10 Heating 

anticipator 

 
This item adjusts the tendency of the thermostat to turn the heating unit off before the desired heat setting is 
reached.  This is done to avoid overheating the air while the walls and furniture catch up.  A setting of 0 will 
disable this feature.   
 
 0 

 

No anticipation

 

 

3-5  

Normal 

anticipation

 

 

10  

Maximum 

anticipation 

 
The following settings are recommended: 
 
Forced air systems: 4 

 

Radiant systems: 6 
 
A lower setting will decrease the tendency to turn off the heating system before the desired heat setting is 
reached.  If the heating system response time is slower, as are most radiant heating systems, a higher number 
will help maintain an even space temperature. 
 
The default setting is 4. 
 
11 

Cooling minimum on/off time (minutes) 

 
This item is used to limit the on and off times of the cooling system.  When the cooling system starts, it must 
remain on for the minimum time set by this item.  When the cooling system turns off, it must remain off for a 
minimum time set by this item.   
 

Setting 

Cycles per hour (maximum) 

5 6 
6 5 
7 4 
8 3.7 

10 3 

 
The recommended setting is 8 minutes.  A higher setting may be appropriate for buildings with low heat 
loss/gain. 
 
The default setting is 8. 
 
12 

Heating minimum on/off time (minutes) 

 
This item is the same as the “Cooling minimum on/off time”, but for the heating system. 
 
The default setting is 8. 
 
13 Not 

used

 

Содержание RC-80 Omnistat

Страница 1: ...country in which this equipment is to be installed INSTALLATION Before installing this thermostat 1 Read all of the installation instructions carefully 2 Read the Owner s Manual carefully 3 Ensure th...

Страница 2: ...TING When mounting the RC 80 grasp the thermostat by the sides avoiding the keys and unsnap the base from the face Holding the base to the wall so that the word TOP is upright and facing you 1 Mark th...

Страница 3: ...tion See Figures 10 11 Insert the cable into the connector on the thermostat circuit board marked COMM Upon completion of wiring the thermostat push all excess wiring into the hole in the wall Plug th...

Страница 4: ...ok up to live circuits An accidental connection to a component on the thermostat circuit board could cause damage to the thermostat Figure 4 Thermostat power up for test or demonstration purposes Note...

Страница 5: ...ons Figure 6 Single stage cool only thermostat Common wire is required to use the display backlight in the RC 80B Also use if heat cool or fan relay cannot supply 15mA to power thermostat without acti...

Страница 6: ...mper to the TIMED position between the middle and left pin on the connector See Figure 9 2 To configure the display backlight to always be on set the JP2 Select Backlight Mode jumper to the ON positio...

Страница 7: ...ter unit comes on Set the mode to OFF Ensure that the heat goes off 6 Set the Mode to COOL Use the down arrow key to lower the desired temperature setting below the current temperature Ensure that the...

Страница 8: ...e of the item number 3 Press the Prog key to advance to the next item 4 Press the Hold key to return to the previous item 5 Use the arrow keys to change the value of each item 6 Do not set the values...

Страница 9: ...ns 0 Auto changeover no fan with heat 1 Auto changeover fan on with heat 4 Manual changeover no fan with heat 5 Manual changeover fan on with heat 12 Heat only no fan with heat 13 Heat only fan on wit...

Страница 10: ...6 Heat setpoint limit This item is used to limit the temperature setting in heat mode The desired heat setting can never be set above this setting The default setting is 91 07 Not used 08 Not used 09...

Страница 11: ...is slower as are most radiant heating systems a higher number will help maintain an even space temperature The default setting is 4 11 Cooling minimum on off time minutes This item is used to limit t...

Страница 12: ...t of time the system fan has been running When this setting reaches 0 the thermostat will display a reminder to replace the filter The setting is the amount of days 24 hours of system operation before...

Страница 13: ...thermostat has been preprogrammed with energy saving settings recommended under the EPA Energy Star program When used with remote systems HAI recommends that the thermostat be configured as non progra...

Страница 14: ...14 4 Note Do not connect the red COMM cable wire to 12V Figure 10 Hookup to an HAI system Additional thermostats are connected in parallel They may be connected in home run or daisy chain configuratio...

Страница 15: ...be set to 24 Run a two conductor wire from the remote system or remote switch to the thermostat location Make the connections using supplied wire splices See Figure 11 Red and yellow wires are not us...

Страница 16: ...at keys for test remove jumper SYMPTOM ACTION TO TAKE 1 Check COMM connector and wiring 2 Check thermostat address setting 3 Check communications mode setting Control By Remote System Not Working 4 Ch...

Отзывы: