seconds

7.1.1.4 The calculation of the compressor’s frequency 

Refrigeration/dehumidification mode:     

Pn=(Nh_c-

 S_c)*10 50        outdoor environment control 

Pn=(Nh_c-

 S_c) *10 50          PID control 

Heating mode:   

Pn=(S_c

 -Nh_c)

 *10 60        outdoor environment control 

Pn=(S_c

 -Nh_c)

 *10 60        PID control 

(Nh_c=indoor

environment    temperature        S_c=setting temperature) 

1 The minimum/maximum frequency limitation 
A While refrigerating: F-MAX-r is the maximum operation frequency of the compressor; F-MIN-r is the 
minimum operation frequency of the compressor. 
B While heating: F-MAX-d is the maximum operation frequency of the compressor; F-MIN-d is the 
minimum operation frequency of the compressor. 
2 The frequency limitation which is affected by the environment temperature. 

(Wh_c= environment temperature) 

Heating mode:   

Serial No. 

Temperature scope 

Frequency limitation 12K

Wh_c<-12 

Max_hz1      99HZ

 

Wh_c<-8 

Max_hz2      99HZ

 

31Hz 

99 Hz 

Содержание 1U35YEGFRA

Страница 1: ...angers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or Repair the product or products dealt with in this service information by anyone else could result in serious injury or death WARNING 2018 Qingdao Haier Air Conditioner General corp Ltd All rights reserved Unauthorized copyin...

Страница 2: ...ns 7 3 Sensors list 8 4 Piping diagrams 9 5 Operation range 10 6 Printed circuit board connector wiring diagram 11 7 Functions and control 8 Dimensional drawings 9 Center of gravity 10 Service diagnosis 11 Performance and curves diagrams 12 Circuit diagrams 15 48 30 29 29 56 ...

Страница 3: ...me explanation 1 U 3 5 Y E G F A R The maximum combination number Type of outdoor unit U normal type Nominal cooling capacity 12000BTU h Platform of outdoor units 0 8P Platform Europe Version number Heat pump R32 refrigerant DC inverter Apply toT1 220 240V50HZ 1ph 1 ...

Страница 4: ...near the symbol After the repair work is complete be sure to conduct a test operation to ensure that the equipment operates Normally and explain the cautions for operating the product to the customer 1 2 1 Embedded wire checking before installation Check the embedded wire diameter suitable to request Power supply from indoor 2 5kw 1 0mm 2 3 5kw 5kw 1 5mm 2 7kw 1 0mm 2 Power supply from outdoor 1 0...

Страница 5: ... stop the air conditioner operation by plugging or unplugging the power cable plug Plugging or unplugging the power cable plug to operate the equipment can cause an electrical shock or fire Warning Do not repair the electrical components with wet hands Working on the equipment with wet hands can cause an electrical shock Do not clean the air conditioner by splashing water Washing the unit with wat...

Страница 6: ...ircuit capacity and improper electrical work can cause an electrical shock or fire Be sure to use the specified cable to connect between the indoor and outdoor units Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals Improper connections can cause excessive heat generation or fire When connecting the cable between the ...

Страница 7: ...o install the packing and seal on the installation frame properly If the packing and seal are not installed properly water can enter the room and wet the furniture and floor 1 2 4 Inspection after Repair Warning Check to make sure that the power cable plug is not dirty or loose then insert the plug into a power outlet all the way If the plug has dust or loose connection it can cause an electrical ...

Страница 8: ...ock Be sure to check the drainage of the indoor unit after the repair Faulty drainage can cause the water to enter the room and wet the furniture and floor 1 2 5 Using Icons Icons are used to attract the attention of the reader to specific information The meaning of each icon is described in the table below 1 2 6 Using Icons List Icon Type of Information Description Note Note A note provides infor...

Страница 9: ... s s e r p d n u o S 64 B d r e w o p d n u o S ELECTRICAL SPECIFICATIONS g n i t a e h g n i l o o c 2 4 5 4 A t n e r r u c g n i n n u r l a n i m o N Maximum running current A 7 1 7 1 4 1 4 1 A t n e r r u c g n i t r a t S TECHNICAL SPECIFICATIONS PARTS g n i t a e h g n i l o o c Compressor r o s s e r p m o C y r a t o R e p y T GSD102RKQA6JT6B l e d o M 0 99 W t u p t u o r o t o M t n e l...

