Example Messages (Data shown in parenthesis are in Hex)
Host:
Poll thermostat 1 for Group 1 data:
RA(01), DL/MT(02), CS(03)
Thermostat 1: RA(81), DL/MT(63), low setpoint(xx), high setpoint(xx), mode(xx),
fan(xx), hold(xx), current temperature (xx), CS(xx)
Host: Broadcast time:
RA(00), DL/MT(41), start register(41), seconds(xx), minutes(xx) , hours(xx),
CS(xx)
Thermostat(s): no reply, it was a broadcast message.
The host should wait a minimum of 90ms before transmitting next message.
Host: Set cooling setpoint on thermostat 5
RA(05), DL/MT(21), start register(3B), setpoint(xx), CS(xx)
Thermostat 5: RA(85), MT/DL(00), CS(85) (acknowledge)
Host:
Set the energy custom message to “CUSTOM MESSAGE” on thermostat 1.
RA(01),DL/MT(21), start register(AF) , ‘C’(43), ‘U’(55), ‘S’(53) , ‘T’(54),
‘O’(4F), ‘M’(4D), ‘ ‘(20), ‘M’(4D), ‘E’(45), ‘S’(53), ‘S’(53), ‘A’(41), ‘G’ (47),
‘E’ (45), ETX (03), CS(34)
Thermostat 1:
RA(81), MT/DL(00), CS(81) (acknowledge)
INTERNAL REGISTERS (RO = READ ONLY)
Setup:
0
(RO) Communication address of the thermostat (1-127)
1
(RO) Communication mode baud (0=300, 1=100, 42=1200, 54=2400, 126=9600, 211=Day/Night)
2
(RO) System type (0/1=Heat/Cool-Auto, 4/5= Heat/Cool-Manual, 12/13=Heat only, 20=Cool
only, odd=Fan on with heat, even=Fan off with heat)
3
Display Options (Bit 0: 0=Celsius, 1=Fahrenheit; Bit 1: 0=12hour, 1=24hour; Bit 2: 0=Advanced
display, 1=Simple display)
4
Calibration offset (+\- 30 Omnitemp units)
5
Low Cool Limit (51-91 Omnitemp units)
6
High Heat Limit (51-91 Omnitemp units)
7
Energy Efficient Control (Turn on, 1 or off, 0 the EEC)
8 Current
OMNI
version
9
Cool Anticipator (1-10, only valid in 1 stage units, 1=AC comes on the cycles air frequently,
10=infrequently)
10
Second stage differential (for multi stage units)
11
Cooling cycle time (2-30 minutes, ignored if used separate on/off times)
12
Heating cycle time (2-30 minutes, ignored if used separate on/off times)
13
Third stage differential (for multi stage units)
14
Clock adjust (+/- 30 seconds per day, 0=-30, 60=+30)
15
Days remaining for filter reminder
16
(RO) System run time, current week - hours
17
(RO) System run time, last week - hours
Copyright © 2008 Home Automation, Inc.
All Rights Reserved
Page 6