11
Fitting the cable(s) with / without the earthing kit
Location for a 2
nd
charging terminal
Location for
the 1
st
charging
terminal
50 mm² bare
earth cable
• Without the earthing kit
• With the earthing kit
Equipotential bonding must be run between the terminal, the pedestal and the base.
The pedestal base and the charging
terminal must be connected to each
other with one
or more earth
cables
Earth cable to connect to the
pedestal base and buried fully
unwound in the ground
13
13
13
The pedestal base and the charging
terminal must be connected to each
other with one or more earth cables
Cable for a 2
nd
charging terminal
Cable for the 1
st
charging terminal
Equipotential bonding must be run between the terminal, the pedestal and the base.
For ease of installation,
allow for at least 500 mm
of bare earth cable above
ground.