Страница 10: ...f Additional Charge of Refrigerant g m 20 Intemational Protection degree IP X4 Note the data are based on the conditions shown in the table below h t g n e l g n i p i P g n i t a e h g n i l o o c Indoor 27 DB 19 WB Outdoor 35 DB 24 WB Indoor 20 DB Outdoor 7 DB 6 WB 5m 3 Sensors list type Description Qty Ambient sensor Its used for detecti e d i s r o o d t u o f o e r u t a r e p m e t g n Defro...

Страница 11: ...Piping diagrams Domestic air conditioner 4ˊPiping diagrams 9 ...

Страница 12: ...Operation range 10 Domestic air conditioner 5 Operation range 10 0 21 27 35 20 40 60 43 20 40 ...

Страница 13: ...ram 11 Domestic air conditioner 6 Printed circuit board connector wiring diagram PCB Control PCB For 1U35YEGFRA UNIT MODEL PCB MODEL 1U35YEGFRA 0011800879J PFC Reactor Compressor Sensor E valve DC fan motor Bottom heater 4 way valve PE COMM L N ...

Страница 14: ...Functions and control 13 Domestic air conditioner Wiring diagrams OUTDOOR UNIT OUTDOOR UNIT WIRING DIAGRAM COMPRESSOR 0011501311E G CONDENSER G G G ...

Страница 15: ...frequency for protection should be prior to the calculated frequency 7 1 1 3 The speeds of increasing or decreasing the frequency of the compressor The speed of increasing or decreasing the frequency rapidly 1 1HZ second The speed of increasing or decreasing the frequency slowly 2 1HZ 10seconds 7 1 1 4 The calculation of the compressor s frequency Refrigeration dehumidification mode Pn Nh_c S_c 10...

Страница 16: ...e environment but also the maximum ability limitation of the system When the starting ability is not the maximum its maximum frequency limitation is calculated by the following equations The frequency limitation which is affected by the temperature and under the condition of actual ability the actual running system ability the maximum frequency which is limited by the temperature and under the con...

Страница 17: ... skipping frequently it must be kept under each mode for over 30 seconds and then it can be changed to another mode when refrigerating the time is changed to 15 seconds 7 1 2 1 The outdoor fan control Within three minutes of compressor starting the compressor is controled according to the ambient temperature Tao Tao 22 22 Tao 29 Tao 29 Refrigeration dehumidification 12K 400r min 600r min 760r min ...

Страница 18: ...for each time continuously sampling for 8 times then order them and take the mean value of the middle 2 values take the mean value TTC 09K Abnormal stop 107 Decreasing the frequency rapidly 1HZ second 104 Decreasing the frequency slowly 1HZ 10seconds 102 The frequency doesn t change 100 Increasing the frequency 1HZ 10second 93 Increasing the frequency 1HZ 1second TTC 110 lasts for 20 seconds Overh...

Страница 19: ...s greater than 9A the frequency of the compressor decreases at the speed of 1HZ second During the starting process of the compressor if the AC current is greater than 8A the frequency of the compressor decreases at the speed of 0 1HZ second During the starting process of the compressor if the AC current is greater than 7 5A the frequency of the compressor increases at the prohibited speed During t...

Страница 20: ...th the running state 11ć ice_temp_3 5 ice_temp_3 3 9ć Increasing slowly 8ć ice_temp_3 2 Keeping the frequency ice_temp_3 7ć 7ć ice_temp_2 5ć Decreasing slowly ice_temp_1 3ć Decreasing rapidly ice_temp_1 1ć Stop When Tpg_indoorLJ ice_temp_1 the frequency of the compressor decreases at the speed of 1HZ 1second When Tpg_indoorLJ ice_temp_2 the frequency of the compressor decreases at the speed of 1HZ 1...

