VE24

AH

 Garage Board

Instructions/Data Sheet

This Garage Board and Hager devices conform with the 
following standards:
Consumer Unit: BS EN 61439-3 including Annex ZB.

 

Residual Current Circuit Breaker (RCCB): BS EN 61008-1

 

Miniature Circuit Breaker (MCB): BS EN 60898-1

Installation Instructions:

All product(s) must be installed by a suitably competent electrician
Giving consideration to their intended use and in accordance with the 
current edition of BS 7671 (IET Wiring Regulations).

The Electricity at Work regulations and the Health and Safety at Work Act 
shall be complied with.

Only equipment and arrangements specified in Hager’s technical 
documentation / catalogue shall be used.

Install in the horizontal plane only.

Important notice:
To prevent potential overheating from loose connections the installer 
shall check connections are tight to the torque levels stated in these 
instructions prior to energizing this board. This check should include 
factory made connections which may have loosened in transit.

Tightening torque values to be applied (Nm)

RCCB’s 40A: 2.8 Nm
MCBs: 2.8 Nm
Earth & Neutral terminal bar connections: 2.0 Nm
Single conductors below 1.5mm2 need to be doubled back in the 
terminal bar

Good workmanship and proper materials must be applied by the installer. 

Note: Only BASEC approved cable should be used
1.0mm

2

 to 10mm

2

 for outgoing cables 

up to 10mm

2

 for incoming live cables

Single conductors below 1.5mm2 need to be doubled back in the terminal bar.

Fig 1. 

VE24AH

IP55

Guidance Notes:

The total load must not exceed the rating of the incoming device or the assigned assembly rating (InA) whichever is the lower. Each neutral and earth 
connection must correspond numerically to its outgoing way. Additional blanks (ref. JK01B) are available to cover spare ways.

A pack is provided to label this garage board, please consult us for spares or replacements.
Operating Instruction leaflet is provided overleaf. This leaflet should be left for the end user.
Single conductors below 1.5mm2 need to be doubled back in the terminal bar.
Precautions need to be taken to prevent faults to earth on the supply side of the RCD (as per BS7671 regulation 531.4.1)

IP Ratings:

Cable access into the garage board must maintain the integrity so far as reasonably practicable. In essence, for surfaces accessible after installation, this 
means maintaining the requirement for the horizontal top surface of the enclosure to provide a degree of protection as detailed in fig 1 and fig 2. For rear 
cable access, the minimum number of knockout(s) shall be removed.

Warranty

This distribution board is offered with a 24 month warranty against defective material or manufacture. If a warranty claim is necessary, please call the 
technical support number given at the bottom of the page and we will be pleased to help.

For dimensional information and weights please consult the Hager catalogue.

Fitting Hager MCBs and RCBOs:

Only equipment and arrangements specified in Hager’s technical 
documentation / catalogue shall be used.
1. Isolate the electrical supply from the Garage Board.
2. Remove the front cover.
3. Fully slacken the lower terminal of the device.
4. Fully open the bottom device clip (fig 1.)

5.  Locate the device onto the din rail, and busbar. Ensure that the 

busbar tooth is within the device terminal cage.

6.  Close the bottom device clip. 
7.  While holding the device firmly onto the busbar, fully tighten the lower 

terminal screw.

8.  After fitting all outgoing devices and connecting all outgoing cables, 

please check the tightness of all cable connections. This should 
include all factory made connections, which may have loosened 
during installation or transit.

fig 1.

GB

1

ZD0630 - Issue 

6

 0

1

-

2

1

Z

D

0

6

3

0

Z

D

0

6

3

0

3

ZD0630 - Issue 

6

 0

1

-

2

1

MCB

tripped

Use circuit as 

normal

Use circuit as 

normal

Unplug faulty

appliance until

repaired. Reset device.

Other appliances may

be used

Try & reset device once

Try & reset device once

Turn OFF 

all MCBs devices

Reset RCCB

Turn ON MCBs 
devices one at a time
until RCCB trips again,
identifying faulty circuit

Unplug all 
appliances from 
circuit and reset
device / replace fuse*

Plug in & switch on 
appliances one at a time
until device trips / blows, 
identifying faulty appliance

What device 

is it?

Does device 

stay ON?

Does device 

stay ON?

Does device 

stay ON?

Does device 

supply socket

outlets

Does device 

stay ON?

START

YES

YES

YES

YES

YES

MCB 

or

RCBO

RCCB

NO

NO

NO

NO

NO

T

 

MCB 

RCCB

MCB

Dimensions - Garage Board

Dimensions 
(mm)

Enclosure Size

VE24

A

H

A

165

B

190

C

N/A

D

114

Отзывы: