Service diagnosis
4
5
Domestic air conditioner
(
A
)
NO
YES
Yes
Check the indoor mainboard.
No
If the voltage is of a constant
value of 0V DCto5V DC
YES
Measure the voltage between Jumpers 3 and
4 of IC1 on the indoor mainboard with a
multimeter.
NO
The outdoor mainboard is damaged;
Replace them with a new one.
Measure the AC voltage between positions 1
and 3 on the terminal of outdoor unit with a
multimeter.
If 230VAC is available but 310DC not,
the power module is damaged, replace it
with a new one.
Test the outdoor power supply (230VAC
and +310VDC) with a multimeter.
The outdoor mainboard is damaged; replace
it with a new one.
The indoor mainboard is damaged; replace
it with a new one.
If the value varies between 0 and 80 VAC,
the outdoor mainboard is damaged, replace it
with a new one.
If the value is constant at about 30V, the
indoor mainboard is damaged, replace it with
a new one.
If both 230VAC and 310DC are
available, measure
+12V(from7805) is available.
Содержание 1U18TR4ERA
Страница 11: ...Pinping diagrams Domestic air conditioner 4 Piping diagrams 9 EEV EEV ...
Страница 12: ...Operation range Domestic air conditioner 5 Operation range 10 ...
Страница 63: ...Domestic air conditioner Removal of procedure 1 Removal of Outdoor panel 1 ...
Страница 64: ...Domestic air conditioner Loosen the top panel screws 1 2 Lift the top panel Removal of procedure 2 ...
Страница 65: ...Domestic air conditioner Loosen the screws and pull the panel Removal of procedure 3 ...
Страница 66: ...Domestic air conditioner 2 Removal of Electrical Box Removal of procedure 4 ...
Страница 67: ...Domestic air conditioner 3 Removal of Fan and Fan Motor Removal of procedure 5 ...
Страница 68: ...Domestic air conditioner 2 Loosen the fixing screws and remove the motor Removal of procedure 6 ...
Страница 69: ...Domestic air conditioner 4 Removal of Fan Motor Bracket and Partition Removal of procedure 7 ...
Страница 70: ...Domestic air conditioner and remove the reactor Loosen the screw Removal of procedure 8 ...