Страница 21: ...7 132 3678 1 94 1 75 29 155 5754 139 5600 125 0806 1 93 1 74 28 146 5609 131 7022 118 2434 1 91 1 73 27 138 1285 124 3392 111 8256 1 89 1 71 26 130 2371 117 4366 105 7989 1 87 1 70 25 122 8484 110 9627 100 1367 1 85 1 69 24 115 9272 104 8882 94 8149 1 83 1 67 23 109 4410 99 1858 89 8106 1 81 1 66 22 103 3598 93 8305 85 1031 1 80 1 64 21 97 6556 88 7989 80 6728 1 78 1 63 20 92 3028 84 0695 76 5017 ...

Страница 22: ...7 14 5748 14 0079 13 4510 0 93 0 92 18 13 9436 13 4185 12 9017 0 91 0 90 19 13 3431 12 8572 12 3778 0 88 0 87 20 12 7718 12 3223 11 8780 0 86 0 85 21 12 2280 11 8126 11 4011 0 83 0 83 22 11 7102 11 3267 10 9459 0 81 0 80 23 11 2172 10 8634 10 5114 0 78 0 78 24 10 7475 10 4216 10 0964 0 75 0 75 25 10 3000 10 0000 9 7000 0 75 0 75 26 9 8975 9 5974 9 2980 0 76 0 76 27 9 5129 9 2132 8 9148 0 80 0 80 2...

Страница 23: ...2 6112 2 4328 2 17 2 05 62 2 7099 2 5246 2 3498 2 22 2 09 63 2 6232 2 4413 2 2700 2 26 2 13 64 2 5396 2 3611 2 1932 2 31 2 17 65 2 4591 2 2840 2 1195 2 36 2 21 66 2 3815 2 2098 2 0486 2 40 2 25 67 2 3068 2 1383 1 9803 2 45 2 29 68 2 2347 2 0695 1 9147 2 49 2 34 69 2 1652 2 0032 1 8516 2 54 2 38 70 2 0983 1 9393 1 7908 2 59 2 42 71 2 0337 1 8778 1 7324 2 63 2 46 72 1 9714 1 8186 1 6761 2 68 2 50 73...

Страница 24: ...36 0 6303 4 34 3 92 105 0 7641 0 6845 0 6127 4 40 3 97 106 0 7441 0 6661 0 5957 4 46 4 02 107 0 7247 0 6482 0 5792 4 51 4 07 108 0 7059 0 6308 0 5632 4 57 4 12 109 0 6877 0 6140 0 5478 4 63 4 16 110 0 6700 0 5977 0 5328 4 69 4 21 111 0 6528 0 5820 0 5183 4 74 4 26 112 0 6361 0 5667 0 5043 4 80 4 31 113 0 6200 0 5518 0 4907 4 86 4 36 114 0 6043 0 5374 0 4775 4 92 4 41 115 0 5891 0 5235 0 4648 4 98 ...

Страница 25: ...6945 2 66 2 29 7 3276 5302 2818 6731 2422 6139 2 64 2 28 6 3085 2854 2658 8058 2289 2164 2 63 2 28 5 2906 2851 2508 9126 2163 9230 2 61 2 27 4 2738 6777 2368 3158 2046 1961 2 60 2 26 3 2581 6752 2236 3876 1935 5371 2 58 2 25 2 2434 5487 2112 5459 1831 4826 2 56 2 24 1 2296 6230 1996 2509 1733 6024 2 55 2 23 0 2167 2730 1887 0018 1641 4966 2 53 2 22 1 2045 9191 1784 3336 1554 7931 2 52 2 21 2 1932 ...

Страница 26: ...6 1 73 37 315 5682 290 6199 267 4031 1 84 1 71 38 301 1254 277 6976 255 8620 1 82 1 70 39 287 4128 265 4119 244 8745 1 80 1 68 40 274 3905 253 7288 234 4118 1 78 1 66 41 262 0206 242 6161 224 4465 1 76 1 64 42 250 2676 232 0436 214 9529 1 74 1 63 43 239 0983 221 9825 205 9065 1 71 1 61 44 228 4809 212 4060 197 2844 1 69 1 59 45 218 3860 203 2887 189 0648 1 67 1 57 46 208 7855 194 6066 181 2273 1 6...

Страница 27: ...00 0 85 0 84 81 49 7063 48 2057 46 7083 0 85 0 85 82 47 9835 46 4842 44 9911 0 89 0 89 83 46 3286 44 8323 43 3452 0 93 0 92 84 44 7385 43 2468 41 7672 0 96 0 95 85 43 2105 41 7248 40 2540 1 00 0 99 86 41 7386 40 2604 38 7996 1 03 1 02 87 40 3241 38 8545 37 4048 1 07 1 06 88 38 9643 37 5045 36 0668 1 11 1 09 89 37 6569 36 2078 34 7831 1 14 1 13 90 36 3996 34 9622 33 5513 1 18 1 16 91 35 1903 33 765...

Страница 28: ...2 36 2 23 120 14 1376 13 1879 12 2909 2 41 2 27 121 13 7294 12 7955 11 9144 2 45 2 31 122 13 3347 12 4165 11 5510 2 50 2 35 123 12 9531 12 0503 11 2003 2 54 2 39 124 12 5840 11 6965 10 8617 2 58 2 43 125 12 2270 11 3545 10 5348 2 63 2 47 126 11 8817 11 0240 10 2191 2 68 2 51 127 11 5475 10 7046 9 9142 2 72 2 55 128 11 2242 10 3957 9 6197 2 77 2 59 129 10 9112 10 0970 9 3352 2 81 2 63 130 10 6084 9...

Страница 29: ...Dimensional drawings Domestic air conditioner 8 Dimensional drawings 9 Center of gravity 00 4 unit mm unit mm 00 700 245 4 4 ...

Страница 30: ...ion error occurs between the indoor and outdoor units In either case conduct the diagnostic procedure described in the following pages Parameter of primary electronic appliance e r u t c i p r e t e m a r a p e m a n Compressor Rated voltage 220 230V Rated current 4 8A Rated frequency 50 60HZ Fan motor Rated voltage 220 230V Rated current 0 2A Rated frequency 50 60HZ Reactor Rated voltage 220 230V...

Страница 31: ...ipment operates but does not cool or does not heat only for heat pump Check for faulty operation of the electronic expansion valve Set the units to cooling operation and compare the temperatures of the liquid side connection pipes of the connection section among rooms to check the opening and closing operation of the electronic expansion valves of the individual units Diagnosis by service port pre...

Страница 32: ...arging temperature protection Page 41 F8 Trouble record 9 Abnormal of DC motor Page 36 F21 Directly display 10 Abnormal of piping sensor Page 32 F7 Directly display 11 Suction temperature sensor failure Page 32 F6 Directly display 12 Abnormal of outdoor ambient sensor Page 32 F25 Directly display 13 Abnormal of compressor discharge sensor Page 32 F13 Trouble record 16 Lack of refrigerant Page F14 ...

Страница 33: ...or input is more than 4 92V or less than 0 08V during compressor Decision operation Conditions z Note The values vary slightly in some models Supposed Ŷ Faulty connector connection Causes Ŷ Faulty thermistor Ŷ Faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Thermistor resistance check method Remove the ...

Страница 34: ... Data detected by the EEPROM are used to determine MCU Malfunction Detection Malfunction When the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed Ŷ Faulty EEPROM data Causes Ŷ Faulty EEPROM Ŷ Faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Replace the indoor or outdoor mainboard...

Страница 35: ...lty indoor unit PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Check whether terminals on indoor pcb is well Electrify the machine again and turn it on in the cooling operation Measure voltage between the positions 1and 3 of Terminal CN5 on the indoor PCB the voltage is about 90 220vac check whether motor can...

Страница 36: ...ing condition and so on Malfunction Detection Malfunction when the data of EEPROM is error or the EEPROM is damaged Decision Conditions Supposed Ƶ DC fan motor protection dues to the DC fan motor faulty Causes Ƶ DC fan motor protection dues to faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred ...

Страница 37: ...Service diagnosis 37 Domestic air conditioner ...

Страница 38: ... to IPM protection due to over current Decision Ŷ The compressor faulty leads to IPM protection Conditions Ŷ circuit component of IPM is broken and led to IPM protection Supposed Ŷ IPM protection dues to the compressor faulty Causes Ŷ IPM protection dues to faulty PCB of IPM module Ŷ Compressor wiring disconnected Troubleshooting Caution Be sure to turn off power switch before connect or disconnec...

Страница 39: ...pply Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Electrify the machine again and turn it on with the remote controller If malfunctions are reported before or upon the compressor being started up IPM Module is damaged and needs replacing Repair the power supply The system may have been over or under charged with gas...

Страница 40: ...isconnected Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred 1 Check whether Terminal CN23 and CN24 on the outdoor mainboard CN10 and CN11 on IPM module 2 Check whether the connected wire between IPM and outdoor Are they good Electrify the machine again and turn it on Check whether the voltage between 1 and 2 of Te...

Страница 41: ...Supply voltage not as specified Causes Ŷ the IPM module is broken Ŷ the outdoor PCB is broken Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Electrify the machine again and turn it on with the remote controller Check whether the compressor is started normally Is it ok Yes Maybe there is some disturbance NO No 230...

Страница 42: ... occurred Electrify the machine again and turn it on with the remote controller then measure the temperature at the exhaust temperature sensor of the compressor on the outdoor unit The temperature exceeds 110 ć shortly after the machine starts up 1 The cryogen may have been leaked during installation or there may be leakage in the piping system 2 There may be other causes to make the exhaust tempe...

Страница 43: ...utdoor PCB Malfunction Detection Malfunction Ŷ The outdoor PCB broken leads to communication fault Decision Ŷ The indoor PCB broken leads to communication fault Conditions Supposed Ŷ Communication wiring disconnected Causes Ŷ The indoor PCB is broken Ŷ The outdoor PCB is broken Ŷ The Module PCB is broken Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connecto...

Страница 44: ...utdoor pcb is damaged replace it with a new one NO Measure the voltage Between 3 and 4 of IC9 on the Outdoor mainboard with a Multimete The voltage is a constant value of 0V DC to 5V DC The outdoor pcb is damaged replace it with a new one YES NO The outdoor pcb is well and then check the cable If the voltage is a constant value of 0V DC to 5V DC Or the voltage between Communication line red and N ...

Страница 45: ...mpressor Ƶ Faulty PCB Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or parts damage may be occurred Within 3 minutes after the machine is supplied with power and turned on with the remote controller check whether the compressor can start up 1 The wiring of compressor is incorrect or the connection is poor 2 The compressor is damaged At first the co...

Страница 46: ...Dirty heat exchanger Ƶ Faulty heat exchange sensor Ƶ Insufficient gas Troubleshooting Caution Be sure to turn off power switch before connect or disconnect connector or else parts damage may be occurred Electrify the machine again and turn it on with the remote controller check whether the wind temperature is below 65ć The malfunction is reported after the machine has run for some time 1 ǃ Check r...

Страница 47: ... 2436 2283 2861 3109 3030 2889 2734 27 19 2863 2811 2753 2565 3152 3500 3409 3319 3039 30 22 3008 2944 2880 2720 3360 3680 3584 3456 3232 32 23 3180 3089 3078 2909 3549 3903 3764 3653 3396 35 24 3279 3289 3151 3000 3675 4039 3924 3861 3553 cooling value temerature table performance curves outdoor temp 1500 2000 2500 3000 3500 4000 4500 cooling capacity W cooling capacity and indoor outdoor temp cu...

Страница 48: ...2 761 466 666 836 1032 1169 1266 27 19 867 852 834 510 722 925 1109 1295 1387 30 22 885 866 847 526 743 949 1132 1337 1429 32 23 909 883 880 563 785 1007 1227 1414 1502 35 24 911 913 875 580 813 1042 1279 1494 1571 power consumption value temp table performance curves outdoor temp 100 300 500 700 900 1100 1300 1500 1700 power consumption w indoor temp DB WB power consumption and temp curves 10 15 ...

Страница 49: ... 1935 1999 2082 20 1944 2025 2093 25 2049 2104 2234 30 2196 2341 2478 35 2386 2499 2643 38 2589 2683 2862 40 2911 3025 3210 43 3283 3419 3535 performance curves cooling discharge pressure table indoor temp 1000 1500 2000 2500 3000 3500 4000 10 15 20 25 30 35 38 40 43 discharge pressure Kpa outdoor temp DB WB cooling discharge pressure and temp curves 21 15 27 19 35 24 ...

Страница 50: ...4 1004 15 746 873 1014 20 753 891 1024 25 793 900 1045 30 835 947 1056 35 843 956 1111 38 887 986 1134 40 976 1085 1247 43 1074 1171 1360 performance curves indoor temp cooling suction pressure table 350 550 750 950 1150 1350 1550 10 15 20 25 30 35 38 40 43 suction pressure Kpa outdoor temp DB WB cooling suction pressure and temp curves 21 15 27 19 35 24 ...

Страница 51: ...48 2238 2064 7 8 3008 2727 2535 2 1 3216 2838 2574 7 6 3130 2890 2572 12 11 2802 2581 2250 18 16 2292 2161 1895 24 20 1839 1653 1474 indoor temp humidity 46 heating capacity and indoor outdoor temp table performance curves 0 500 1000 1500 2000 2500 3000 3500 heating capacity W heating capacity and indoor outdoor temp curves 10 20 27 outdoor temp DB WB ...

Страница 52: ...771 10 827 862 905 7 8 864 919 965 2 1 897 944 992 7 6 831 866 909 12 11 588 632 696 18 16 437 485 534 24 20 308 343 377 indoor temp humidity 46 power consumption value temp table performance curves 0 200 400 600 800 1000 1200 15 10 7 8 2 1 7 6 12 11 18 16 24 20 cooling capacity w outdoor temp DB WB heating capacity and indoor outdoor temp curves 10 20 27 ...

Страница 53: ...22 3030 7 8 3127 3344 3528 2 1 3329 3626 3813 7 6 3358 3520 3615 12 11 3292 3414 3580 18 16 3067 3210 3296 24 20 2603 2728 2811 performance curves heating discharge pressure table indoor temp 1000 1500 2000 2500 3000 3500 4000 15 10 7 8 2 1 7 6 12 11 18 16 24 20 discharge pressure Kpa outdoor temp DB WB heating discharge pressure and temp curves 10 20 27 ...

Страница 54: ... 8 494 533 553 2 1 613 652 672 7 6 746 785 805 12 11 847 886 906 18 16 1014 1053 1073 24 20 1200 1239 1259 performance curves heating suction pressure table indoor temp 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 15 10 7 8 2 1 7 6 12 11 18 16 24 20 suction pressure Kpa outdoor temp DB WB heating suction pressure and temp curves 10 20 27 ...

Страница 55: ...56 Do C omestic air ircuit Diagra conditioner ams r 12 Circuit diagrams 12 1 Outdoor unit control board circuit diagrams ...

Страница 56: ...57 Do C omestic air ircuit Diagra conditioner ams r ...

Страница 57: ...ams Domestic air conditioner Sincere Forever Haier Group Haier Industrial Park No 1 Haier Road 266101 Qingdao China_ Http www haier com Edited by Signed by Approved by Shi Haiyan Yang Xiaodong Yang Wenjun Wu Hongjin ...

Страница 58: ...roduct Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to service or Repair the product or products dealt with in this service information by anyone else could result in serious injury or death WARNING 2015 Qingdao Haier Air Conditioner General corp Ltd All rights reserved Unauthorized copying and distribution is a violation o...

Страница 59: ...Removal Procedure 1 Removal of Outdoor panel RPHVWLF LU RQGLWLR ...

Страница 60: ...Removal Procedure 2 Domestic Air Condition ...

Страница 61: ...4 Removal Procedure 3 Domestic Air Condition ...

Страница 62: ...Removal Procedure 2 Removal of Electrical Box RPHVWLF LU RQGLWLR ...

Страница 63: ...Removal Procedure 3 Removal of Fan and Fan Motor RPHVWLF LU RQGLWLR ...

Страница 64: ...Removal Procedure 4 Removal of fan motor brcked and partition RPHVWLF LU RQGLWLR ...

Страница 65: ...Removal Procedure 7 Domestic Air Condition ...

Страница 66: ...Removal Procedure 5 Removal of compressor and heat exchanger RPHVWLF LU RQGLWLR ...

Страница 67: ...Removal Procedure 9 Domestic Air Condition ...

Отзывы: